Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Gas-Vapor
Mixtures and
Air-Conditioning
Introduction
The air in the atmosphere normally contains some water
vapor, and it is referred to as atmospheric air. By contrast, air
that contains no water vapor is called dry air.
Moist Air Constant-Pressure Cooling and DewPoint Temperature on T-s Diagram of Water
(Fig. 13-8)
Definition-Dew Point
375
325
275
T [C]
225
175
1.491 kPa
125
75
TDP
25
-25
0
10
12
s [kJ/kg-K]
Prof Dr. Kamaruzzaman
Definition-Relative Humidity, :
mass of vapor in air
mv
Pg
Pg Pv , 1 or 100%
Steam
125
Pg Pv , 1 or 100%
T [C]
75
Tm
o Vapor State
Pg = 3.169 kPa
25
Tdp
Pv = 1.491 kPa
-25
0
s [kJ/kg-K]
10
12
Definition-Absolute Humidity or
Specific Humidity(sometimes
called humidity ratio), :
mass of water vapor in air mv
PVM
Pa M a
a
a / ( Ru T )
Pv
Pv
0.622 0.622
Pa
P Pv
Prof Dr. Kamaruzzaman
and
(0.622 ) Pg
P Pg
Definition-Volume of Mixture
per Mass of Dry Air, v:
V
mm RmTm / Pm
v
ma
ma
V
v
va
ma
Definition-Mass of Mixture :
mv
m ma mv ma (1 ) ma (1 )
ma
Definition-Mass
Flow Rate of
m a
Dry Air, :
V
m a
v
m /s
kga
3
m / kga
s
Definition-Enthalpy of Mixture
Per Mass Dry Air, h
Hm Ha Hv ma ha mv hv
h
ma
ma
ma
ha hv
Example 1
Example 1
Pv 2.548 kPa
0.6 or 60%
Pg 4.246 kPa
2.548 kPa
kgv
0.622
0.01626
(100 2.548) kPa
kgv
Example 1
h ha hv
C p , a T (2013
. 182
. T)
kJ
kgv
kJ
o
o
1005
.
(30 C ) 0.01626
(25013
. 182
. (30 C ))
o
kga C
kga
kgv
kJ
7171
.
kga
Example 2
Example 2
Pv Pg 0.4(2.339 kPa ) 0.936 kPa
Pv
0.936 kPa
w 0.622
0.622
P Pv
(100 0.936) kPa
kgv
0.00588
kga
Prof Dr. Kamaruzzaman
Example 2
mv , 2 mv ,1
ma
mv , 2 mv ,1
ma
2 1
kgv
(0.00588 0.01626)
kga
kgv
0.01038
kga
Prof Dr. Kamaruzzaman
Example 3
Example 3
At 25oC, Psat = 3.169 kPa, and with 1 = 50%
Pv ,1 1 Pg ,1 0.5(3169
.
kPa ) 15845
.
kPa
Pv ,1
15845
.
kPa
w1 0.622
0.622
P Pv ,1
(100 15845
.
) kPa
kgv
0.01001
kga
Prof Dr. Kamaruzzaman
Example 3
Therefore, when the mixture get cooled to 10oC ,
the mixture is saturated, and 1 = 100%.
Pv,2 = Pg,2 = 1.228 kPa
w2 0.622
Pv , 2
P Pv , 2
1228
.
kPa
0.622
(100 1228
. ) kPa
kgv
0.00773
kga
Prof Dr. Kamaruzzaman
Example 3
The change in mass of water per mass of dry air is
mv , 2 mv ,1
ma
2 1
kgv
(0.00773 0.01001)
kga
kgv
0.00228
kga
The Cp of Air
(fig. 13-1)
kJ
hv hg T 250.13 1.82T
kgv
o
T C
Prof Dr. Kamaruzzaman
Out
Atmospheric Air
T2=20oC
T1=30oC
P1=100kPa
=80%
Condensate at 20oC
P2=98kPa
2=95%
=200m3/s
2
2
V
V
Qnet m i (h
gz ) i Wnet m e (h
gz ) e
2
2
inlets
exits
Prof Dr. Kamaruzzaman
m m
i
inlets
exits
m a1 m a 2 m a
m v1 m v 2 m l 2
Thus
m l 2 m v1 m v 2
m a ( 1 2 )
Prof Dr. Kamaruzzaman
m a
Q net
ha1 1hv1 ha 2 2 hv 2 ( 1 2 )hl 2
m a
Q net
ha 2 ha1 2 hv 2 1hv1 ( 1 2 )hl 2
m a
Q net
C pa (T2 T1 ) 2 hv 2 1hv1 ( 1 2 )hl 2
m a
Prof Dr. Kamaruzzaman
P1 Pv1
100 3.396
kgv
0.02187
kga
Pv 2 2 P2
(0.95)(2.339 kPa ) 2.222 kPa
0.622 Pv 2 0.622(2.222)
2
P2 Pv 2
98 2.222
kgv
0.01443
kga
Prof Dr. Kamaruzzaman
kJ
hv1 2556.3
kgv
kJ
hv 2 25381
.
kgv
kJ
hl 2 83.96
kgv
Prof Dr. Kamaruzzaman
Q net
C pa (T2 T1 ) 2 hv 2 1hv1 ( 1 2 )hl 2
m a
kJ
kgv
kJ
o
1005
.
(20 30) C 0.01443
(25381
.
)
o
kga C
kga
kgv
kgv
kJ
kgv
kJ
0.02187
(2556.3
) (0.2187 0.01443)
(83.96
)
kga
kgv
kga
kgv
kJ
8.622
kga
Prof Dr. Kamaruzzaman
qout
Q net
kJ
8.622
m a
kga
V1
m a
v1
Prof Dr. Kamaruzzaman
Pa1
(100 3.396) kPa
kJ
3
m
0.886
kga
m
200
kga
min
m a
2251
.
3
m
min
0.886
kga
Q out
kga
kJ 1 min 1kWs
m a qout 2251
.
(8.622
)
min
kga 60s kJ
32.35 kW 9.196 Tons
Prof Dr. Kamaruzzaman
water
2
2
V
V
Qnet m i (h
gz ) i Wnet m e (h
gz ) e
2
2
inlets
exits
Neglecting the kinetic and potential energies and noting that
the heat transfer and work are zero, we get
m a1ha1 m v1hv1 m l 2 hl 2 m a 2 ha 2 m v 2 hv 2
m m
i
inlets
exits
m a1 m a 2 m a
m v1 m l 2 m v 2
m l 2 m v 2 m v1
m a ( 2 1 )
Prof Dr. Kamaruzzaman
ha 2 ha1 2 (hv 2 hl 2 )
1
2 (hv1 hl 2 )
C pa (T2 T1 ) 2 h fg 2
2 (hg1 h f 2 )
Prof Dr. Kamaruzzaman
Pv1
1 0.622
P1 Pv1
1 P1
Pv1
0.622 1
Pv1
1
Pg1
Most air-conditioning processes can be modeled as steady-flow processes, and therefore they can be analyzed by applying the steady-flow mass (for both dry air and water) and energy balances,
Dry air mass:
Water mass:
Energy:
where subscripts i and e denote inlet and exit states, respectively. The changes in kinetic and potential energies are assumed to be negligible.
T2=20oC
T1=24 C
o
P1=100kPa
1= ?
1 = ?
h1 = ?
Make-up
Water
At 16oC
P2=100kPa
2=100%
R
||P P 1818
. kPa
100% U
|
0.622 P
0.622(1818
. )
V
S
.
T 16 C W
|| P P 100 1818
kg
|T 0.0115 kg
v2
g2
v2
v2
kJ
h f 2 76.2
kgv
kJ
hv1 2545.4
kgv
kJ
h fg 2 2463.6
kgv
Prof Dr. Kamaruzzaman
C pa (T2 T1 ) 2 h fg 2
2 (hg1 h f 2 )
b g
kJ
kgv
kJ
o
1005
.
16 24 C 0.0115
(2463.4
)
o
kga
kgv
kga C
kJ
(2545.4 67.2)
kgv
kgv
0.00820
kga
Prof Dr. Kamaruzzaman
1 P1
Pv1
0.622 1
0.00820(100kPa )
0.622 0.00820
13
. kPa
Pv1
Pv1
1
Pg1 Psat @ 24 o C
13
. kPa
0.436 or 43.6%
2.985 kPa
h1 ha1 1hv1
C pa T1 1hv1
kJ
kgv
kJ
o
1005
.
(24 C ) 0.00820
2545.4
o
kga C
kga
kgv
kJ
44.99
kga
Psychrometric Chart
The properties of atmospheric air at a specified total pressure are presented in
the form of easily readable charts, called psychrometric charts. The lines of
constant enthalpy and the lines of constant wet-bulb temperature are very
nearly parallel on these charts.
Various Air-Conditioning
Processes
The needs of the human body and the conditions of the environment are not quite compatible. Therefore, it often
becomes necessary to change the conditions of a living space to make it more comfortable. Maintaining a living space
or an industrial facility at the desired temperature and humidity may require simple heating (raising the temperature),
simple cooling (lowering the temperature), humidifying (adding moisture), or dehumidifying (removing moisture).
Sometimes two or more of these processes are needed to bring the air to the desired temperature and humidity level.
Example 4:
Determine the relative humidity, humidity ratio
(specific humidity), enthalpy of the atmospheric
air per mass of dry air, and the specific volume
of the mixture per mass of dry air at a state
where the dry-bulb temperature is 24oC, the wetbulb temperature is 16oC, and atmospheric
pressure is 100 kPa.
Example 4:
From the psychrometric chart read
44%
gv
kgv
8.0
0.008
kga
kga
kJ
h 46
kga
m3
v 0.853
kga
Prof Dr. Kamaruzzaman
Example 5:
For the air-conditioning system shown below in
which atmospheric air is first heated and then
humified with a steam spray, determine the
required heat transfer rate in the heating
section, and the required steam temperature in
the humidification section when the steam
pressure is 1 MPa.
Example 5:
Heating fluid
Out
In
s
Steam, P = 1 MPa
Throttle
Atmospheric
Air
T3=25oC
T1=5 C
o
P1=100kPa
1=90%
T2=24 C
o
P3=100kPa
3=45%
=60m3/min
Example 5:
Psychrometric Diagram
0.050
0.045
0.040
0.035
0.8
0.030
30 C
0.025
0.6
0.020
h3 =48 kJ/kga
0.015
0.010
0.005
0.000
-10
20 C
h2 =37 kJ/kga
h1 =17 kJ/kga1
10 C
3 =0.0091kgv/kga
0.2
0C
-5
0.4
1 = 2 =0.0049 kgv/kga
2
0
10
v1 =0.793 m^3/kga
15
20
25
30
35
40
T [C]
Prof Dr. Kamaruzzaman
Example 5:
Apply conservation of mass and conservation of
energy for steady-flow to process 1-2.
Conservation of mass for the steady-flow
control volume is
m m
i
inlets
exits
m a1 m a 2 m a
Prof Dr. Kamaruzzaman
Example 5:
For the water vapor (Note: no water is added or
condensed during simple heating):
Thus
m v1 m v 2
2 1
h ha hv
Prof Dr. Kamaruzzaman
Example 5:
We obtained
E in E out
Q in m a h1 m a h2
Q in m a (h2 h1 )
Prof Dr. Kamaruzzaman
Example 5:
Now to find
chart.
m a
R
kJ
|| h 17 kg
| 0.0049 kg
90% U
V
S
kg
T 5 C W
||
m
||Tv 0.793 kg
1
Example 5:
Now to find
chart.
m a
kgv
2 1 0.0049
kga
T2 24 C
o
U
kJ
|VR
h 37
S
kg
T
|W
2
Example 5:
The mass flow rate of dry air is given by
V1
m a
v1
3
m
60
kga 1 min
kga
min
m a
75.66
1261
.
3
m
min 60s
s
0.793
kga
Prof Dr. Kamaruzzaman
Example 5:
The required heat transfer rate for the heating section is
kga
kJ 1kWs
Qin 1261
.
(37 17)
s
kga kJ
25.22 kW
This is the required heat transfer to the atmospheric
air.
Example 5:
At the exit, state 3, T3 = 25oC and 3 = 45%. The
psychrometric chart gives
R
kJ
|| h 48 kg
| 0.0089 kg
45% U
V
S
kg
T 25 C W
||
m
|| v 0.858 kg
T
3
Example 5:
Apply conservation of mass and conservation of energy
to process 2-3. Conservation of mass for the steadyflow control volume is
m m
i
inlets
exits
m a 2 m a 3 m a
Prof Dr. Kamaruzzaman
Example 5:
For the water vapor (Note: water is added during the
humidification process):
m v1 m s m v 2
m s m v 2 m v1
m s m a ( 2 1 )
kga
kgv
1261
.
(0.0089 0.0049)
s
kga
kgv
0.00504
s
Prof Dr. Kamaruzzaman
Example 5:
Neglecting the kinetic and potential energies and noting
that the heat transfer and work are zero, the
conservation of energy yields
E in E out
m a h2 m s hs m a h2
m s hs m a (h2 h1 )
Prof Dr. Kamaruzzaman
Example 5:
Solving for the enthalpy of the steam
m a ( 3 2 )hs m a (h2 h1 )
h2 h1
hs
3 2
Prof Dr. Kamaruzzaman
Example 5:
hs
kJ
( 48 37)
kgv
kgv
( 0.0089 0.0049)
kga
kJ
2750
kgv
Evaporative Cooling
At a given P and T, a pure substance will exist
as a compressed liquid if T<T sat @ P
(Fig. 13-27)
Cooling Tower
(Fig. 13-31)
A Spray Pond