Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
I
1
I
I 2
4
I
3
I1 + I 2 + I3 + I4 = 0
I=0
Definition:
Currents, which flow into the knot (protected object), are counted positive.
Currents, which flow out of the knot (protected object), are counted negative.
Protection objects:
Line, Transformer, Generator/Motor, Bus bar
Ct 1: Ct 2:
IP1 1= - 2 = IP2 = -IP1
Protected IF
5% +5%
object
IS1= IS2=
0.95IP1 IDiff = 0.1IP1
1.05IP2
I
IRest = 2IP1
IS2=
IS1= 1.05IP2
0.95IP1
IDiff= IS1+ IS2
IDiff
IDiff = 0.1IP1
L1
L2
L3
Diff.
Rest. current
Conventional
Differential Protection
Diferent current values of the CT- sets on the high voltage side
(HV)
and on the low voltage side (LV)
Transient currents
Inrush
CT-saturation
kU = U1N/U2N = 110kV/20kV =
5.5
kWinding = w1/w2 = kU/3
I2*L1 = -I1L1ku /3 + I1L2ku /3
I2*L
I1L1ku/3 3
I1L1
530
I2*L2
I1L2ku /3
I1L3 I1L2
-I1L1ku
/3
I2*L
Principles Transf. Dif 8
3-phase Transformer : secondary values
SN I
I L1sec NCT1sec
3 U N I NCTlprim
100MVA 1A
I1L1sec 0.7A
3 110kV 750A
I1L1sec= 0.7A ,
0
100MVA 1A
I2L1sec 0.96A
3 20kV 3000A
I2L1sec = 0.96A ,
-150
L3
0.96A 0.7A
Diff. 29 23
IR Wdg. Wdg.
Rest. current
Conventional Matching transformer
Differential Prot. -Vector group adaptation
-Current value adaptation
-Zero seq. current handling
~ L2
~ L3
3I0
IL1(S2) = -IL1(S1) , IL3(S2) = IL1(S1)
I L1(S2) IL3(S2) IL1(S1)
1 2 3
+
Differential Protection
zero sequence I0
I0 elimination nessesary
Principles Transf. Dif 11
Vector group and current value adaptation in case of
(2/2)
conventional Transformer Differential Protection
Load: 100MVA ,vector group: YNd5
side 2: 20kV side1: 110kV
3000/1A 750/1A
~ L1
13655A
~ L2
~ L3
3I0
IP =
4.55A 5.73A 4300
A
Diff. 29 23
IR Wdg. Wdg.
Rest. current
Conventional Matching transformer
Differential Prot. -Vector group adaptation
-Current value adaptation
-Zero seq. current handling
I0-Elimination
I Diff
InO
3.0 Fault
Characteristic
2.5
Trip
slope 2
Total error
2.0
Block
1.5
CT- error
1.0
slope 1 Tap changer error
0.5
IDiff>
Transf. magnetising current
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 I Rest InO
even i1 iDiff = i1
Inrush
2. Harm.
Y
t=0
i1 I2 = 0
i1 I2 = 0
-T2
t=0
Inrush -T2 t=0 t
1P 2P 3P t
I 2har
I Diff block Cross-block = Yes (blocking of all phases)
L1-block
Setting
15 % value IDiff > trip blocking
L2-block OR
1 for an adjustable time
L3-block
no block
0
0 t
recognise inrush condition by evaluating the ratio 2nd harmonic I2har to basic wave IDiff.
Time limit for cross-block. Reliable reaction to the inrush condition with cross-block.
Trip of a short circuit after the set time delay.
recognise over excitation [V/Hz] by evaluating the ratio 3rd or 5th harmonic to basic wave
Principles Transf. Dif 17
Demonstration of Inrush with evolving fault
Internal
fault
IDiff>>
Inrush
IDiff>
3 cycles
Cross Blocking
i1 i2
i1 i2
i1 I2 0
Fault
6 Characteristic Trip
Block
5
D
C
4
3
Add-on
Stabilisation
2
1
Begin of saturation
IDiff> B
0 14 I Rest
0 2 4 6 8 10 12 16
A
InO
Fault
Characterist
ic
Block
Trip
Add-
Stabilisation
>
I / InO
iDiff IDiff>
kIDiff>
>
1 >
ms ms
SN = 100 MVA
UN2 = 20 kV UN1 = 110 kV
3000/1A 750/1A IP1 = 500A
IP2 = 2750A
(load current) Side 2 Side 1 (load current)
InO2 = 2887A InO1 = 525A
measured
IS2 = -0.916A 7UT6 IS1 = 0.66A secondary currents
7UM62
IDiff = ?
IRest = ?
4. Calculation of the differential and IDiff = |I1* + I2*| IRest = |I1*| + |I2*|
restraint current
Calculation example:
Matched
Principles Transf. Dif 24