Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
System
General
guidelines
Interlock and Protection
Hardware architecture
NFPA guidelines
BMS requirements
Oil burner
Coal burner
BMS architecture
What is NFPA?
NFPA is an abbreviation for National Fire Protection Association
Its mission is to reduce the worldwide burden of fire and other hazards on the
quality of life by providing and advocating consensus codes and standards,
research, training, and education.
building,
process,
service,
design, and
installation
Requirement
Multiple burner boilers require two independent
control systems.
NFPA definition
NFPA defines
NFPA definition
NFPA defines
must be designed to ensure a safe, orderly operating sequence in the startup and shutdown of fuel firing equipment and to reduce possible errors by
following the operating procedure.
all parts of the BMS shall remain in good working order and in service
whenever the burner is in service if the system is to provide the protection
for which it is designed.
Prevent firing unless a satisfactory furnace purge has first been completed.
Prohibit start-up of the equipment unless certain permissive interlocks have first
been completed.
Monitor and control the correct component sequencing during start-up and shutdown of the equipment.
Combustion control
Excess air control
Steam drum level control
Loss of HT power
Loss of UPS power
Loss of 220V DC power
Condenser vacuum low
MFT hard relay tripped
2 out of 3 main processors failed
Both emergency trip push buttons operated
Any of the above occasions will result in a MFT
MFT conditions
MFT conditions
Action: MFT
MFT conditions
Action: MFT
MFT conditions
MFT conditions
Critical Flameout
Source : Furnace flame scanners detect 2 out of 3 zones
no flame
Implication: Is a consequence of improper combustion in
pre-identified zones within the furnace resulting in flame
instability which may give rise to improper heat
distribution
Action: MFT
MFT conditions
Delayed light up
Source : MFT reset , LDO shut off valves open and no oil
gun in operation (or in other words put into service) within
10 mins of opening of LDO shut-off valves.
Implication: Repeated unsuccessful attempts to light up
the boiler with oil gun has resulted in accumulation of unburnt fuel (oil) in the furnace and hence the furnace
requires purging.
Action: MFT
MFT conditions
Re-heater protection
Source : All governor valves closed, HP bypass valve < 2% open with
a. at least one feeder running from remote
or
b. More than 8 out of 12 oil guns in operation
Implication: Damage to tubes that can result from firing in excess of
safe limit which will cause overheating of re-heater tubes due to
absence of a steam flow through it.
Action: MFT
MFT conditions
MFT conditions
EFFECTS OF MFT
LDOT
HFOT
TRIP TURBINE
Burner for coal firing gravity fed down shot fired, corner
fired, front fired
Secondary air dampers are initiated to move to oil position ( air flow 30 to 120
T/hr)
Step 2:
Step 5a:
Burner in lighting mode for 60 secs and oil gun not inserted
Burner in lighting mode for 60 secs and LDO valve closed
Burner in lighting mode for 60 secs and atomising air valve not full open
LDO valve not closed and oil gun not inserted
LDO valve neither full close for 15 secs nor full open
LDO valve not closed for 10 secs and oil flame not detected
LDO valve not closed and scavenge valve not closed
LDOT
MFT
Air flow < 10 %
Sequence of operation
Step 1:
MFT
LDOT
Either scavenge valve or atomising valve not full open when burner is in
scavenge mode, oil gun is inserted, atomizing air pressure is healthy,
ignitor is inserted and sparking
Either ignitor power is not available or ignitor not inserted when burner is
in scavenge mode, oil gun is inserted, atomizing air pressure is healthy,
Oil gun scavenge required persists and Atomizing air pressure not
healthy
Oil gun scavenge required persists and Oil gun not inserted
Oil Burner stop command
Step 4:
Scavenge valve open
Step 3b condition satisfied
Atomising air selected
Atomizing
Step 6:
Step 5 all conditions remaining except that 2 mins has elapsed since
starting of scavenge process
Oil
Initiates
Note:
Mill running from remote for 10 secs moves the secondary air
dampers to PF position
The above conditions gives the permissive to start a Mill and when
Mill start is initiated from remote.. MILL STARTS provided Mill
is not in shutdown mode
The above conditions gives the permissive to open Mill discharge valve and
when Open is initiated .. MDV opens
The following conditions need to be true prior to closing a Mill Discharge
Valve
Feeder stopped
Mill stopped
MDV open
The above conditions gives the permissive to close Mill discharge valve and
when Close is initiated or MFT or Mill hard relay trip occurs.. MDV
closes
Feeder Starting
The following conditions generates a start permissive for a Feeder
The above conditions gives the permissive to start a Feeder from remote
This generates an alarm Mill support ignition required and accordingly oil
burners are to be put in service
OR
The above condition need to persist for more than 5 mins to initiate a
permission to stop a Mill . It signifies Mill is empty.
Either of the following conditions below de-energize Mill hard relay and
indicates Mill in shutdown mode
Mill is empty, Mill selected to remote, Stop Mill initiated. Inhibits oil burner
shutdown until Mill outlet temperature is < 60C and mill is stopped
MFT
Mill Trip relay
When :
On Turbine trip
Load rejection >50 %
Single FD or PA fan running
Hardware - PLC
EFFECTIVE AND RELIABLE SYSTEM
FOR OVERALL SUPERVISION OF
BOILER SAFETY IN A POWER PLANT.
Transferring control to
Fault Tolerant pair and
running self diagnostics
Chassis
with
Processor
and I/O
cards
Running self
diagnostics and
monitoring
Hardware - PLC
THE BMS IS A PLC, PROGRAMMED ACCORDING TO USER NEED.
LIKE CONVENTIONAL PLC SYSTEMS THE BMS ALSO CONSISTS
OF THE FOLLOWING PARTS:1. MOUNTING RACK
2. POWER SUPPLY
3. MAIN PROCESSOR
4. I/O CARDS
5. SPECIAL MODULES
6. SPECIAL FUNCTIONS
The Tricon controller uses three identical channels to process single data
from field
Each channel is isolated from the others and no single point failure in any
channel can pass to another channel
TMR Architecture
Input
Leg
A
Input
Leg
B
Input
Leg
C
Main
Process
or A
Output
Output
Leg
Leg
A
A
Output
Output
Leg
Leg
B
B
Main
Process
or B
Main
Process
or C
Output
Output
Leg
Leg
CC
+V
C
Loopback
Loopback
Fault Tolerant
The Ability of the System to Continue to Perform its
Function in the Presence of Faults and Errors.
No Single Point of Failure will Shutdown the System
Fail-Safe
If the System does Fail it will Fail to the Safe State or the
state of the Equipment Under Control (EUC) when safety
is achieved - de-energized for ESD Systems
PFD - Probability-to-Fail On Demand
Availability
The probability that the system will be operational at
some instant of time
Diagnostic Features