Electricity is essential for life as the air, water and food. With
electricity we light our houses, shops, streets and run our fans, air
conditioners and refrigerators.
The electricity is the backbone of economy of our country as it
is used to run the industries and agricultural tube wells.
WAPDA electricity system is segregated into
1. Generation.
2. Transmission.
3. Distribution.
2
GENERATION OF ELECTRICITY
The electric generator is a machine, which converts mechanical
energy into electrical energy. The fundamental principal of electricity
generation is based upon Faradays Law of electromagnetic induction,
which states that whenever the magnetic flux linked with a circuit is
changed, an e.m.f. is induced in the circuit. The magnitude of induced
e.m.f. is directly proportional to the rate of change of flux. This induced
e.m.f. causes flow of electric current if the circuit is closed.
The electricity generation in Pakistan is categorized into:1.
Thermal generation
2.
Hydal generation
3.
Nuclear generation
3
1.
2.
3.
THERMAL GENERATION
In thermal generation coal, oil and gas is used to produce heat energy .
This heat energy is converted into mechanical energy with the help of turbines and
the mechanical energy is converted into electrical energy by generators according to
Faradays Law of electromagnetic induction.
HYDAL GENERATION
In hydal generation the potential energy of water is converted into
mechanical energy with the help of turbines. The turbines are coupled with the
electric generators, which convert the mechanical energy into electrical energy
according to Faradays Law of electromagnetic induction. The type of generation is
most economical and cheap.
NUCLEAR GENERATION
In this type of generation heat energy is produced by fission process.
This heat energy is converted into mechanical energy by steam turbines and
mechanical energy is converted to electrical energy by the electric generators.
Nuclear generation is produced at Karachi and Chashma.
4
The installed capacities of different power plants in Pakistan are shown as below:HYDAL GENERATION (WAPDA)
Sr.
No.
Name of Plant
Capacity in M.W
Completed
1.
Tarbela
3478
1974
2.
Ghazi Barotha
1450
2002
3.
Mangla
1120
1967
4.
Warsak
243
1960
5.
Chashma
184
2001
6.
Jinnah Hydal
96
2013
7.
Small hydal
600
--
7171
--
Sub Total
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
Jamshoro
Guddu
Faisalabad
Sukhar
Quetta
Multan
Muzaffargarh
Pasni
Mesco
Lakhra
Shahdra
Kotri
Sub Total
880
1655
376
50
83
260
1370
17
20
150
85
174
5120
6.36
11.96
2.72
0.36
0.60
1.87
9.90
0.12
0.14
1.08
0.61
1.25
37.01
Hubco
1292
--
2.
Kohinoor
131
--
3.
Kapco
1621
--
4.
AES Lalpir
362
--
5.
365
--
6.
117
--
7.
586
--
8.
412
--
9.
235
--
10.
157
11.
120
--
Sub Total
5398
--
Grand Total
--
--
10
11
13
14
FACING OF CROSS-ARMS
The cross-arms on 11KV poles/structures are installed by adopting the method of facing. It will provide
maximum strength to the line and the cross arms will not go on breaking incase of a break down.
Facing of cross-arms of different situations is explained as below:1.
STRAIGHT LINE.
CURVE.
The X-arms on the poles next to angle or corner pole should face
4.
towards corner.
STEEP GRADES.
LONG SPANS.
Cross arms on poles next to those supporting to long span should face away from the long
span.
15
16
17
STANDARD
LINE
ASSEMBLIES
DESCRIPTION
11 KV SINGLE
CROSS ARM
1-L
ASSEMBLY
11 - KV DOUBLE
2 - L CROSS ARM
ASSEMBLY
LOCATION / USE
ROAD CROSSING/SMALL
ANGLE
TYPE OF SUPPORT
STRUCTURE WITH WOODEN
CROSS ARM
PC POLE WITH WOODEN CROSS
ARM
PC POLE WITH ANGLE IRON
CROSS ARM
STRUCTURE WITH WOODEN
CROSS ARM
PC POLE WITH WOODEN CROSS
ARM
PC POLE WITH ANGLE IRON
CROSS ARM
11 - KV VERTICAL
USED FOR MEDIUM ANGLE OF
3 - L ANGLE ASSEMBLY
DOG CONDUCTOR
(WITH EXT.LINK)
11 - KV VERTICAL
ANGLE ASSEMBLY USED WHERE ANGLE IS UPTO
4-L
(WITH OUT EXT.
60
LINK)
11 - KV VERTICAL
DEADEND
5-L
USE ON LINE ANGLE 60-90
ASSEMBLY (WITH
EXT. LINK)
STRUCTURE / PC POLE
REMARKS
GOPHER 0-11
RABBIT
08
DOG
0-03
GOPHER
0-19
DOG
0-
0-25
RABBIT
0-08
GOPHER, USE
ASSEMBLY 4 L
RABBIT, USE ASSEMBLY
4L
DOG 06-12
GOPHER USE ASSEMBLY
4 L 20-60
RABBIT USE ASSEMBLY 4
L 15-60
DOG 12-60
-
10
ES/DD
8-L
10 - L
15 - L
16 - L
11
20 - L
12
21 - L
13
22 - L
DESCRIPTION
LOCATION / USE
11-KV HORIZONTAL
SINGLE DEAD END WHERE LINE ENDS FOR DOG
ASSEMBLY (STEEL CONDUCTORS ONLY
CROSS ARM)
USED FOR FORMING DOUBLE
DEAD END ON LONG LINE OR
11-KV HORIZONTAL TAKING SMALL ANGLE. ALSO
DOUBLE DEAD END USED FOR INSTALLATION OF
ASSEMBLY
SECTIONALIZING SWITCHING.
OMITANCHOR SHACKLES FOR
LINE ANGLE OF 5 OR LESS.
TYPE OF SUPPORT
STRUCTURE WITH STEEL CROSS ARM
_
PC POLE WITH ANGLE IRON CROSS ARM
REMARKS
GOPHER 0-10
RABBIT 0-05
DOG 0-03
GOPHER 0-20
RABBIT 0-15
DOG 0-05
_
_
OMIT ANCHOR
SHACKLE FOR
TEE OFF ANGLE
OF 5 OR LESS.
14
15
16
17
DESCRIPTION
LOCATION / USE
TYPE OF SUPPORT
REMARKS
OMIT ANCHOR
SHACKLE FOR TEE
OFF ANGLE OF 5 OR
LESS.
This assembly is used for angled running lines with Double X-ARMS.
This assembly is also used for road crossings.
This assembly is used for 11 KV vertical line with extension link for medium angled and
conductor passes through suspension clamps.
This assembly is used for crossing of two 11 KV lines with each others
upper & lower positions
This assembly is used for new T-Off line from existing 11 KV line.
DESCRIPTION
1-L
11 KV SINGLE CROSS ARM ASSEMBLY 1-L
This Assembly is used for 11 KV Straight Lines and small angle
S#
1
2
APPLICATION TABLE
CONDUCTO LINE
R
ANGLES
Gopher
O to 11
Rabbit
O to 08
Dog
O to 03
DESCRIPTION
Wood Cross Arm
0
Cross Arm Brace
1xx28
QUANTITY
4x5x8-
1
2
11 KV Pin Insulator
Insulator Pin
M. S. Bolt 3/8x6
M. S. Bolt 5/8x2
M. S. Bolt 5/8x14
2-L
11 KV DOUBLE CROSS ARM ASSEMBLY 2-L FOR LATTICE STEEL POLE
This assembly is used for angled running lines with Double X-ARMS.
this assembly is also used for road crossings.
S#
APPLICATION TABLE
CONDUCTO LINE
R
ANGLES
Gopher
O to 25
Rabbit
O to 19
Dog
O to 08
DESCRIPTION
4x5x8-0
QUANTITY
11 KV Pin Insulator
Insulator Pin
M. S. Bolt
3/8x6
M. S. Bolt
5/8x2
M. S. Bolt
5/8x18
Round Washer
1 Dia
10
Square Washer
Hole
2 x 2 x Dia 11/16
1xx28
5/8x20
7/16 Hole
2
4
2
4
10
3-L
11 KV VERTICAL ANGLE ASSEMBLY 3-L (WITH EXTENSION LINK) FOR
LATTICE STEEL POLE.
This assembly is used for 11 KV vertical line with extension link for medium angled and
conductor passes through suspension clamps.
NOTE:USE THIS ASSEMBLY AT MEDIUM ANGLE
LOCATIONS FOR 11KV LINE WITHOUT LT
WITH DOG ACSR CONDUCTOR, ESPECIALLY
WHERE CLEARANCE ON THE GUY SIDE IS
REQUIRED. USE ONE GUY.
APPLICATION TABLE
CONDUCT
LINE ANGLES
OR
Use Assembly
Gopher
4-L
Use Assembly
Rabbit
4-L
Dog
6 to 12
S#
DESCRIPTION
QUANTITY
5/8x12
5/8x14
Anchor Shackle
Extension Link 14
4-L
S#
1
APPLICATION TABLE
CONDUCTO LINE
R
ANGLES
2O to
Gopher
60
15 to
Rabbit
60
12 to
Dog
60
DESCRIPTION
11 KV Disc Insulator 10 Dia Clevis
Type
QUANTIT
Y
3
Eye Nut
5/8x12
5/8x14
Anchor Shackle
5/8
5-L
S#
QUANTITY
Eye Nut
5/8x12
5/8x14
Extension link 14
Anker Shackle
NOTE:-
DESCRIPTION
5/8
6
6
6
7-L
DESCRIPTION
QUANTITY
M.S. Bolt
3/8 x 6
M.S. Bolt
5/8 x 2
10
10
8-L
11 KV HORIZONTAL SINGLE DEAD END ASSEMBLY 8-L
(STEEL CROSS ARM) FOR LATTICE STEEL POLE.
This 11 KV single line dead end assembly is used on terminal pole or dead
end pole with single steel X-ARM.
S#
DESCRIPTION
QUANTITY
M.S. Bolt
5/8 x 2
Anchor Shakle
M.S. Bolt
3/8 x 2
M.S. Bolt
5/8 x 2
10-L
DESCRIPTION
Wood Cross Arm
4x5x8-0
Cross Arm Brace 1 x x 28
11 KV Disc Insulator 10 Dia Clevis eye
Type
11 KV Pin Type Insulator
Insulator Pin
Dead End Clamp
P G Clamp two bolt type
Eye Nut 5/8
M.S. Bolt
3/8 x 6
M.S. Bolt
5/8 x 2
Double Arming Bolt 5/8 x 20
Round Washer 1 Dia 7/16 Hole
Square Washer 2 x 2, 11/16 Hole
Anchor Shakle
QUANTITY
2
4
6
3
3
6
3
6
4
2
3
4
10
6
15-L
11 KV OFFSET SINGLE CROSS ARM ASSEMBLY 15-L FOR
LATTICE STEEL POLE.
This Assembly is used on 11 KV running lines with Single X-Arm and single step brace.
This Assembly is used for narrow streets with slight angles and where clearance is required from
buildings.
S#
1
APPLICATION TABLE
CONDUCTO LINE
R
ANGLES
Gopher
0 to 10
Rabbit
0 to 05
Dog
0 to 03
DESCRIPTION
Wood Cross Arm
4x5x8-0
QUANTITY
1
Insulator Pin
M.S. Bolt
1/2 x 2
M.S. Bolt
1/2 x 6
M.S. Bolt
5/8 x 14
16-L
11 KV OFFSET DOUBLE CROSS ARM ASSEMBLY 16-L FOR
LATTICE STEEL POLE.
This assembly is used on 11 KV running lines with double cross arm.
This assembly is used for narrow streets and medium angled where clearance is
QUANTIT
S#
DESCRIPTION
Y
required from buildings.
1
3
4
Insulator Pin
M.S. Bolt
1/2 x 2
M.S. Bolt
1/2 x 6
M.S. Bolt
5/8 x 18
10
NOTE:-
4x5x8-0
APPLICATION TABLE
CONDUCTO LINE
R
ANGLES
Gopher
0 to 20
Rabbit
0 to 15
Dog
0 to 05
2
6
6
5/8 x 20
1
2
6
20-L
11 KV CROSS OVER AND TAP ASSEMBLY 20-L FOR
LATTICE STEEL POLE.
This assembly is used for crossing of two 11 KV lines with each others upper & lower positions
S#
DESCRIPTION
4x5x8-0
QUANTITY
2
4
Insulator Pin
M.S. Bolt
3/8 x 6
M.S. Bolt
5/8 x 2
M.S. Bolt
5/8 x 14
10
11
M S Bolt 5/8 x 2
21-L
11 KV CROSS OVER AND TAP ASSEMBLY 21-L (FOR EXISTING LINE)
FOR LATTICE STEEL POLE
This assembly is used for crossing of new 11 KV line under the existing 11 KV line on the same
structure.
S#
DESCRIPTION
QUANTITY
Insulator Pin
M.S. Bolt
3/8 x 6
M.S. Bolt
5/8 x 2
M.S. Bolt
5/8 x 14
9
10
1
2
2
1
6
22-L
DESCRIPTION
Wood Cross Arm
4x5x8-0
Cross Arm Brace 1 x x 28
11 KV Disc Insulator 10 Dia Clevis Eye
Type
11 KV Pin Type Insulator
Insulator Pin
Dead End Clamp
P G Clamp two bolt type
Eye Nut 5/8
M.S. Bolt
3/8 x 6
M.S. Bolt
1/2 x 2
M.S. Bolt
5/8 x 14
Double Arming Bolt 5/8 x 20
Round Washer 1 Dia 7/16 Hole
Square Washer 2 x 2 , 11/16 Hole
Anchor Shakle
M. S. Bolt
5/8x2
QUANTITY
3
6
3
4
4
3
3
3
6
4
1
3
6
11
3
1
23-L
DESCRIPTION
Insulator Pin
M.S. Bolt
3/8 x 6
10
M.S. Bolt
1/2 x 2
4x5x8-0
QUANTITY
2
3
1
11
12
13
10
14
Anchor Shakle
40-L
11 KV AND 400 VOLT COMPOSITE IN LINE ASSEMBLY 40-L FOR
LATTICE STEEL POLE.
This assembly is used for straight 11 KV line with LT composite line on single
QUANTIT
cross arm.
S#
DESCRIPTION
Y
1
2
3
4
5
6
7
8
9
10
11
12
13
4x5x8-0
1
2
3
3
2
1
1
2
1
4
4
4
4
41-L
11 KV AND 400 VOLT COMPOSITE SMALL ANGLE ASSEMBLY 41-L
FOR LATTICE STEEL POLE
This assembly is used on angled 11 KV running line with LT composite line.
S#
1
DESCRIPTION
Wood Cross Arm
4x5x8-0
QUANTITY
2
Insulator Pin
M.S. Bolt
3/8 x 6
M.S. Bolt
5/8 x 2
M. S. Bolt
5/8 x 18
10
10
11
Spool Insulator
12
M. S. Bolt
13
14
5/8 x 1
4
4
42-L
DESCRIPTION
M.S. Bolt
3/8 x 6
M. S. Bolt
5/8 x 2
10
10
4
4x5x8-0
QUANTITY
5/8 x 1
3
3
11
M. S. Bolt
12
D-Shackle
13
Spool Insulator
14
NOTES:
USE SIDE GROOVES OF PIN INSULATORS FOR
THE MIDDLE INSULATOR AND TOP GROOVES
FOR
TWO
OUTER
CONDUCTORS.
THE
TRANSPORTATION OF CENTRAL PHASE PROVIDES
THE ADDITION OF MECHANICAL BALANCE AS
WELL AS INCREASE OF CLEARANCE BETWEEN
CONDUCTORS AT THE MID SPAN.
LT T-OFF ASSEMBLY
a. LT T-off at Intermediate LT
Pole
i)
I.
60
ELEVATION
ELEVATION
Plan
L.T STRAIGHT LINE &
ANGLE.
No.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Plan
L.T DEAD
Description
END.
DWG No.
6W/DF-35
6W/DF-34
6W/DF-30
6W/DF-13
-
61
ELEVATION
Plan
LT Dead End. No.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
Description
MS Bolt, Nut 5/8 Dia, 6 Long
MS Bolt, Nut 5/8 Dia, 12 Long
Eye Nut
Thimble
Guy Wire 7/10 SWG: 45 Ton GLTY
Strain Insulator
Aluminum Tape
U Bolt Clip
LT Conductor
Parallel Groove Clamp
DWG No.
6W/DF-36
6W/DF-37
6W/DF-31
-
62
MINIMUM
CLEARANCE
1
FROM GROUND
IN FEET/MM
LINE VOLTAGE
400V 11KV 33KV 66KV 132KV 220KV
3
4
5
6
7
8
Description
2
ACROSS A STREET OR
INTARSECTION OR ROAD
19/
5791
20/
6096
20/
6096
26/
7923
26/
7925
26/
7925
ALONG A STREET
17/
5182
20/
6096
20/
6096
ACROSS PRIVATE
PROPERTY AND CROSS
COUNTRY
15/
4572
15/
4572
13/
4572
20/
6096
22/
6706
23/
7010
08/
2438
12/
3658
12/
3658
30/
9144
15/
4572
30/
9144
17/
5182
30/
9144
20/
6096
04/
1219
06/
1829
06/
1829
15/
4572
20/
6096
25/
7620
37/
11278
MINIMUM
CLEARANCE
2
FROM BUILDING HORIZONTAL CLEARANCE
FROM WALLS END PARTS
IN FEET/MM
OF A BUILDING
MINIMUM
CLEARANCE
3 FROM RAILWAY
INSTALLATIONS
FT/MM
(IN FEET/MILIMETERS)
10.5/
3200
29/
8839
30/
9144
31/
9449
32/
9754
33/
10058
34/
10363
22/
6706
23/
7010
24/
7315
25/
7620
26/
7925
10.5/
3200
10.5/
3200
10.5/
3200
12.5/
3810
13.5/
4115
63
64
Description
Miscellaneous
Clearance
between Circuits,
7
Conductor or
Objects Not
Covered above.
(IN FEET/MILIMETERS)
LINE VOLTAGE
400V
11KV
33KV
66KV
132KV
220KV
a.
2'/610 mm
b.
1'/305 mm
c.
2'/610 mm
d.
Clearance between street light brackets & 400 Lines or telegraph line.
1'/305 mm
e.
Clearance between guy wire at pole attachment & open telegraph line
2'/610 mm
f.
Clearance between guy wire at poles attachment & 400V Line or Cable
0.25'/76 mm
g.
Clearance between guy wire at pole attachment & 11KV Line or Cable
0.75'/229 mm
For Lines of 66KV and above generally two circuits will be mounted on the same pole and will
be in vertical formation. At these voltage circuits of different voltages are not to be installed on the same
poles. The horizontal clearance for circuit of the same voltage are given at Sr. No.05. These are preferred
design values for the conductors now used and spans of 900 ft. and 1200 ft. for 66KV, 132KV Lines
respectively. For other spans or heavy conductors the clearances may have to be changed.
65
Rural
% V.D
AEL (%)
% V.D
AEL (%)
HT
03
2.5
05
3.5
Distribution
T/Former
04
3.5
04
3.5
LT
03
2.5
03
2.5
Cable
01
0.5
01
0.5
Total:-
11
13
10
66
AMPERE
NO. of strands/Size
Gnat
Ant
Wasp
Hornet
Chafer
130
200
315
410
500
7/0.087
7/0.122
7/0.173
19/0.128
19/0.149
AMPERE
NO. of strands/Size
Gopher
Rabbit
150
205
6/1 (A/S)
6/1 (A/S)
Dog
300
6/0.186 (A)
Lynex
Panther
Ospray
470
510
660
30/7 (A/S)
30/7 (A/S)
18/1 (A/S)
7/0.093
7/0.132
7/0.062
(S)
0.11
0.118
0.176
67
Gopher, Gnat
Cabels 7/.052, 19/.052
(3.5-7.5 mm)
Gopher , Gnat
Cabels 7/.052, 19/.052
(3.5-7.5 mm)
Gopher, Rabbit, Gnat, Ant
Cabels 19/.052, 19/.083
(6-11 mm)
Rabbit, Dog, Gnat, Ant
Cabels 19/.052, 19/.083
(6-11 mm)
Rabbit, Dog, Ant , Wasp
Cabels 19/.083, 37/.083
(9-15 mm)
Osprey, Panther
Connector No.
S 117
S 157
T 110
T 155
T 150
T 220
Earthing means connecting the dead part (it means the part which does
not carries current under normal condition) to the earth for example
electrical equipments frames, enclosures, supports etc.
The purpose of earthing is to minimize risk of receiving an electric shock
if touching metal parts when a fault is present. Generally green wire is
used for this as a nomenclature.
Earthing is to ensure safety or Protectionof electrical
equipment and Humanby discharging the electrical energy to
the earth.
Grounding:
Grounding means connecting the live part (it means the part which
carries current under normal condition) to the earth for example neutral
of power transformer.
Grounding is done for the protections of power system equipment and
to provide an effective return path. For example grounding of neutral
point of a star connected transformer.
Generally Black wire is used for this as a nomenclature.
Earthing is more commonly used in Britain, European and most of the
commonwealth countries standards (IEC, IS), while Grounding is the word
used in North American standards (NEC, IEEE, ANSI, UL).
But in both above case Earthing and Grounding are used for the same
Purpose
There is no major difference between earthing and Grounding, both
69
meansConnecting an electrical circuit or device to the
69
Earth.This serves various purposes like to drain away unwanted