Electrical design brief

Electrical outlet mounting height detail

Electrical Load calculation


1.00

Block-177 load estimation

Load for 2 and 3 Bedroom apartments - 45 Nos @


4.5/6.2kW - Three phase/Apartment

Total

202.50 kW

202.50 kW

Common Load

common area Loads (Stilt, corridor, Staircase )

23.00 kW

Lifts 2 nos. @ 7.5kW/lift

15.00 kW

Total

Total Block -177

38.00 kW
240.50 kW

SUMMARY - TRANSFORMER SIZING - Phase II


Total
Connected
load (kW)

Existing
22/0.415kV
transformers
DT-3

Slno

Description

Total No.
of services

1.00

Total Block
-177

50

240.50

2.00

Total Block
-178

50

240.50

3.00

Total Block
-179

29

136.00

4.00

Total Block
-180

29

136.00

5.00

Total Block
-181

29

136.00

6.00

Total Block
-182

29

136.00

7.00

Total Block
-183

29

136.00

245.00

1161.00

Total load

Remarks

DT-4

TR-Yard-A
DT-2

DT-1

Electrical room selection procedure:

TNERC TAMIL NADU ELECTRICITY REGULATORY COMMISSION

TNEDC - TAMIL NADU ELECTRICITY DISTRIBUTION CODE

For indoor metering, an electrical room with RCC roof having a clear floor
area 5mx6m with a vertical clearance of 3.7 metres between the floor
and the ceiling/beam bottom with locking facility, exhaust fan and
adequate size of cable duct shall be provided at the ground/basement
floor for installing the Licensees equipments, etc. This room shall be of
fireproof and weatherproof

For outdoor metering, a clear space of 10 metre x 4 metre or 5 metre x 5


metre open to sky shall be provided. This enclosure shall be at the
periphery of the building and shall be cut off from other portions of the
premises by fire resistance walls. These areas shall be specifically shown
in the plan. Before the plan is sent to the competent authority for
approval, it shall be sent to the Engineer and got approved. The point of
supply shall be within 30 meters from the main gate easily accessible
and visible and satisfactory with regards to security aspects. Failure to
comply with the above requirements will result in denial of supply

Sequence of Electrical works

RECOMMENDED MAKE OF EQUIPMENTS/COMPONENTS FOR ELECTRICAL

Description

Approved Make

LT Panel

CREATIVE / POWER CONTROLS/ VINTECH /


ABB / INDOASIAN / SIEMENS

UPS / Inverter

CONSUL / NUMERIC/DUBAS/ MICROTEK

MCB / ELCB

LEGRAND / HAGER / MOELLER / SCHNEIDER

MCB Distribution Boards


Cables

LEGRAND / HAGER / ELTEE/MANILEC /


SCHNEIDER
UCL / GEMSCAB / POLYCAB / RALLISON / CCI /
TORRENT/
Gloster

Cable Glands

COMET / PRABHAT / SMI

Cable Lugs and Accessories

DOWELLS / LOTUS

Cable Tray & Accessories

PAIFAB (BANGALORE) / INDIANA / PROFAB

Light Fittings

THORN / WIPRO /PHILIPS

Lamps

PHILIPS / OSRAM

Switch / Switch Box / Socket / Fan

MK / MOSAIC

PVC Wires

FINOLEX / POWER FLEX / RR CABLES /


POLYCAB / RALLISON

PVC Conduit

AVON / GARWARE / VASAVI

Earth Electrode

ASHLOK / GALAXY

Data Cable

DAX / FINOLEX

Telephone Cable

DELTON / FINOLEX

PHE Mounting Height Detail

Coordination Detail

Sequence of Plumbing works

RECOMMENDED MAKE OF EQUIPMENTS/COMPONENTS FOR PLUMBING


Description

Approved Make

PVC SWR Pipes,IS 13592

Prince / Supreme / Astral

Upvc SCH 40 Pipes & Fittings

Aquarus, Astral

CI Manhole cover and frame

Neco / BIC

SFRC MH cover

KK product /NECO/Equivalent make

cPVC pipes and fittings

Astral / Ashirwad

Concealed Stop Cock

Jaquar / Equivalent

Sanitary Wares

RAK Ceramic / Equivalent

Cp fittings

Jaquar / Equivalent

Pipe supports

Hitech pipe/Intellotech

Stainless Steel Sink

Jaquar /franke/Diamond/Nirali

Ball valves

Sant / RB (Italy)/ Astral- ( Screwed


end)Leader/
Zoloto/Itap/RB/Hawa

Strainer

GRAND FRIX/TELFLOW/GUJRATOTOFILT

Butterfly valves

Audco /KEYstone/BDK/Fouress

Rain water outlet ( Dome type)


GI fittings

Vigneshwara fabricator, bangalore/


Equivalent
R brand /Bharat Forge/Tube products/Vs
brand/Goyal

One pipe system


S/N

Description

Merits

Air pressure
Fluctuation(negative and NA
positive pressure)

Discharging of soil and


waste water

Efficiently functional for


ground and first floor

Fowl gas in the toilets

NA

Branch Vent pipe

To minimise air admittance


valve BVP incorporated

Piping system

Discharge washing
machine waste water

Costing

De-Merits
Required additional Vent
stack
More than two toilet
discharging time will be
high
Water get evaporated in
trap seal during dry / not
usage of toilets may lead
to fowl gas
Branch vent required
every individual loading
units (EWC, WB, FT,
Kitchen sink)

Single pipe can be used for


Pipe dia size will be
discharging of soil and waste
increase depends on
water with additional vent
loading units
pipe
Detergent discharge may
leads to forming of foam
NA
due to continuous flow of
water
High Material cost
(additional fittings to be
Low erection cost
used like Y, Tee, Elbow
etc.)

Two pipe system


S/N

Description

Merits

De-Merits

Air pressure
Fluctuation(negative and Self air venting
positive pressure)

NA

Discharging of soil and


waste water

Efficiently functional for


multistories building

NA

Fowl gas in the toilets

Return gas will be controlled Additional gully trap


by gully trap
required in ground floor

Branch Vent pipe

Not required

NA

Pipe dia size will be reduced


due to distribution of loading
units in double pipe
No continuous flow of
detergent waste water due to
minimum loading unit

Individual pipes to be
installed for soile and
waste water

High erection cost

Piping system

Discharge washing
machine waste water

Costing

Low material cost

Maintenance

Low maintenance(minimised
NA
soaking)

Separate stack required


for waste water.