PROVIDING ENGINEERING FOR OPERATION TRAINING

MV SWITCHGEAR WITH SEPAM RELAY AND POWER


QUALITY DISTURBANCES

Understand Sepam control logic

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- General
Sepam performs the control and monitoring functions:
Predefined and fit the applications most frequently used
ready to use, simple parameter setting: Local annunciation, Circuit breaker/
contactor control, Latching / acknowledgement
Customized functions by using the SFT2841 software:
can be adapted for particular needs by logic equation editor, Logipam software
(by expert), customization of the control matrix, LEDs and display messages.
Operating principle: 3 phases
1. Acquisition of input data: protections, inputs, remote control via the
communication (TC)
2. Actual logic processing of the control and monitoring function
3. Utilization of the processing results: activating output, message, LED, remote
indicator via the communication (TS)

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- General
Operating principle:

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Logic inputs and outputs
Can be assigned to predefined functions.
May be used for the SFT2841 customization functions
May also be inverted for undervoltage type operation.
A default input / output assignment is proposed for the most frequent uses.
by clicking on the "Standard assignment" button in SFT2841 software

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Logic inputs and outputs

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Logic inputs and outputs

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Circuit breaker / contactor control
This function controls the breaking device (ANSI code 94/69)
tripping on output O1
protection unit (units configured to trip the circuit breaker)
logic discrimination
remote control via the communication link
external protection
open order by logic input
closing on output O11
recloser
remote control via the communication link
closing control by logic input
inhibition of closing on output O2
trip circuit fault (TCS)
SF6 fault
inhibit order by logic input.

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Circuit breaker / contactor control
Circuit breaker / contactor control- Associated functions
Circuit breaker / contactor control with lockout function (ANSI 86)
grouping of all tripping conditions and breaking device control
latching of the tripping order with inhibition of closing until the cause of tripping
disappears and is acknowledged by the user
indication of the cause of tripping: local & remote
Latching/acknowledgment the tripping outputs
all the protection functions and all the logic inputs may be latched individually.
The logic outputs set up in pulse mode
Latched data are saved in the event of a power failure
All latched data may be acknowledged locally on the UMI, or remotely by means of
a logic input or via the communication link
Associated with the "Circuit breaker / contactor control" function.

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Circuit breaker / contactor control
Circuit breaker / contactor control- Associated functions
TC/circuit breaker position discrepancy
This function detects a discrepancy between the last remote control order received
and the actual position of the circuit breaker.

Circuit breaker / contactor control- Associated functions


Tripping
It indicates whether a Sepam internal or external protection has tripped.

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Circuit breaker / contactor control
Circuit breaker / contactor control- Associated functions
Trip circuit supervision and open / closed matching (With MES option)
designed for trip circuits with shunt trip units. The function detects:
circuit continuity
loss of supply
mismatching of position contacts
designed for trip circuits with with undervoltage trip units. The function detects:
mismatching of position contacts,
coil supervision being unnecessary in this case

1. The function inhibits closing of the breaking device


2. The function is activated if inputs I11 and I12 are set
respectively as circuit breaker "open position" and circuit
breaker "closed position".

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

10

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Circuit breaker / contactor control
Circuit breaker / contactor control- Associated functions
Open and close order supervision
Following a circuit breaker open or close order, after a 200 ms time delay, the circuit
breaker has actually changed status.
If the circuit breaker status does not match the last order sent, a "Control fault"
message and remote indication TS108 are generated.

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

11

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Logic discrimination
For Radial network (ANSI code 68)
full tripping discrimination
a substantial reduction indelayed tripping of the circuit breakers located nearest the
source.

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

12

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Disturbance recording triggering
The recording of analog and logic signals may be triggered by different events,
according to control matrix parameter setting or by manual action:
triggering by the grouping of all pick-up signals of the protection functions in service
triggering by the outputs of selected protection functions
triggering by selected logic inputs
triggering by selected outputs Vx (logic equations)
manual triggering by a remote control order (TC10)
manual triggering via the SFT2841 software tool.

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

13

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Switching of groups of settings
Switching from one group of settings to another makes it possible to adapt the
protection characteristics to suit the electrical environment of the application
There are two groups of settings, group A / group B, for:
the phase overcurrent
the earth fault
directional phase overcurrent and directional earth fault protection functions
The setting switching mode is determined by parameter setting:
switching according to the position of logic input I13 (0 = group A, 1 = group B)
switching by remote control (TC3, TC4)
forced group A or group B.

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

14

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Local indication (ANSI code 30)
Events may be indicated on the front panel of Sepam by:
appearance of a message on the display of the advanced UMI
lighting up of one of the 9 yellow signal lamps
Predefined messages:
in English, factory messages, not modifiable
in the local language, according to the version delivered
Personalized user message editor in SFT2841

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

15

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Control matrix
The control matrix is used for simple assignment of :
the logic outputs and signal lamps to information produced by the protection units
program logic and logic inputs
The matrix may also be used to display the alarms connected to the information:
in English, factory messages, not modifiable
in the local language, according to the version delivered
Guarantees the consistency of the parametersetting with the predefined functions

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

16

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Logic equations
to configure simple logic functions by combining data received from the
protectionfunctions or logic inputs
By using logic operators (AND, OR, XOR, NOT) and time delays, new processing
operations and indications may be added to the existing ones
The logic functions produce outputs
that may be used:
in the matrix to control relay outputs, light
up LEDs or display new messages
in the protection functions to create new
inhibition or reset conditions
in circuit breaker control to add cases of
circuit breaker tripping, closing or inhibition
in disturbance recording to record
particular logic data.

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

17

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Self-tests and fail-safe position
Sepam Self-tests
The self-tests are run when Sepam is initialized
and/or during its operation..
List of self-tests which place Sepam in the failsafe position

List of self-tests which do not place Sepam in the


fail-safe position

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

18

PROVIDING ENGINEERING FOR OPERATION TRAINING MV SWITCHGEAR


WITH SEPAM RELAY AND POWER QUALITY DISTURBANCES

Understand Sepam control logic


Sepam Control and Monitoring functions- Self-tests and fail-safe position
Sepam in the Fail-safe position
All the output relays are forced to the idle state
All protection functions are inhibited
The watchdog output indicates failure
A red LED on the Sepam front panel is on and a diagnostic message appears on the Sepam display
Minor failure: Sepam switches to downgraded operation.
Major failure: Sepam switches to the fail-safe position and attempts a restart during which it again runs its
self-tests. There are 2 possible scenarios:
the internal failure is still present. It is a permanent failure.
the internal failure is no longer present. It is a transient failure.

Using the watchdog


The watchdog output activates a system alarm.
To ensure that Sepam protection functions are working correctly.

Schneider Electric - Field Services Division

Operation training for electrical engineer - NESTLE Viet nam Tri An Plant

19

Thanks!
Make the most of your energy