7SR23 (DAD)

High Impedance Protection

For internal use only / Siemens


Protection
AG 2012.
noticeAll
/ Copyright
rights reserved.
notice
Product Updates

2013/01 2435H85014R7c-1a Revised file handling during shutdown.

2012/07 2435H85014R7b-1a First Release

Protection notice / Copyright notice


Page 2 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Structure of the Electrical Energy System Location of Motors

GENERATORS

Busbars
Auto-Transformers
TRANSMISSION NETWORK Interconnected Feeders

Busbars
Interconnectors
Double Wound Transformers
DISTRIBUTION Radial Feeders
NETWORK Ring Mains
Embedded Generation
Motors

G M

UTILISATION

Protection notice / Copyright notice


Page 6 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Applications of 3-Phase High Impedance Protections

Protection notice / Copyright notice


Page 7 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Applications of High Impedance Restricted Earth Fault Protection

Protection notice / Copyright notice


Page 8 05/17/17 Kevin Hearfield Reyrolle Protection Devices
7SR23 MLFB - Hardware

Protection notice / Copyright notice


Page 10 05/17/17 Kevin Hearfield Reyrolle Protection Devices
7SR23 Construction

High impedance specific hardware

Alpha Numeric LCD Display


4 lines, 20 characters
Backlit

Pushbuttons
Menu navigation x5
Programmable from Fascia

LEDs: HEALTHY TRIP PICKUP


User programmable:
x8 (E6 case) or x16 (E8 case)

Standard Data Comms Ports


Front USB-B Port, Rear RS485 Port

Optional Rear Data Comms Ports


F.O. ST connectors (x2) and IRIG-B
RS485 (x1) and IRIG-B
RS232 (x1) and IRIG-B
2 x Optical Duplex LC connectors (2 transmitters and 2 receivers)
2 x Electrical RJ45 connectors
Protection notice / Copyright notice
Page 11 05/17/17 Kevin Hearfield Reyrolle Protection Devices
7SR23 DAD Wiring Diagram

Protection notice / Copyright notice


Page 12 05/17/17 Kevin Hearfield Reyrolle Protection Devices
7SR23 Protection Functions

Relay and external components can be configured to provide different arrangements of


high impedance protection SYSTEM CONFIG > Relay Config:
User
3P + REF
3P + EF
REF1 + REF2

Protection notice / Copyright notice


Page 18 05/17/17 Kevin Hearfield Reyrolle Protection Devices
SYSTEM CONFIG > Relay Config

Protection notice / Copyright notice


Page 19 05/17/17 Kevin Hearfield Reyrolle Protection Devices
7SR23 and 7SG12 Equivalence

Using the connections shown overall 3-


phase differential protection is provided in
the same way as provided by the 7SG12
DAD N relay.

Protection notice / Copyright notice


Page 20 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Basics of Circulating Current Differential Protection

Protection notice / Copyright notice


Page 21 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Comparison of Current Differential Protections

Protection notice / Copyright notice


Page 22 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Busbar Current Distribution During Faults

Protection notice / Copyright notice


Page 23 05/17/17 Kevin Hearfield Reyrolle Protection Devices
High Impedance Principles

Performance Ensured by Calculation:


Stability ensured for worst case:
One CT saturated, all other CTs transform perfectly

Operating current (fault setting) adjusted according to requirements

Proven, simple, high performance protection


Protection notice / Copyright notice
Page 29 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Magnetising Curve of Class X Current Transformer

Protection notice / Copyright notice


Page 30 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Calculation Procedure

Protection notice / Copyright notice


Page 31 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Data Required for Typical Calculation

SYSTEM DATA
Current Transformers
Ratio 500/1
SYSTEM DATA
VK 400V
Rated Voltage: 132kV
imag @ VK 100mA
Swgr Rating: 3500 MVA (15300A)
Secy Res. 0.7 Ohms

RL max2 Ohms

F2: Internal Fault


BUSBAR 1 BUSBAR 2

F1: External Fault


BBZ 1 CHECK BBZ 2

Overall fault setting between 10% and 50% of minimum fault current
The fault setting of the check zone and the minimum fault setting of the individual discriminating zones shall be equal to
approximately 50% of the full load rating of the associated busbar.
The maximum fault setting of the individual discriminating zones shall not exceed of the full load rating of the associated
busbar.
When two or more sections of busbar are connected together via section disconnectors and the combined discriminating
zone gives rise to a fault setting in excess of the full load current rating of the associated busbar, the minimum fault
setting of the individual discriminating zones shall be reduced below 50% to achieve a combined fault setting equal to or
less than the full load rating of the associated busbar.
Protection notice / Copyright notice
Page 32 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Circuit Components for High Impedance Protection

Protection notice / Copyright notice


Page 45 05/17/17 Kevin Hearfield Reyrolle Protection Devices
High Impedance Component Box - Option

Standardises component ordering for high impedance schemes ordering,


engineering and installation simplified.

E6 case suitable for panel mounting includes:


Stabilising resistors
Voltage limiting Varistors

500R, 1K or 2K user selectable stabilising resistance, selected by external


connections.

Software settings tool available on request.

Protection zone short circuiting relay

Protection notice / Copyright notice


Page 46 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Integrated Solution

Protection notice / Copyright notice


Page 47 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Settings Software

Applicable to all high impedance scheme


arrangements.

Provides guidance on appropriate fault


level setting (primary operate current)
selection.

Settings recommendations include:


Component box stabilising resistor
value selection.
Differential protection current setting.
CT Supervision current setting.

Available on request.

Protection notice / Copyright notice


Page 49 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Considering CT Location Overlapping CTs

Protection notice / Copyright notice


Page 51 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Considering CT Location Non Overlapping CTs

Protection notice / Copyright notice


Page 52 05/17/17 Kevin Hearfield Reyrolle Protection Devices
New feature - Sustained Fault Monitor

The 7SR23 is connected to


measure unbalance current.
The sustained flow of fault
current after a differential
protection operation indicates
either a failed CB condition or
fault in a protection blind spot.

Where one of the circuit


breakers fails to trip the relay
cannot inherently identify the
failed CB, it can measure
continued flow of differential
current only.

Can be used in conjunction with


circuit position monitoring.

Protection notice / Copyright notice


Page 53 05/17/17 Kevin Hearfield Reyrolle Protection Devices
New feature Circuit Position Monitoring

CB position monitoring can utilise either the


IEC61850 comms or be hardwired between
binary inputs of the 7SR23 and CB auxiliary
switches, in effect producing a replica of the
busbar.

This feature can be used for example on


double busbar installations to issue trip
outputs to the relevant circuit breakers. Back-
tripping logic from circuit CB fail inputs can
also utilise these busbar replica tripping
outputs.

Where differential current continues to flow


and CB status indicates that all CBs are open
then this indicates a blind-spot fault has
occurred.

Protection notice / Copyright notice


Page 54 05/17/17 Kevin Hearfield Reyrolle Protection Devices
New feature - Zone In/Out Switching

In/Out switching of the high impedance protections is provided to aid commissioning and testing.
When the Zone Switch Out feature is initiated the operation of the differential protection and CT
supervision monitoring is inhibited.
User selected output contacts assigned to CT50 are operated when Zone Switchout CT Shorting is
selected to Enabled. The connection of these contacts in the protection scheme ensures that any
unbalance current in the differential circuit does not flow through the relay/stabilising resistor.

Protection notice / Copyright notice


Page 55 05/17/17 Kevin Hearfield Reyrolle Protection Devices
User Interface Fascia Menu Structure

Consistent user interface for all 7SR relays.

Compatible with Reydisp EVO and MANAGER.

Settings files and templates available from


website.

Protection notice / Copyright notice


Page 59 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Data Storage

Protection notice / Copyright notice


Page 61 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Easy configuration with Reydisp software
(Free download)

Reydisp Software Interface


- View and download settings
- Disturbance records
- Relay events
- Fault Records
Language Editor Change the text descriptions in
the relay to suit your preferences within the
European character set.

Communications Editor - Configure the Data


Communications Files in the relay to match your
control system requirements. Protocols:
DNP 3.0
MODBUS RTU
IEC60870-5-103

Protection notice / Copyright notice


Page 62 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Reydisp Manager for 61850 configuration / Graphical Logic
(Free download)

Manage the project


Add devices
Import third party ICDs
Add Station
Add time sever
Mange updates
Manage logic
Manage Settings
Export files
Update device

Reylogic Express
Setting Editor

Protection notice / Copyright notice


Page 63 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Serial Data Communications

Standard Data Comms Ports


Front USB-B Port
Rear RS485 Port

Optional Data Comms Ports


2 x Fibre Optic ports, with ST Connectors Optimised
for 62.5/125m Glass Fibres
RS232 Port: 9 pin D Connector
RS485 Port: 2 wire with integral Terminating Resistor

Protocols
IEC 60870-5-103, MODBUS RTU, DNP-3, ASCII

Each port can be set for local or remote access

REYDISP is compatible with IEC 60870-5-103 and can be


used on all ports

IRIG-B with BNC connector


Protection notice / Copyright notice
Page 64 05/17/17 Kevin Hearfield Reyrolle Protection Devices
Optional Ethernet communications - IEC61850

Integration of the EN100 module


established in Siprotec devices with
many worldwide installations.

Simplified tool chain using Reydisp


Manager and DIGSI 4 system
configurator
EN100
2 x Optical Duplex LC connectors
(2 transmitters and 2 receivers) Functions
2 x Electrical RJ45 connectors Object Modelling
GOOSE Messaging
Buffered and Unbuffered Reporting
SNTP Tine Synchronising
Disturbance Record File Transfer
Redundancy
5 Clients Supported

Protection notice / Copyright notice


Page 65 05/17/17 Kevin Hearfield Reyrolle Protection Devices
7SR23: Further Information

www.siemens.com/energy
Information Available:
Catalogue sheets

Technical Manual:
1. Description of Operation
2. Settings, Configuration and Instruments
3. Performance Specification
4. Data Communications
5. Installation
6. Commissioning
7. Applications Guide
8. IEC61850 MICS, PICS, PIXIT files

Wiring diagrams
Panel drilling drawings

Reydisp Evolution settings files


Reydisp Manager templates

Relay firmware

High Impedance Applications Guide