Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
1/44
Surge definition
Self oscillations of pressure and flow, often
including a flow reversal in the centrifugal
and axial compressors is known as surging
Surge description
Flow reversal in 20 to 50 milli seconds
Surge cycles at a rate of 0.3s to 3 s per cycle
Compressor vibrates
Temperature rises
whooshing noise or Clanking noise
Trip may occur
Conventional instruments /human operators
may fail to recognise surge
4/44
Surge leads to
Once surge is induced, the flow rate & pressure
will oscillate drastically until the cause is
removed or protective devices shut down the
machine or a failure occurs.
The excessive thrust bearing & impeller loads,
vibration & rising gas temperatures associated
with surge can produce process upsets &
severe compressor damage if more than a very
few surge cycles are experienced.
5/44
Objective
of Surge Protection Systems
To prevent Compressor Damage due to surge or
Process Upset without sacrificing energy
efficiency or system capacity
To maintain selected process variables within
Safe or acceptable ranges
6/44
VSDS
Compressor
TT
FT
PT
PT
TT
UIC
Discharge
Suction
How to prevent
8/44
The challenges
Location of operating point
Location of surge limit
High speed of approaching surge
Control loop interactions
Load sharing for multiple compressor
Co-coordinating control of compressor &
driver
9/44
Hp
Surge Control Line
Surge Limit Line
Maximum Pressure
2
2
2
1
1
Surge Control
Zone
Q s
Antisurge Controller Actions
10/44
Control Actions
For any given performance curve (Operating Curve)
the point of minimum flow & maximum pressure is
known as the surge limit point. The locus of all such
points defines a curve known as Surge Limit line.
The anti surge controllers task is to keep the
operating point to the right of the surge limit line.
This is accomplished by opening an anti surge
valve to recycle enough gas to maintain the
required minimum flow rate.
11/44
Control Actions
However, because the dynamics of the system are
inherently slow, this control action must be started
before the operating point reaches the surge limit.
The point at which the controller starts to open the
valve is known as Surge Control Point. The locus of
all such points defines a surge control line. The
Distance between SCL& SLL is refereed as the
margin of safety. Region left to the SCL is known as
Surge Control Zone.
Anti surge Controller starts opening the recycle
valve, When ever the operating point is in the Surge
Control Zone
12/44
Pressure:
Hp
Rc
Pd
Pc
SOL
SLL
RTL
New SCL
After SO
SCL
Operating Point
Rt
b1
b2
13/44
Control Lines
Control Actions
16/44
18/44
Series 3 Controllers
Series 3 Controllers
Series 3 Controllers
Serial Communication Features : Series 3 Anti Surge Controllers
are equipped with either a three or four port Serial PCB assembly.
With these ports controllers can communicate with other series 3
controller like performance controller/Load Sharing Controller &
also with Host Computer/DCS/PLC.
Port 1 & 2 are reserved for communication with other series 3
controller
Port 3 & 4 are used for communication with other control
systems using the Modicon Modbus communication protocol.On
these ports controller can be monitored or even controlled.
Series 3 Anti surge controller can be operated by DCS in much
the same fashion as an operator would control it from the front
panel.
The controller can be Switched between its manual & Automatics
modes from DCS by forcing the Automatic Coils. When Operating
in Manual ,The controller output signal can be set either from
front panel or from DCS by changing register value.
21/44
22/44
Series 3 Controllers
DIGITAL DISPLAY : Front panel has three digital displays
DEV(Deviation)
DEV : Display how far the compressor operation is deviating from
the minimum acceptable margin of safety. The controller acts to
maintain deviation at values equal or greater than Zero.
STATUS : run = Normal Operation, stp : Stop or Shutdown ,prg =
Purge
Purge mode will close the recycle valve, Allowing Purge gases to
pass through compressor.
OUT : Indicate the intended output of the controller to the anti
surge valve. Operator can observe valve position by pressing Alter
Display Key.
Indicator Lights: As Shown in the diagram except computer inhibit
lamp which if yellow ,host communication have been inhibited, If
lamp is off host communication are fully enabled.
23/44
Series 3 Controllers
CONTROL KEYS : There are seven active control keys on the front
panel.
24/44
Label
Color
Meaning
What Can I do
Auto
Green
Manual
Yellow
Remote
Green
Local
Yellow
Limit
Yellow
Tracking
Green
25/44
Label
Color
Meaning
What Can I do
TranFail
Red
Fallback
Yellow
ComErr
Red
Fault
Red
26/44
Series 3 Controllers
Configuration Procedure : Catalog is to be referred.
Modes & Fall Back Strategies : Series 3 Anti surge controller offers
a wide variety of modes which allow you to tailor its surge
control algorithms to specific applications & no. of input s,
location of inputs like flow measurement at suction or
discharge, temp. measurement, pressure measurement, diff.
pressure measurement.
In most applications , the more complicated algorithms will
provide energy savings as they tune controller more
aggressively.But because they require additional input signals,
so more complicated algorithms are also more likely to succumb
to transmitter failures.
In many such cases it is feasible to provide continued
surge protection by substituting an approximate constant value
for the missing input. A fallback strategy defined will trigger the
algorithms upon transmitter alarm condition.
27/44
Series 3 Controllers
Fallback stretegies
Over 75%
31
Fallback stretegies
Assumed speed
Assumed vane angle
Assumed adjacent stage flow rate
Temperature based polytropic head
A second anti surge controller as on line
back up
33/44
Service
Stages
Flow 1st stg
Flow 2nd stg
Driver
Driver power
Input
Output
Speed
Vendor
OUTPUTS
FY-002 - signal 4-20mA for RECYCLE VALVE (FV-002)
UA-011 controller fault / output failure alarm to
annunciation panel
35/44
37/44
SURGE TEST
38/44
of the fluid
under different rpms
39/44
40/44
PARAMETERS MONITORED
Suction Flow
Suction Pressure
Suction Temperature
Discharge Pressure
Discharge Temperature
41/44
Pressure:
Hp
Rc
Pd
Pc
SOL
SLL
RTL
New SCL
After SO
SCL
Operating Point
Rt
b1
b2
42/44
1.
Surge
test
Steps
Reduce the flow somewhat through the compressor with anti surge valve
closed
2. Hold the compressor at minimum performance level minimum speed
3. Put the anti surge controller in manual and open the recycle valve 100%
4. If possible, isolate the compressor with a discharge block valve
5. Disable derivative response - opening of recycle valve will be constant on
Recycle Trip and no shifting of Surge Control Line
6. Disable fall back strategy
7. Put b1 =0 , now SCL will be on the top of SLL
8. Put b2 =40, to ensure large Margin of Safety on Safety On response
9. Put RT=5 & SO= 10 to put RTL & SOL just to the left of SCL /SLL
10. Put C1=30 & C2= 0.4 to open recycle valve 30% for 0.4 sec
11. Put TL =200 recycle valve closure time for 63% closing
12. Put PI tuning constants to average conservative values
13. Put K= .999 this moves SCL & SLL to right as far as possible
14. Put controller in auto. DEViation will be +ve, valve will close, DEV will be 0
15. Reduce K by 0.01, DEV again will be +ve, valve will close and DEV will be 0
16. Repeat step 15 till K value will correspond to actual SLL location, then drop in
DEV will result in RT (crossing of RT & SOL line), valve will open , RT line will
shift 40% -- this is the point surge has occurred
17. Put the controller in manual , open the valve 100%, note the value of 43/44
K
?
Thank you
44/44