Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
FEEDER DESIGN
The service equipment is the main control and means of cutoff for the supply.
In the case of a large premise, the electrical power is usually supplied by the
electric utility at medium-voltage level, requiring a transformer to step down
the voltage to the utilization level.
Contd
Feeders: These are the conductors for delivering the energy from the
service equipment location to the final branch-circuit overcurrent device
protecting each piece of utilization equipment.
Branch Circuits: These are the conductors for delivering the energy from
the point of the final overcurrent device to the utilization equipment.
Each feeder, subfeeder, and branch circuit in turn needs its own overcurrent
protection in the form of a circuit breaker or fused switch.
Contd
The term conductor refers properly to the copper or
aluminum wire that actually carries the electrical
current.
As current flows in the conductor of the cable, heat is generated because of the
resistance of the conductor (I2R)
The rate at which heat can be dissipated is not only dependent on the insulating
material of the cable but also on the environment that surrounds the cable, for
example the air temperature.
The precise calculations to determine the ampacity of a
conductor operating under specific conditions are very complex.
For example, the rating of a 250 MCM copper conductor with 60 insulation
is 215 amperes, whereas the rating of a 500 MCM copper conductor (twice
the size) is 320 amperes, only 1.5 times as much.
Copper has historically been used for conductors of insulated cables because of its
desirable electrical and mechanical properties.
Aluminum has had restricted use but is considered where its ampacity rating to weight
ratio and its relative cost are favorable.
The use of aluminum requires a larger conductor size in order to have the same ampacity
rating as copper.
For example, from the table, a No. 1 AWG copper conductor with 90 temperature rating
has a rating of 150 amperes. An aluminum conductor with the same temperature rating
has to be size 2/0 (two sizes larger) to have the same rating of 150 amperes.
Contd
Unlike copper, aluminum has a few undesirable properties when used as the conductor material.
An oxide film forms on the surface of aluminum.
This aluminum oxide is essentially an insulating film, causing poor electrical contact at
connections.
To help overcome this problem, the aluminum must be cleaned immediately prior to being
connected.
On the other hand, the oxide film that forms on copper is a relatively good conductor, causing
no real problem at connections.
Aluminum conductors can break after bending much more readily than copper conductors and
therefore aluminum conductors must be handled very carefully during installation.
Aluminum deforms at lower pressure than copper and can become loose at connections after a
period of time. The resulting poor electrical contact can cause excessive heat buildup, leading
to the ultimate failure of insulation.
The terminals of equipment, unless otherwise marked, are approved for use with copper
conductors only.
Maximum Allowable Temperature
The maximum continuous current that a conductor can carry is ultimately
determined by temperature at which it is allowed to operate for prolonged
periods of time.
The higher temperature rated insulation may cost a bit more, but if its use
results in a smaller size conductor being required for a given feeder, then the
overall cost may be less.
Contd
An exception to the foregoing is with regard to conductor
sizes Nos. 14, 12, and 10.
This means that the conductor can carry less current before it reaches
its maximum operating temperature.
For wiring installed in areas with ambient temperatures higher than 30 the ampacity of the
conductors must be reduced, called derating.
Conversely, if the ambient temperature is lower than 30, the ampacity can be increased.
For example, for a conductor with 90 insulation operating in an ambient temperature of 40,
the correction factor is 0.91. thus a No. 6 copper conductor, 90, has an ampacity rating of
75 amperes at 30 and only a rating of 0.91 times 75 or 68 amperes at 40.
Conductors installed in Raceways
most common method of installing wiring in a
The
building is to run the conductors in a raceway.
Where conduits are run adjacent to each other, sufficient spacing must be maintained
between them to permit proper cooling.
The second table, on the other hand, applies to 75 rated conductors installed in
underground electrical ducts.
The ampacities are based on ambient earth temperature of 20(68). Ratings are shown for
arrangements where from 1 to 6 electrical ducts are run in the same duct bank.
Details and Adjustment Factors for tables 1 and 2
The duct arrangements and accompanying notes are shown in figure.
raceway or electrical duct.
The ratings in in tables 1 and 2 apply when not more than three conductors are installed, in the one
When more than three conductors are installed, their ampacity rating must be decreased to
compensate for added conductors.
Adjacent conductors have the dual effect of raising the temperature within the raceway and of
impeding the heat dissipated from the raceway.
The table shows the percentages that must be applied to the values listed in tables 1 and 2.
For example, three No. 1/0 copper conductors, 90, installed in a raceway in free air have an
ampacity of 170 amperes. If six No. 1/0 copper conductors, 90, are installed in one raceway, then
the rating of each conductor is reduced to 80% of 170, or 136 amperes.
Note that for more than nine conductors in one raceway the percentage values are based on load
Determining the Ampacity of Conductors
Example 1:
Determine the ampacity of a three-phase, four-wire feeder using 250
MCM copper conductors, 75 insulation, installed in a raceway in free air,
40 ambient temperature, and feeding an incandescent lighting load.
Solution:
From table 1, column 3, the rating for 250 MCM 255 A. the correction factor for 40 is
0.88.
There is no need to derate for the neutral (the fourth wire) because
there are no third harmonics with incandescent lighting.
Short-Circuit Current Rating of Conductors
Short-circuit calculations can impose tremendous stresses on an electrical system.
In the case of feeders, the resulting high short-circuit currents can cause the conductor
temperature to rise very rapidly.
The device protecting the feeder requires some finite time before it can detect and then
fully interrupt the fault current.
The feeder conductors must be sized large enough to carry the fault current for this time
interval without reaching a temperature that will permanently damage the insulation.
The maximum allowable short-circuit transient temperature rating of a cable is much higher
than its maximum allowable operating temperature rating because the short circuit is of such
short duration. The maximum short-circuit temperature rating depends on the type of
With an asymmetrical fault current, the heating of the
conductors is greater than it would be if the fault current were
symmetrical.
Therefore, allowance must be made for this increased heating in
selecting the correct size of conductor.
The ration between the asymmetrical and the symmetrical
current is dependent on the rate of decay of the dc component
after the fault occurs.
If we let represent this ratio, then
The value depends on the system voltage and the type of overcurrent
device used for the feeder, as shown in the table below.
This table also shows the total clearing times for the overcurrent devices.
precise calculation to determine the short-
The
circuit current rating of a cable is very
complex. Fortunately, graphs have been
prepared that simplify the process.
Solution
The maximum conductor voltage-drop
recommended for both the feeder and
branch circuit is 5% of the voltage source
(120V). The total conductor voltage drop
(feeder and branch circuit) shouldn't exceed
120V0.05=6V. Calculate the operating
voltage at the load by subtracting the
conductor voltage drop from the voltage
source: 120V-6V=114V. Therefore, the
correct answer is 114V.
Exercise 1
Let's look at a 3-phase example. A 3-phase, 36kVA load rated 208V is wired
to the panelboard with 80-foot lengths of 1 AWG THHN aluminum. What is
the approximate voltage drop of the feeder circuit conductors?
An equal function is to protect people against electrical hazards and to minimize the likelihood
of fires being caused by faults in the electrical wiring.
As previously discussed, the ampacities are reduced by having them installed in a raceway, but in
the interest of safety the NEC requires all wiring must be properly protected (Section 300-4).
The final function of metallic-type raceways is to provide for continuity of the equipment
grounding system throughout the building.
The total cross-sectional area of the conductors, including the insulation, must not exceed a
specified percentage of the cross-sectional area of the inside of the conduit. This referred
to as the percentage fill.
If the percentage fill is too high, then the cables can be damaged as they are pulled
through the run of conduit.
Also the heat buildup within the conduit from the conductor currents could become
excessive under operation because of overcrowding.
The National Electrical Code restricts the percentage fill to 40% for three or more
conductors.
Conductors in Parallel
For larger-rated feeders, it may be desirable
to parallel two or more conductors per phase,
rather than use one large conductor, paralleling
means that the conductors of each phase are
electrically joined at both ends to effectively
form a single conductor as shown.
As previously illustrated, the ampacity of
conductors is not a linear function of their size;
that is, the doubling of the cross-sectional area
of the conductor doesnt result in the doubling
of its ampacity rating.
Another reason to use to avoid using large
conductors is the difficulty of pulling them into
the raceway.
Also, a large-sized conduit is required, which is
cumbersome to handle during installation.
The general recommendation for conductors installed in conduit is that, if
required conductor size is computed to be larger than 500 MCM, then
paralleling should definitely be considered. In fact, the NEC allows
conductors size 1/0 and larger to be paralleled ( Section 310-4).
There are two exceptions to this requirement. The first concerns feeders to groups
of motor. The second concerns 100% rated overcurrent devices.
For the method of calculating minimum load requirements for the feeders to panels
supplying lighting units and general purpose receptacles see next chapter.
The following examples show the procedures for the selection of feeder conductors.
Example