Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
SM6
MV Metal enclosed cubicle up to 24 kV
Aplication:
Secondary distribution
Low Isc level (<20kA/1s)
Type of cubicles:
Switch and fuse switch
Circuit Breaker (Incoming,Outgoing and Coupler) fixed and draw out
Direct incomer or outgoer
Busbar metering (CM, GBC-A/B)
Other functional (interface VM6, Aux power,intermediate,etc)
SM6
SM6
MV Metal enclosed Switch cubicle up to 24 kV
Switch Cubicle:
SM6
MV Metal enclosed Switch cubicle up to 24 kV
Switch :
Switch : rating current : 630A and 400 A
SF6 with pressure : 0.4 bar relatif pressure
Sealed pressure system
Earthing switch
Switch disconnector
Safety membrane
Busbar :
rating current : 630A and 1250 A
Rating voltage : 7.2kV, 12kV, 17.5kV, 24kV
Insulated busbar
Isc : 20kA/1s max
Cover with field distributors
Connection in horizontal plane
Easy for manintenance
SM6
SM6
MV Metal enclosed CB cubicle up to 24 kV
CB Cubicle:
6
6. CT and VT
SM6
MV Metal enclosed CB cubicle up to 24 kV
CB :
CB : rating current : 400A, 630A and 1250 A
SF6 with pressure : 0.5 bar relatif pressure
(no vacuum version at the moment until 2005 or beg 2006)
Sealed for life, no pressure switch
Earthing switch
Switch disconnector
Safety membrane
Switch disconnector & ES:
Isolate the CB from main busbar
Earthed the CB compartment
Main Busbar :
Same as Switch cubucle
SM6
MV Metal enclosed CB cubicle up to 24 kV
CB : (630A - Isc 25kA/3s for Singapore market)
CB : rating current : 630A (using 1250A CB)
LMK Type Tested
Main Busbar 630A (using busbar 1250A to increase mech strength)
Earthing switch 20 kA
Switch disconnector using 1250A
Incoming feeder without ES, outgoing feeder with ES
Incoming CT with class X for Solkor relay
Metering Cubicle:
CT with protection class
VT with primary fuse
Door interlock with incoming feeder
CT for metering inside bottom pan
SM6
General
Characteristic:
10
SM6
General
Characteristic:
11
SM6
MV Metal enclosed Switch cubicle up to 24 kV
Switch cubicle:
12
SM6
MV Metal enclosed Switch cubicle up to 24 kV
Fuse Switch cubicle:
375/500
375/500
750
375/500
13
SM6
MV Metal enclosed Switch cubicle up to 24 kV
CB cubicle:
14
SM6
MV Metal enclosed Switch cubicle up to 24 kV
CB cubicle:
15
SM6
MV Metal enclosed Switch cubicle up to 24 kV
ATS cubicle:NSM
16
SM6
MV Metal enclosed Switch cubicle up to 24 kV
Metering cubicle:
17
SM6
MV Metal enclosed Switch cubicle up to 24 kV
All functions cubicle:
18
SM6
MV Metal enclosed switch cubicle up to 24kV
Switch Operating mechanism :
19
SM6
MV Metal enclosed switch cubicle up to 24kV
Motorized optional for switch unit :
20
SM6
MV Metal enclosed CB switch cubicle up to 24kV
Motorized optional for switch unit :
Option:
operation counter
opening release:
Shunt trip, mitop & under voltage
closing release: shunt trip
Mechanism charge indication: 1C
Aux contact of CB : 4NO + 4 NC
21
SM6
MV Metal enclosed CB cubicle up to 24kV
Low Volatge compartment:
There are 2 LV compartment in SM6 cubicle:
a. Front LV compartment (open with screw) (A)
b. LV box compartment at the top of cubicle (with handle and key
lock) (B or C)
22
SM6
MV Metal enclosedSM6 cubicle up to 24kV
CTs:
CT for IMC cubicle:
CT
23
SM6
MV Metal enclosedSM6 cubicle up to 24kV
CTs:
CT for CB cubicle: (DM1A,DM1W,DM1D,DM2, GBC-A,GBC-B)
24
SM6
MV Metal enclosedSM6 cubicle up to 24kV
VTs:
VT for cubicles: CM, DM1A,DM1W,DM2, DM1D, GBC-A,GBC-B
VT: Phase to ground (wye-wye connection)
Grounding and Ungrounding network system (VT selection)
Up to 22kV/V3
25
SM6
MV Metal enclosedSM6 cubicle up to 24kV
VTs:
VT for cubicles: CM2, GBC-A,GBC-B
VT: Phase to Phase (open delta connection)
Up to 22kV/V3
26
SM6
MV Metal enclosedSM6 cubicle up to 24kV
VTs:
VT for cubicles: TM
VT: Phase to Phase (Single phase transformer)
Up to 22kV/V3
Use for aux power supply 230VAC(max 2500VA/4000VA)
27
SM6
MV Metal enclosedSM6 cubicle up to 24kV
Surge Arrestor:
Can be installed in cubicle: IM500, DM1A, DM1W,GAM
Surge Arrestor in IM cubile to protect cable side
Surge Arrestor in GAM cubicle to protect busbar and cable side
Surge Arrestor in DM1A, DM1W cubicle to protect cable side
Surge arrestor 24kV 10kA (Elina or ABB-MWK 24)
28
SM6
29
SM6
MV Metal enclosed SM6 cubicle up to 24kV
Protection:
Using Sepam 1000+ series (S20,T20,M20,B21,B22)
With external power supply (DC:24,48,110V or AC:230V)
Using VIP relay integrated in DM1-S with 3 CR sensor current
No need external power supply.(internal power)
Tripping release: mitop
VIP 35 OCR (DT) + EFR (IT)
VIP 300LL OCR(IT,VIT,EVIT)
Using SF set CB: VIP 200 or 201
Dedicated for transformer protection
No need external power supply
Protection against Over Current and Earth Fault
Using Statimax or Sepam 100LA
Using regular CT (I sec: 5A or 1 A)
No need external power supply
Protection against Over Current(DT) and Earth Fault (DT)
Tripping release : mitop
30
SM6
MV Metal enclosed SM6 cubicle up to 24kV
Protection:
31
SM6
MV Metal enclosed SM6 cubicle up to 24kV
Source Change Over : NSM Cubicle.
Consist of 2 Incmoing switch
Mechanically interlock (as standard offer)
No need VT to sensing the voltage (voltage sensor by using
capacitive voltage devider)
Including DC power supply 24VDC (need aux supply 230VAC)
Switch with motorized operation.
Switch Rated current : 630A/switch 24kV
Change over controller : RCV420 and RNS 11
With Earthing switch (at both cable side)
With neon indicator (at both side)
Main busbar 630A or 1250A
Note:
RCV 420 for Stand by power
RNS 11 for Emergency power (Genset)
32
SM6
NSM
33
SM6
NSM
34
SM6
INTERLOCKING
Interlocking is provided by key lock
Comply with IEC recomendation 60298 and EDF spec HN 64-S-41
Built in padlocking fasilities (padlocks not supplied)
For knock outs that may be used for key locks(supplied on request) for mechnism
locking functions.
35
SM6
INTERLOCKING
36
SM6
INTERLOCKING
37
SM6
Key Type Interlock:
38
SM6
39
SM6
40
SM6
MV Metal enclosed CB cubicle up to 24kV
Cable connection:
Bottom entry (as standard)
41
SM6
MV Metal enclosed CB cubicle up to 24kV
Cable connection:
Connection height: Switch and Fuse switch
42
SM6
MV Metal enclosed CB cubicle up to 24kV
Cable connection:
Connection height: DM1 and GAM
43
SM6
MV Metal enclosed SM6 cubicle up to 24kV
Cable connection from above:
(Incoming from top,outgoing from bottom)
TOP Incoming:
Dry type and 1c cables
No LV box in the unit.
VPIS for incoming voltage
monitor
44
SM6
MV Metal enclosed SM6 cubicle up to 24kV
Dimension and weight:
45
SM6
46
SM6
GBC-A(s)
DM1-D
CB
GBM
DM1-A
CB
DM1-A
CB
DM1-A
CB
47
Using
DM1-A cubicle
Change
Easy
No
Save
Alternative
Price
+ 3 % DM1-A
control
plug in
bolt same
as DM1-A
48
SM6
49