Sei sulla pagina 1di 6

Single Phase Scenario

DC Load

190V~220V

MCB

TP power

Battery

AC load
The meanings of parameter :

I MAX

WAC WLoad WBat / 0.95

U min 0.8

IMAX Max current through MCB


WAC The Maximum AC load;
WLoad The Maximum DC load;
WBat The battery charging power
Umin Min voltage per phase from the grid;
0.95 The power system efficiency;
0.8 The recommended safety factor for MCB capacity ( 25%
redundance protection)

HUAWEI TECHNOLOGIES CO., LTD.

Huawei proprietary. No spread without permission.

Page 1

Three Phase Scenario


Rectifier in TP power
No.1

L1
L2
L3
N

No.4
No.2

The meanings of parameter :

DC Load

IMAX Max current through MCB


WAC The Maximum AC load;

No.3

WRec The real output power of

Battery

rectifier

MCB

Umin Min voltage per phase from


the grid;
0.95 The power system

AC load
CASE 1.
Max current will be in L1 if we are using REC.1
& REC. 4 for power supply in the same time. Or
the total power consumption >9000W.

I MAX

2 WRe c

U min 0.8 0.95

HUAWEI TECHNOLOGIES CO., LTD.

efficiency;

CASE 2 .
0.8 The recommended safety
Max current will be in L3 if we are not using
factor for MCB capacity ( 25%
REC.1 and REC.4 for power supply in the same
redundance protection)
time and the total power consumption <9000W.

I MAX

Huawei proprietary. No spread without permission.

WAC WRe c / 0.95

U min 0.8
Page 2

Scenario 1: Indoor, single phase


Scenario:
2G+3G
Configuration:
1*BBU + 9* RRU + 1*TM
Battery:
600Ah
Max DC load power consumption
7400W
Battery Charging power:
3384W
AC power :
0W

HUAWEI TECHNOLOGIES CO., LTD.

For single phase input:

I MAX

WAC WLoad WBat / 0.95

U min 0.8

I MAX 74.68 A

80A Breaker is recommended for single phase


scenarios basing on current configuration
when in max power consumption.

Huawei proprietary. No spread without permission.

Page 3

Scenario 2: Indoor, three phase


Scenario:
2G+3G
Configuration:
1*BBU + 9* RRU + 1*TM
Battery:
600Ah
Max DC load power consumption
7400W
Battery Charging power:
3384W
AC power :
0W

HUAWEI TECHNOLOGIES CO., LTD.

For three phases input:(Case 2, total power >9000W)

I MAX

2 WRe c

U min 0.8 0.95

*WRec =(7400W+3384W)/4

=2696.75W

I MAX 37.35 A

40A Breaker is recommended for three phase


scenarios basing on current configuration
when in max power consumption.

Huawei proprietary. No spread without permission.

Page 4

Scenario 3: Outdoor, single phase


Scenario:
2G+3G
Configuration:
1*BBU + 9* RRU + 1*TM
Battery:
300Ah
Max DC load power consumption
7500W
Battery Charging power:
2538W
AC power :
500W(heater)

HUAWEI TECHNOLOGIES CO., LTD.

For single phase input:

I MAX

WAC WLoad WBat / 0.95

U min 0.8

I MAX 72.8 A

80A Breaker is recommended for single phase


scenarios basing on current configuration
when in max power consumption.

Huawei proprietary. No spread without permission.

Page 5

Scenario 4: Outdoor, three phase


Scenario:
2G+3G
Configuration:
1*BBU + 9* RRU + 1*TM
Battery:
300Ah
Max DC load power consumption
7500W
Battery Charging power:
2538W
AC power :
500W(heater)

HUAWEI TECHNOLOGIES CO., LTD.

For three phases input:(Case 2, total power >9000W)

I MAX

2 WRe c

U min 0.8 0.95

*WRec =(7500W+2538W)/4

=2509.5W

I MAX 34.75 A

40A Breaker is recommended for three phase


scenarios basing on current configuration
when in max power consumption.

Huawei proprietary. No spread without permission.

Page 6