Sei sulla pagina 1di 64

THE "GUIDING SYSTEM"

Sepam Offer EN 2007_01.ppt


1

Sepam protection relays


A range of solutions for all
applications

Sepam series 80:


intelligent solutions
for personalized applications
Sepam series 40:
high-performing solutions
for demanding applications

Sepam series 20:


simple solutions
for common applications

Sepam series 10:


designed for building and Utilities

Sepam Offer EN 2007_01.ppt


2

Sepam Series 10 selection guide

Sepam series 10 N: earth fault


protection
-Sepam series 10 B: 3 phases
overcurrent and earth fault protection
- Sepam series 10 A: communication,
logic input and signalling relays

Sepam Offer EN 2007_01.ppt


3

Sepam series 20 40 80 selection guide


sensors

Series 20

Specific
protection

Sub transformer motor


station

50BF

S 20
S 23

3I + I0

10 I / 8 O
1 com. port

T 20

generator Bus bar capacitor

M 20

T 23
B 21
B 22

3 V + V0

81R

Series 40

3I + I0
10 I / 8 O
3V
1 com. port
Logical equations

67et 67N

S 40
S 41
S 42

67N

S 80
S 81

67N

Series 80 3I + 2xI0
3V + V0
42 I / 23 O
2 com. port
Logical equations
LOGIPAM
2x3I + 2xI0
3 V + V0
3I + 2xI0
2x3V + V0
3I + I0
4unbalance I
3V + V0

67et 67N
37P et 81R
87 T
87 M

S 82
S 84

T 40

G 40
M 41

T 42
B 80
T 81

M 81
G 82

T 82
T 87

M 88
M 87

G 88
G 87
B 83
C 86

Sepam Offer EN 2007_01.ppt


4

Tools

Get to know the Sepam range

Situate SEPAM
protection relays
A

Protection for each type of application

Software

General introduction

Tools

Sepam Offer EN 2007_01.ppt


5

Data sheets
Series 20
Series 40
Series 80

To be included with quotes

Project managers
Description of the main
characteristics:
Selection table
Wiring diagrams
Modularity principle

Sepam Offer EN 2007_01.ppt


6

Commercial catalogue
Series 10

Used to choose and order the


right Sepam

Sepam Offer EN 2007_01.ppt


7

Commercial catalogue
Series 20
Series 40
Series 80

Used to choose and order the


right Sepam

Sales engineers
1 Selection guide
2 & 3 for each series
General presentation and
selection table
Concise description of metering,
protection, control logic and
communication functions.
Wiring diagram and general
characteristics

4 Add-on modules and


accessories
Characteristics
Connection

5 Order forms
Sepam Offer EN 2007_01.ppt
8

User manuals
Series 10

Provide the information


required to use Sepam
Series 20 and 40

Sepam Offer EN 2007_01.ppt


9

User manuals
Series 20
Series 40

Provide the information


required to use Sepam
Series 20 and 40

Design offices and users


Describe function characteristics
in detail
metering
protection
control and monitoring

Present Modbus communication


tables
Present characteristics and wiring
rules for Sepam and remote
modules

Sepam Offer EN 2007_01.ppt


10

User manuals
Series 80

Provide the information


Design offices and users
required to use Sepam Series 80
Manual 1
Describes characteristics and
wiring rules for Sepam and remote
modules
Manual 2
Describes function characteristics
in detail
metering
protection
control and monitoring

Manual 3
Presents Modbus communication
tables
Sepam Offer EN 2007_01.ppt
11

DNP3 communication
Series 20
Series 40
Series 80

Provides the information


required to implement
the DNP3 protocol

Design offices and users

Presentation of the protocol


List of data
Configuration of interfaces

Sepam Offer EN 2007_01.ppt


12

IEC 60870-5-103 communication


Series 20
Series 40
Series 80

Provides the information


required to implement
the IEC 60870-5-103 protocol

Design offices and users

Presentation of the protocol


List of data
Configuration of interfaces

Sepam Offer EN 2007_01.ppt


13

General introduction

Get to know the Sepam range

Situate SEPAM
protection relays
A

Protection for each type of application

Software

General introduction

Tools

Sepam Offer EN 2007_01.ppt


14

Basic earth-fault relay and / or overcurrent


Series 10

Different type of supply

Standard input (for conventional CTs)


Sensitive input (for conventional CTs)
Very sensitive (for G0110 CSH 120/200)

Sepam Offer EN 2007_01.ppt


15

No modularity choose the right reference


Series 10

Sepam Offer EN 2007_01.ppt


16

How to built the reference


Series 10

Sepam Offer EN 2007_01.ppt


17

Choose the base


Series 20
Series 40

SEPAM is provided with different types of base :

Series 80

Sepam Offer EN 2007_01.ppt


18

Ready to use configuration


Series 20
Series 40
Series 80

Build your SEPAM configuration :


Choose the base unit e.g. :

Then add
connectors :
Application :

Working language :
Manuals :

Sepam Offer EN 2007_01.ppt


19

Current sensor inputs


Series 20
Series 40
Series 80

CCA630 connector
The CCA630 connector is used to
connect 3 phase current
transformers to Sepam
contain interposing ring CTs with
through primaries
Can be disconnected with the power
on since disconnection does not
open the CT secondary circuit.

Sepam Offer EN 2007_01.ppt


20

Current sensor inputs


Series 20
Series 40
Series 80

CCA634 connector
The CCA634 adds an input for a
residual current transformer :
do not connect a core balance ct
do not use bases Io input
contain interposing ring CTs with
through primaries
can be disconnected with the power
on since disconnection does not
open the CT secondary circuit.

Sepam Offer EN 2007_01.ppt


21

Evolve with the installation


Series 20
Series 40
Series 80

Upgrading of functions by optional modules


possible at any time
easy to connect
implementation by simple parameter setting

Sepam Offer EN 2007_01.ppt


22

Increase input/output capacity


Module MES 114

Series 20
Series 40

Addition of a module with


10 logic inputs
4 output relays

3 models of modules
MES 114
voltage on inputs

24 to 250 V DC

MES 114 E
voltage on inputs

110 to 250 V DC
110 V AC

MES 114 F
voltage on inputs

220 to 250 V DC
220 to 240 V AC

How to choice :
- general case, without immunity constraint Vcc:
- auxiliary supply : 100 or 110V
Vcc ou Vca
- auxiliary supply >200V
Vcc ou Vca

MES114
MES114E
MES114F
Sepam Offer EN 2007_01.ppt
23

Increase input/output capacity


Module MES 120
Addition of modules with

Series 80

14 logic inputs
6 output relays

3 models of modules
MES 120
voltage on inputs
24 to 250 V DC

MES 120 G
voltage on inputs

220 to 250 V DC

MES 120 H
voltage on inputs

110 to 250 V DC

3 modules maximum
Maximum configuration:

How to choice :
- general case, without immunity constraint Vcc
- auxiliary supply 100 or 110V
Vcc
- auxiliary supply >200V
Vcc

42 inputs (3 x 14)
23 outputs (3 x 6 + 5)

MES120
MES120H
MES120G
Sepam Offer EN 2007_01.ppt
24

Improve ergonomics and the installation


Series 20
Series 40
Series 80

Remote advanced UMI module


Module flush-mounted "wherever you want"
May only be connected to a base unit without advanced UMI

Sepam Offer EN 2007_01.ppt


25

Acquire temperature data


Series 20
Series 40
Series 80

Remote MET148-2 module


Measurement of 8
temperatures
By Pt100, Ni100 or Ni120
RTD
To protect transformers,
motors and generators
Number of modules per
Sepam
Series 20: 1
Series 40: 2
Series 80: 2

Sepam Offer EN 2007_01.ppt


26

Remote measurement available


Series 20
Series 40
Series 80

Remote MSA141 module


Choice of measurement
via SFT2841
Transmission format
0-10mA
0-20mA
4-20mA

1 module per Sepam

Sepam Offer EN 2007_01.ppt


27

Enable the coupling of 2 networks


Series 80

Remote MCS025 module


For substation, transformer,
generator and busbar
applications
Measurement of 2 phaseto-neutral or phase-tophase voltages
Checking for voltage,
frequency and phase
differences between 2
different networks
Configuration via base unit
3 output relays to enable
coupling used by Sepam to
control the closing of
breaking devices

Sepam Offer EN 2007_01.ppt


28

Connect optional modules


Series 20
Series 40

Inter-module connection cables


CCA770, 0.6 m long
CCA772, 2 m long
CCA774, 4 m long

1 single chain of modules


Base unit

Cable

1st module

Cable

2nd module Cable

3rd mod.

Series 20

CCA772

MSA141

CCA770

MET148-2

CCA774

DSM303

Series 40

CCA772

MSA141

CA770

MET148-2

CCA774

DSM303

Series 40

CCA772

MSA141

CCA770

MET148-2

CCA772

MET148-2

Series 40

CCA772

MET148-2

CCA770

MET148-2

CCA774

DSM303

Sepam Offer EN 2007_01.ppt


29

Connect optional modules


Series 80

Inter-module connection cables

same as for Series 20 & 40


CCA785 must be used to connect the MCS025 module (cable supplied
with the module)

2 chains of modules
Base unit

Cable

1st module

Cable

2nd module

Cable

3rd mod.

CCA774

DSM303

Chain 1

D1

CCA772

MET148-2

CCA770

MET148-2

Chain 2

D2

CCA772

MSA141

CCA785

MCS025

Sepam Offer EN 2007_01.ppt


30

Communicate: no interface needed


Series 10
to scada system

Sepam series 10 can be daisy


chained to a RTU (with Modbus or
IEC 60870-5-103 protocols
Several functions available for
easy remote operation

control of the CB
dated events and trip currents
reading of the currents
reset of the protections

Sepam Offer EN 2007_01.ppt


31

Communicate: interfaces for


connection to one network
Series 20
Series 40
Series 80

Modbus interfaces
ACE949-2:
2-wire RS 485
ACE959:
4-wire RS 485
ACE937: Fiber optic

Number of interfaces
that can be connected:
Series 20: 1
Series 40: 1
Series 80: 2

Sepam Offer EN 2007_01.ppt


32

Communicate: interfaces for


connection to two networks
Series 20
Series 40
Series 80

Interfaces:

ACE969-TP
S-LAN

ACE969-FO

2-wire RS 485

Fiber optic

network linked to the


supervisory system

MODBUS, DNP3, IEC 60870-5-103

E-LAN

2-wire RS 485
MODBUS

network linked to a PC for


Sepam parameter setting

Number of interfaces
Series 20: 1
Series 40: 1
Series 80: 2
Sepam Offer EN 2007_01.ppt
33

S-LAN

E-LAN

Series 20
Series 40
Series 80

S20 >V0526

S40 >V3.00

S80 : all versions


Sepam Offer EN 2007_01.ppt
34

Software

Get to know the Sepam range

Situate SEPAM
protection relays
A

Protection for each type of application

Software

General introduction

Tools

Sepam Offer EN 2007_01.ppt


35

Selection guide
Series 20
Series 40
Series 80

Definition and quoting of Sepam

Selection of protection functions


Selection of remote modules
Basic configuration
Creation of the quote

Sepam Offer EN 2007_01.ppt


36

SFT2841
Series 20
Series 40
Series 80

Sepam parameter setting


2 operating modes
not connected
connected to Sepam

Windows environment
On-line help available
Comes in 3 languages,
and may also be
customized
For commissioning, the
SFT2841 tool is
useful for Series 20
recommended for Series
40
essential for Series 80

Sepam Offer EN 2007_01.ppt


37

SFT2826
Series 20
Series 40
Series 80

Display of disturbance recording files

Selection of analog
channels displayed
Selection of logic data
displayed
2 cursors to measure
differences
Possibility of zooming
on a zone of the graph

Sepam Offer EN 2007_01.ppt


38

SFTSAV
Series 20
Series 40
Series 80

Diagnosis of Sepam operating problems

Display of current and


cumulative faults
Display of passwords
This software is not
diffused yet.
Provided by the help
desk where necessary

Internal PMC use only

Sepam Offer EN 2007_01.ppt


39

SFT2840
Series 20
Series 40
Series 80

Conversion of language files

Conversion of all text


displayed on front
panel
Creation of a language
file

Sepam Offer EN 2007_01.ppt


40

SFT2842
Series 20
Series 40
Series 80

Adaptation of Sepam units in local adaptation centers

Loading of the
application in Sepam
Loading of language
files in Sepam

For local adaptation center

Sepam Offer EN 2007_01.ppt


41

SFT2885
Series 80

Creation of control logic schemes

Entry of the control logic


scheme
Simulation of operation

Sepam Offer EN 2007_01.ppt


42

SFT2887
Series 80

Conversion of Sepam 2000 control logic into Sepam Series 80


control logic
Definition of I/O
equivalence tables
Conversion of control logic
Generation of a report

Sepam Offer EN 2007_01.ppt


43

No software
Series 10

Sepam series 10 is easy to configure:


no need for a PC software
Sepam Offer EN 2007_01.ppt
44

Protection for each type of application

Get to know the Sepam range

Situate SEPAM
protection relays
A

Protection for each type of application

Software

General introduction

Tools

Sepam Offer EN 2007_01.ppt


45

Incomer protection
Detection of short-circuits and overloads on busbars
Without voltage monitoring
50/51 : maxi I 50N/51N : maxi I0
46 : unbalance
(50BF : breaker failure)

With voltage monitoring


50/51 : maxi I 50N/51N : maxi I0
46 : unbalance
50BF : breaker failure
27 (+D+R) : Under voltage (positive seq remanent)
59 +N : Over voltage neutral displacement
47 : negative sequence over voltage
81L+H : under over frequency

thermal overload for cables


49RMS with a single time constant
S81/82/84

Sepam Offer EN 2007_01.ppt


46

Incomer protection
Detection of short-circuits and overloads on busbars

Additional bus bar voltage monitoring


A single L-L or L-N voltage on the second measuring point for
27+R / 59 / 81 L+H protections

Load-shedding by ROCOF (rate-of-change of


frequency) function (81R)
for faster action

Sepam Offer EN 2007_01.ppt


47

Parallel Incomer protection


Isolate the faulty section and resupply when required
Directional phase 67 and earth fault
67N/67NC
Directional discrimination

Underpower disconnection
function 37P
disconnection of the network if the
power drawn by the load can be
supplied by the generator

Automatic transfer (AT)


Synchro-check 25

Sepam Offer EN 2007_01.ppt


48

Bus bar protection


Monitoring of voltages and frequency

Monitoring of bus bar voltages


27 +D+R : Under voltage positive seq - remanent
59 +N : Over voltage neutral displacement
47 : negative sequence over voltage
81L+H : under over frequency

Load-shedding by ROCOF (rate-of-change of


frequency) function (81R)
for faster action

Sepam Offer EN 2007_01.ppt


49

Coupling circuit breaker protection


Detection of short-circuits on bus bars
Monitoring of voltages and frequency

Monitoring of the voltages and frequency of two


bus bars
50/51 : maxi I 50N/51N : maxi I0
50BF : Breaker failure
46 : unbalance
27 +D+R : Under voltage positive seq - remanent
59 +N : Over voltage neutral displacement
47 : negative sequence over voltage
81L+H : under over frequency

Sepam Offer EN 2007_01.ppt


50

Feeder protection
Detection of short-circuits and overloads on the line
Without voltage monitoring
50/51 : maxi I 50N/51N : maxi I0
(50BF : breaker failure)
79 : re-closer

With voltage monitoring


50/51 : maxi I 50N/51N : maxi I0
50BF : Breaker failure
27 (+D+R) : Under voltage ( positive seq remanent)
59 +N : Over voltage neutral displacement
47 : negative sequence over voltage
81L+H : under over frequency

Highly capacitive feeder or isolated neutral


directional earth fault 67N/67NC

Sepam Offer EN 2007_01.ppt


51

Transformer protection
Detection of short-circuits and overloads
Detection of internal faults, Thermostat or Buchholz
Temperature monitoring by RTD
Without voltage monitoring
50/51 : maxi I 50N/51N : maxi I0
(50BF : Breaker failure)
46 : unbalance
49RMS : thermal overload
38/49T : temp monitoring
26/63 : thermostat / bucholz ( DGPT2 DMCR)

With voltage monitoring


27 (+D+R) : Under voltage ( positive seq remanent)
59 +N : Over voltage neutral displacement
47 : negative sequence over voltage
81L+H : under over frequency

Sepam Offer EN 2007_01.ppt


52

Transformer protection
Fast detection of short-circuits in the transformer

Transformer differential 87T


Several possible combinations of earth fault
protection functions
restricted earth fault differential 64REF on the
primary and/or secondary circuit
sensitive earth fault 50G/51G on the primary
and/or secondary circuit
Transformer
rating higher than
5MVA

Sepam Offer EN 2007_01.ppt


53

Transformer protection
Isolation of faulty section and different sources in parallel
when applicable
Same
source

Directional phase overcurrent 67


and earth fault 67N/67NC
Directional logic discrimination

Different
sources

Restricted earth fault differential


64REF
Synchro-check 25
Sepam Offer EN 2007_01.ppt
54

Motor protection
Detection of internal faults
Detection of power supply faults
Detection of load-related faults
Temperature monitoring by RTD
Without voltage monitoring
50/51 : maxi I 50N/51N : maxi I0 37 : undercurrent
46 : unbalance
49RMS : thermal overload
38/49T : temp monitoring
48 / 51LR / 14 : excessive starting time / locked rotor
66 : starts per hour

With voltage monitoring


32 P+Q : directional active/reactive power
(40 : field loss 78PS :pole slip)
(12/14 : over under speed)

Possibility of control logic scheme


starting by autotransformer
two operating directions
Sepam Offer EN 2007_01.ppt
55

Motor protection
Fast detection of short-circuits in the motor

Machine differential 87M

Motor rating higher


than 2MVA

Sepam Offer EN 2007_01.ppt


56

Motor-transformer unit protection


Detection of internal faults in the motor and transformer
Detection of power supply faults
Detection of load-related faults
Temperature monitoring by RTD

If the transformer is not monitored by the Sepam, a


M41 may be suitable

Sepam Offer EN 2007_01.ppt


57

Motor-transformer unit protection


Fast detection of short-circuits in the transformer and motor

Transformer differential 87T

Motor rating higher


than 2MVA

Sepam Offer EN 2007_01.ppt


58

Generator protection
Detection of internal faults
Detection of network faults
Detection of driving machine-related faults
Temperature monitoring by RTD
Monitoring of voltages and frequency
Isolated generator

Coupled generator
Detection of short-circuits on generator side by
directional protection 67
Restricted earth fault differential 64REF
Sepam Offer EN 2007_01.ppt
59

Generator protection
Fast detection of short-circuits in the generator

Machine differential 87M

Generator rating higher


than 5MVA

Sepam Offer EN 2007_01.ppt


60

Generator-transformer unit protection


Detection of internal faults in the generator and transformer
Detection of network faults
Detection of driving machine-related faults
Temperature monitoring by RTD
Monitoring of voltages and frequency

If the generator is isolated, a G40 may be suitable

Sepam Offer EN 2007_01.ppt


61

Generator-transformer unit protection


Fast detection of short-circuits in the generator and transformer

Transformer differential 87T

Generator rating higher


than 5MVA

Sepam Offer EN 2007_01.ppt


62

Capacitor bank (delta connection) protection


Detection of short-circuits in the capacitor bank

Without voltage monitoring

With voltage monitoring


Detection of overloads by thermal overload
protection 49RMS (Sepam C86 only)

Sepam Offer EN 2007_01.ppt


63

Protection of capacitor banks with 1 to 4 steps


(double star connection)
Detection of short-circuits and overloads in the capacitor bank
Monitoring of voltages and frequency
Detection of unbalance in each step

Detection of capacitor bank unbalance 51C


Detection of overloads by thermal overload
protection 49RMS, with automatic adaptation of
the number of steps in service
(steps must have the same size)

Sepam Offer EN 2007_01.ppt


64

Potrebbero piacerti anche