Choosing the appropriate

voltage dip mitigation device


LABORELEC

dr. ir. Marcel Didden


marcel.didden@laborelec.com
LABORELEC 0032 - 479 77 01 35
LABORELEC 2006 1
Content

1. Introduction
2. Mitigation equipment
3. Dip immunization capability
4. Other aspects
5. Conclusion

LABORELEC
LABORELEC 2006 2
1. Introduction

LABORELEC
LABORELEC 2006 3
Voltage dips / sags

> 10%

<2s
Dip
Dips are mainly caused by short circuits

LABORELEC
LABORELEC 2006 4
Cost per process outage
(cases Laborelec 2004/2005)
Basic Chemicals
Semiconductor
Automotive
Textile
Non-Ferro
Food 190 000
100 000
Textile
Textile
Textile
Textile
Dairy
Textile
Textile
Plastics
Food
Textile
Food
Dairy
Dairy

0 10.000 20.000 30.000 40.000 50.000 60.000 70.000 80.000 90.000 100.000

LABORELEC
LABORELEC 2006 5
Mitigation possibilities
a. Adaptation processes
b. Adaptations protections
a c. Installing mitigation equipment
d. Grid restructuring

VSD 1 b
c d
VSD 2 Entrance grid
company
PLC

Sensitive Processes

Options a, b and d are most interesting, but not always possible


Sometimes c is the only option
Installing a UPS is the easiest way to mitigate dips but too expensive
This presentation analyses alternatives

LABORELEC
LABORELEC 2006 6
2. Mitigation equipment

LABORELEC
LABORELEC 2006 7
Flywheel

grid load

static switch

G M/G

converters

LABORELEC
LABORELEC 2006 8
Static UPS

grid load

AC/DC-converter DC/AC-converter

battery

LABORELEC
LABORELEC 2006 9
Dynamic Voltage Restorer

grid load

transformer

converter

DC-link with
possibleenergy
reserve

LABORELEC
LABORELEC 2006 10
Statcom

grid load

transformer

converter

DC-link with optional


energy storage

LABORELEC
LABORELEC 2006 11
Shunt connected
synchronous motor

optional damping coil


grid load

synchronous machine

LABORELEC
LABORELEC 2006 12
Transformerless series
injection

staticswitch

load

LABORELEC
LABORELEC 2006 13
3. Dip immunization
capability

LABORELEC
LABORELEC 2006 14
Dip distribution
100
100
voltage drop
drop

9090
8080
than voltage

7070 B1
6060
F
5050
less than

4040
B2
NL
sags less

3030 PP
2020 US
of sags

1010 C
% of

0 0
%

0 0 2020 4040 60
60 80
80 100
100
Voltage
Voltagedrop
drop(%)
(%)

LABORELEC
LABORELEC 2006 15
Immunization level
sag (% Urated)

0 1. 2. 3. 4. .5. 6.

1. -x1%: Immunity process 1


2. -x2%: Immunity process 2

3. -(x1%+y%): Immunity process 1 with DVR


4. -(x2%+y%): Immunity process 2 with DVR

5. -z%: Immunity process 1 with Transformerless Series Injector


6. -z%: Immunity process 2 with Transformerless Series Injector

-100

LABORELEC
LABORELEC 2006 16
Immunization level

Belgian bus bar (B2) , initial

Belgian bus bar (B2) , initial


Maximum voltage lift in %

Cigre bus bar (C) , initial

Cigre bus bar (C) , initial


Maximum voltage drop
Percentage of outages

being protected in %
due to sags that will be

immunity 30%
immunity 10%

immunity 30%

immunity 10%
reduced:

40 - 60%
60 - 80%
80 -100%
Flywheel 100 /
Static UPS 100 /
DVR-Cap1 / 30
DVR-Cap2, 200% load / 50
DVR-Cap2, 400% load / 25
Statcom-SMES / 60
Shunt Connected SM / 60
Transformerless series injection 50 /
LABORELEC
LABORELEC 2006 17
4. Other aspects

LABORELEC
LABORELEC 2006 18
Size
- : only > 1MW
= : only > 100 kW
+ : also < 100 kW
Purchase cost
- : > 250 /kVA
= : 150 250 /kVA
+ : < 150 /kVA
Maintenance
- : annual maintenance required
+ : no annual maintenance required

LABORELEC
LABORELEC 2006 19
Efficiency
+ : losses <0,5% Srated
= : losses 0,5-2% Srated
- : losses >2% Srated
Reaction time
+ : reaction or activation transient < 1 ms
= : transient 1-5 ms
- : transient > 5 ms

Harmonics, reactive power


= : no influence
+ : positive influence

LABORELEC
LABORELEC 2006 20
Summary

Reactive power
Purchase cost

Reaction time
Maintenance

Technology
harmonics
harmonics
Efficiency

maturity
Voltage
Current
Size
Flywheel = - - - = + + + +
Static UPS + = - - + + + + +
DVR-1 + + + = = = = + =
DVR-2, 200% load - + + - = + = = =
DVR-2, 400% load - + + - = + = = =
Statcom-SMES - = - = - = = + -
Shunt connected SM + - - -/= = + +1 + -
Transformerless series injector + = + + = = = = =
1 The harmonic currents are reduced by creating a low impedance path through the SM

LABORELEC
LABORELEC 2006 21
5. Conclusion

LABORELEC
LABORELEC 2006 22
Most cost efficient
DVR without energy storage
Transformerless series injector
If harmonics are an issue
Synchronous motor
If all sags have to be dealt with
Flywheel or static UPS

further information on
manufacturers or concrete case studies
marcel.didden@laborelec.com

LABORELEC
LABORELEC 2006 23