Sei sulla pagina 1di 39

MiCOM P124 Range

Jean-Philippe PETIT
Products Marketing

Lattes, April 2005


MiCOM P124 Range

3 > MiCOM P124 Range - December 2004 3


MiCOM P124 Range

Self / Dual Powered overcurrent relays

4 > MiCOM P124 Range - December 2004 4


MiCOM P124 Range

Application:

Industrial plants
Utilities networks and substations
Main or backup protection relay

5 > MiCOM P124 Range - December 2004 5


MiCOM P124 Range

Two models for a global answer

3 phases + earth O/C Self-powered Relay


3 phases + earth O/C Dual-powered Relay

6 > MiCOM P124 Range - December 2004 6


P124 Self Powered
Single line diagram
CB Trip via Striker
Busbar

Striker
P124 Self Powered
52 Possible Tripping
Output for signaling or Tripping coil
RL1
Striker via external device

RL0 Watchdog
49
Phase CTs 3

51 50

Earth CT 51N 50N

RS 232 Setting Software


front Port

7 > MiCOM P124 Range - December 2004 7


P124 Dual Powered
Single line diagram
CB Trip via Striker
Busbar

Striker
P124 Dual Powered
52
Output for Tripping signaling
Striker 86 RL1 or trip coil

37 49 RL0 Watchdog

3 RL 2
Phase CTs 51 50 Programmable
RL 3
RL 4 Logic
RL 5 outputs
51N 50N RL 6
Earth CT
L1 46 50BF RS 485 Remote control
Programmable L2 rear port
Logic L3
L4 RS 232 Setting Software
inputs 79
L5 front port

U aux
8 > MiCOM P124 Range - December 2004 8
P124 Dual Powered
Single line diagram
CB Trip via CB Coil Possible CB Trip
Busbar back up via Striker

CB coil P124 D
52 Striker Striker
Trip Output
output RL1 86
relay

Watchdog
U aux 37 49 RL0

3 RL 2
Phase CTs 51 50 Programmable
RL 3
RL 4 Logic
RL 5 outputs
51N 50N RL 6
Earth CT
RS 485
L1 46 50BF Remote control
Programmable L2 rear port
Logic L3 RS 232
inputs L4 79 front port Setting Software
L5

U aux
9 > MiCOM P124 Range - December 2004 9
MiCOM P124 Range

The striker
Function
Trip the mechanical command of the circuit breaker

Principle
Transform few millijoules electrical impulse into daN/cm
mechanical power

10 > MiCOM P124 Range - December 2004 10


MiCOM P124 Range
The striker

Striking pin

Cover

Coil
Mobile magnet

Spring

Fixed magnet

P124 command: Pulse 20mJ/ >12V


11 > MiCOM P124 Range - December 2004 11
MiCOM P124 Range

Self Powered relay operation

Minimum level of current required for relay powering:


0.2IN on at least one phase
Frequency: 50Hz or 60Hz

12 > MiCOM P124 Range - December 2004 12


MiCOM P124 Range

Burden, phase & earth: In 1A or 5A


2.5 VA
CT recommandations
5VA 5P10 or 5VA 10P10
Secondary 1A or 5A

13 > MiCOM P124 Range - December 2004 13


MiCOM P124
Functions

14 > MiCOM P124 Range - December 2004 14


MiCOM P124 Range
Protection Functions

FUNCTIONS ANSI P124 Self P124 Dual


codes Powered Powered

Non directional Earth fault MORE 50N/51N X X

Non directional 3 phase O/C MORE 50/51 X X

Thermal overload MORE 49 X X

Undercurrent MORE 37 X

Cold load pick-up MORE X

15 > MiCOM P124 Range - December 2004 15


MiCOM P124 Range
Protection Functions

FUNCTIONS ANSI P124 Self P124 Dual


codes Powered Powered

Negative phase sequence 46 X


MORE
Overcurrent

Setting Groups MORE 1 2

Broken Conductor MORE X

16 > MiCOM P124 Range - December 2004 16


MiCOM P124 Range
Automation Functions

FUNCTIONS ANSI P124 Self P124 Dual


codes Powered Powered

Output relay latching MORE 86 X

Selective relay scheme logic MORE X

Blocking logic MORE X

Circuit breaker fail detection MORE 50 BF X

Circuit breaker monitoring MORE X

Auto-reclose (4 shots) MORE 79 X

17 > MiCOM P124 Range - December 2004 17


MiCOM P124 Range
Ancillary Functions

FUNCTIONS P124 Self P124 Dual


Powered Powered

Measurements (true RMS value) X X

Peak and average values MORE X X

Event record MORE X

Fault record MORE X X

Disturbance record MORE X

18 > MiCOM P124 Range - December 2004 18


MiCOM P124
Physical Features

19 > MiCOM P124 Range - December 2004 19


MiCOM P124 Range
Housing

MiCOM shallow case with MIDOS connectors


4U hight (152 mm)
Front plate face 177 mm
140.8 mm depth
30 TE width (155 mm)
Same case and wiring for Self- & Dual-Powered model

Withdrawable active part with integral CT shorting

20 > MiCOM P124 Range - December 2004 20


Rear face MiCOM P124

Earth
Housing

2 blades 4,8mm x 0,8mm

+ 1 M4 screw

by connection
point

21 > MiCOM P124 Range - December 2004 21


User Interface: Self Powered type

2 tactile button keypad 2 X 16


for reading and clearing alphanumerical
alarms and messages backlit display

Trip flag
indicator

Retractable flaps
Healthy led help to withdrawn
the active part
5 tactile
button
keypad for
setting
and
consulting
P124 S
Menu
RS 232

22 > MiCOM P124 Range - December 2004 22


MiCOM P124 Range

Battery Box MiCOM E1


Battery box

To RS 232 124 Relay


Input for
external DC
supply
12Vdc- 24Vdc

23 > MiCOM P124 Range - December 2004 23


User Interface: Dual Powered type

2 tactile button keypad


for reading and clearing 2 X 16
alarms and messages alphanumerical
backlit display

1Trip & 4 free


flags
indicators

Retractable flaps
Trip led help to withdrawn
Alarm led the active part
Healthy led
Equipment failure led

4 Programmable
leds
5 tactile
button
keypad for
setting
RS 232
and P124 D
consulting Battery Menu
24 > MiCOM P124 Range - December 2004 24
MiCOM P124 Range
Current Inputs

Phase & earth 1 or 5 Amps: defined by ordering code

Overload withstand:
1 second @ 100 In
2 seconds @ 40 In
Continuous @ 3 In

25 > MiCOM P124 Range - December 2004 25


MiCOM P124: Dual Powered type
Auxiliary Supply

3 ranges:
24 Vdc to 60 Vdc
48 Vdc to 150 Vdc
130 to 250 Vdc/100 to 250 Vac (50/60 Hz)

Burden: 3W dc, 6VA ac

Variation: 0.8 to 1.2 Uaux

Ripple: 12%

Supply interruption: 50ms

26 > MiCOM P124 Range - December 2004 26


MiCOM P124 Range
Digital Inputs & Outputs

Programmable Programmable Trip Trip WatchDog


Logic Inputs Logic Outputs output output Change
including 2 for for CB over (RL0)
Change-over striker coil
Change
over (RL1)

Self Powered 0 0 1 1 1

Dual Powered 5 5 1 1 1

27 > MiCOM P124 Range - December 2004 27


MiCOM P124 Dual Powered
Digital Inputs

Identical range to Uaux range selected with the ordering


code (dc only):
24 to 60 Vdc
48 to 150 Vdc
130 to 250 Vdc

Optically isolated inputs

28 > MiCOM P124 Range - December 2004 28


MiCOM P12x Range
Trip Output Relay RL1

Make: 30 A and carry for 3s

Carry: 8 A continuous

Break:
300 Vdc: 50W resistive or 25W inductive (L/R = 40 ms)
220 Vac: 5 A , P.F = 0.5

29 > MiCOM P124 Range - December 2004 29


MiCOM P12x Range
Output Relays (RL2 to RL6 + WD)

Make: 30 A and carry for 3s

Carry: 5 A continuous

Break :
135 Vdc: 0,3 A (L/R = 30 ms)
250 Vdc: 50W resistive or 25W inductive (L/R = 40 ms)
220 Vac: 5 A , P.F = 0.6

30 > MiCOM P124 Range - December 2004 30


MiCOM P124
High Voltage Withstand &
Environment

31 > MiCOM P124 Range - December 2004 31


MiCOM P124
Atmospheric Environment

Temperature IEC 60255-6


Operating: - 25C + 55C
Storage: - 25C + 70C

Humidity: IEC 60068-2-3


56 days at 93 %

32 > MiCOM P124 Range - December 2004 32


MiCOM P124
Electrical Environment

Dielectric withstand: IEC 60255-5


Impulse voltage: IEC 60255-5
Fast transient: IEC 61000-4-4
EMC: IEC 61000-4-3 10V/m
ANSI C37.90.2 35V/m

33 > MiCOM P124 Range - December 2004 33


MiCOM P124
Communication

34 > MiCOM P124 Range - December 2004 34


MiCOM P124 Range
Communication

Front communication port


RS232

Rear communication port


RS485

35 > MiCOM P124 Range - December 2004 35


MiCOM P124 Range
RS 232 Front Communication Port

PC with Setting Software MiCOM S1

New firmware downloading (flash memory)

36 > MiCOM P124 Range - December 2004 36


MiCOM P124 Dual Powered
RS 485 Rear Communication Port

MODBUS
MORE
RTU protocol
Courier
Compatible with K-BUS/Courier
MORE

IEC 60870-5-103
Compatible with VDEW standard

DNP3

37 > MiCOM P124 Range - December 2004 37


MiCOM P124
MiCOM S1 Software

CONTROLS to MiCOM relays


MORE
Settings
CB Opening/Closing
Setting group change
Data extraction
Settings
Measurements
Events records (75 events)
Faults records (Last 5 faults)
Disturbance records (5 records)

38 > MiCOM P124 Range - December 2004 38


MiCOM P124 Range

THANKS FOR YOUR ATTENTION

39 > MiCOM P124 Range - December 2004 39

Potrebbero piacerti anche