Sei sulla pagina 1di 87

Transformer

Professor Mohamed A. ElSharkawi

Why do we need transformers?


Increase voltage of generators output
Transmit high power at low current
Reduce cost of transmission system

Adjust voltage to a usable level


Create electrical isolation
Match load impedance
Filters
El-Sharkawi@Univers

220kV-750kV
Distribution
Transformer

15 kV- 25kV

Service
Transformer

Transmission
Transformer
208V- 416V

El-Sharkawi@Univers

Transmission Transformer

El-Sharkawi@Univers

Distribution Transformer

El-Sharkawi@Univers

Distribution Transformer

El-Sharkawi@Univers

Service Transformer

El-Sharkawi@Univers

Service Transformer bank

El-Sharkawi@Univers

Service Transformer bank

El-Sharkawi@Univers

Service Transformer

El-Sharkawi@Univers

10

Service Transformer

El-Sharkawi@Univers

11

Service Transformer

El-Sharkawi@Univers

12

Service Transformer

El-Sharkawi@Univers

13

Service Transformer

El-Sharkawi@Univers

14

Low power Transformer

El-Sharkawi@Univers

15

Basic Components
Iron Core

El-Sharkawi@Univers

Insulated Copper Wire

16

Basic Components
Laminated
iron core

Insulated
copper wire

El-Sharkawi@Univers

17

El-Sharkawi@Univers

18

El-Sharkawi@Univers

19

El-Sharkawi@Univers

20

d
e1 N1
dt
1

e1 dt

N1

d
e2 N 2
dt

i1

e1

i2
N1

N2

Primary

e2

Secondary
El-Sharkawi@Univers

21

Basic Analysis:Voltage
d
N1
e1 t
N1
dt

e2 t N d N 2
2
dt

E1 N1

E2 N 2

i1

e1

+
_

N1

N2

i2
+
_

e2

E1 E2

N1 N 2

Volts/turn is constant
Voltages are in phase (no phase shift)
Voltage magnitudes vary with turns ratio.
El-Sharkawi@Univers

22

Basic Analysis: Power and


current
i1

S1 S 2

EI E I
*
1 1

*
1
*
2

*
2 2

I
E2 N 2

I
E1 N1

e1

+
_

I1 N 2

I 2 N1

N1

N2

i2
+
_

e2

N1 I 1 N 2 I 2

Currents are in phase.


Current ratio is opposite to the voltage ratio
El-Sharkawi@Univers

23

Basic Analysis: Reflected


impedance
Flux
I2

I1

Load

Source

E1

N1

N2

E2

Zload

Secondary

Primary

Z load
El-Sharkawi@Univers

E2

I 2 24

Basic Analysis: Reflected


impedance
I1
Source

E1
Primary

'
load

'
load

E1

I1

Z
E1 I 2 N1


Z load E2 I1 N 2
'
load

'
load

N1

Z load
N2

El-Sharkawi@Univers

25

Single-Phase, Ideal Transformer


Ratings

I1

Apparent Power
2 KVA, 120/240 V
Primary Voltage

+
V1
-

N1

I2

N2

+
V2
-

Secondary Voltage
El-Sharkawi@Univers

26

Rated Values
Rated voltage: The device can continuously
operate at the rated voltage without being
damaged due to insulation failure
Rated current: The device can
continuously operate at the rated current
without being damaged due to thermal
destruction
El-Sharkawi@Univers

27

Example I1
Transformer rating:
2 KVA, 240/120 V
Compute the currents

S V1 I1 V2 I 2 2 KVA

+
V1
-

N1

I2
N2

+
V2
-

2 KVA
I2

16.67 A
V2 120 V

2 KVA
I1

8.33 A
V1 240 V
El-Sharkawi@Univers

28

Multi-Secondary Transformer

El-Sharkawi@Univers

29

Multi-secondary windings

El-Sharkawi@Univers

30

I3
N3

I1
E1

E3
I2

N1
N2

E2

Primary

E1 N1

E2 N 2

El-Sharkawi@Univers

E1 N1

E3 N 3

31

Current ratio: superposition

I12

I12
E1

N2
I2
N1

I2

N1
N2

E2

Primary

El-Sharkawi@Univers

32

Current ratio: superposition

I3
N3

I13
E1

N1

E3

N3
I13 I 3
N1

Primary

El-Sharkawi@Univers

33

I3

E1

E3

N3

I1

Superposition

I2

N1

E2

N2
Primary

I1 I12

N3
N2
I13 I 2
I3
N1
N1

I 1 N1 I 2 N 2 I 3 N 3
El-Sharkawi@Univers

34

I3
N3

I1
E1

Superposition

E3
I2

N1
N2

E2

Primary

S1 S 3 S 3
EI E I EI
*
1 1

*
2 2

El-Sharkawi@Univers

*
3 3

35

Example

The transformer consists of one primary winding and two secondary


windings. The number of turns is each winding is

N1 4000; N 2 1000; N 3 500

A voltage source of 120V is applied to the primary winding, and


purely resistive loads are connected across the secondary windings. A
wattmeter placed in the primary circuit measures 300W. Another
wattmeter placed in the secondary winding N2 measures 90W.
Compute the following:

The voltages of the secondary windings


The currents in N3
The power consumed by the load connected across N3

El-Sharkawi@Univers

36

Solution
N2
1000
E 2 E1
120
30
N1
4000
N3
500
E3 E1
120
15
N1
4000

P1
300
I1

2.5
E1 cos1 120

P2
90
I2

3
E 2 cos 2 30

El-Sharkawi@Univers

37

Solution
I 1 N1 I 2 N 2 I 3 N 3
2.5 * 4000 1000 * 3 500 I 3

I 3 14
E1 I 1 E 2 I 2 E3 I 3
120 * 2.5 30 * 3 15 I 3

I 3 14
El-Sharkawi@Univers

38

Solution
P1 P2 P3
300 90 P3

P3 210
El-Sharkawi@Univers

39

Autotransformer

El-Sharkawi@Univers

40

I1

V1

A1
E1

I2

B1
N1

E2

N2

V2

A2
B2

El-Sharkawi@Univers

41

Autotransformer: Voltage and current


Is

I load I1 I 2

A1

N1

I1

E1

V1 E1 E2

Iload

A2

V1

B1

E2

N2

I2

V2

B2

El-Sharkawi@Univers

42

I1
+
E1
-

N1

I2
N2

Autotransformer
+
E2

Is

E1

I1
Iload

A2

V1

S A E1 I1 E2 I 2

N1

A1

E2

N2

B1

I2

V2

B2

S B V1 I s V2 I load
El-Sharkawi@Univers

43

Autotransformer: Power
S B V1 I s ( E1 E2 ) I1 E1 I1 E2 I1
S B S A E 2 I1

SB S A
El-Sharkawi@Univers

44

Example
Ratings of regular transformer: 10 kVA, 400/200 V
New voltage ratio: 600/200 V
Is
Compute the new ratings
A
N1

Solution
10
I2
50 A
0.2
10
I1
25 A
0.4

E1

E2

El-Sharkawi@Univers

I1
Iload

A2

V1

S B V1 I1 600 25 15 kVA

N2

B1

I2

V2

B2

45

VARIC: Variable Auto-Transformer


Z

Is

N3
Y

V1

N1

N2

Sliding
terminal

I1

Iload
I2

V2

El-Sharkawi@Univers

46

Output Voltage
Vload

N2
Vs
N1 N 2

Z
Is

N3
Y

At Y

Vload

Sliding
terminal

I1
N1

N1 N 2
Vs
Vs
N1 N 2

Iload

V1
N2

I2

V2

At Z

Vload

N1 N 2 N 3
Vs
N1 N 2
El-Sharkawi@Univers

47

Three-Phase Transformer

El-Sharkawi@Univers

48

3-phase transformer

El-Sharkawi@Univers

49

N1

N2

Van
N1

VAN
N2

b C
Vac

VAC

Ratio of Line Voltage

Ratio of Phase Voltage

3-phase transformer Y-Y connection.


Also known as star-star connection

3 Van
N1

N2
3 VAN

El-Sharkawi@Univers

50

Ratio of Phase Voltage and line voltage

3-phase transformer ( - )
A

N2

N1

Vac
N1

VAC
N2
El-Sharkawi@Univers

51

3-phase transformer (Y- )


Also known as star-delta connection
N1
n

Van
N1

VAC
N2

N2

Vac
3 Van

VAC
VAC
El-Sharkawi@Univers

Ratio of Line Voltage

Ratio of Phase Voltage

3 N1
N2
52

3-phase transformer bank (Y- )


a

V AB
N2

Van
N1

Vab

Van

N1

N2

VAB

V AB
V AB

Vab
3 Van

N2
3 N1

N1

N2

c
N1
El-Sharkawi@Univers

N2
53

El-Sharkawi@Univers

54

Ratings of Ideal 3-phase


Transformer
Apparent Power (3-phase)
100 MVA, 13.8/138 KV
Primary Voltage
line-to-line

Secondary Voltage
line-to-line

El-Sharkawi@Univers

55

Example
Three single-phase transformers are used to form a threephase transformer bank. Each single-phase transformer is
rated at 10 kVA, 13.8 KV/240 V. One side of the
transformer bank is connected to a three-phase, 13.8 kV
transmission line. The other side of the transformer is
connected to a three-phase residential load of 415.7V,
9kVA at 0.8 power factor lagging. Determine the
connection of the transformer bank, the voltage ratio of the
transformer bank, and the line current of the bank at the
13.8 kV side
El-Sharkawi@Univers

56

Solution
Secondary voltage (Low voltage side) should be in
Y to provide the needed residential voltage
415.7
240 V
3
The high voltage side must be Delta-connection
The line-to-line voltage of the supply is 13.8 kV. Same
as the transformer rating of the primary.
If the primary is connected in Y, the voltage of the load
would be lower than 240 V.

El-Sharkawi@Univers

57

Solution

Van= 240 V

VAB= 13.8 kV

N1

N2

Van

a
Vab

b
N1

N2

El-Sharkawi@Univers

58

VAB
VAB

Vab
3 Van

Solution
13,800
3 240

Phase current of the load

I2

9000
3
240

Van= 240 V

VAB= 13.8 kV

N1

Van V
ab

B
N1

12.5 A

N2

N2

Phase current of the Transformer primary

N2
240
I1 I 2
12.5
0.2174 A
N1
13,800

Line Current in primary

El-Sharkawi@Univers

I A 3 I1 0.377 A
59

Actual Transformer
Windings:

i2

i1

Resistance
Inductance

e1

+
_

N1

N2

+
_

e2

Core:
Eddy Current
Hysteresis

El-Sharkawi@Univers

60

Windings Impedance
R1

X1

N1

R2

X2

N2

Ideal Transformer
El-Sharkawi@Univers

61

Core Hysteresis
i

+
e
_

N
H

B f

e dt

H f i

El-Sharkawi@Univers

62

El-Sharkawi@Univers

63

Core Model
Let
e Emax sin t

Emax
e dt cos t

e Emax
i
sin t
R
R
El-Sharkawi@Univers

R
e

64

Core Model
Let

e Emax sin t
Emax
e dt cos t

di
eL
dt
Emax
1
i e dt
cos t
L
L
El-Sharkawi@Univers

Xl
e

65

i
e

Xl

El-Sharkawi@Univers

66

Equivalent Circuit
'
2

N1 N2

R2

Io

I1
Ro

Xo

E1
N1 V1

E2
N 2 V2

E1

E2

X2

I2

V2

'
I2

N2
I1

I2
N1
I2

El-Sharkawi@Univers

67

load

R1

V1

X1

Referred impedance

V1

X1

R1

'
2

N1 N2

R2

Io

I1
Ro

Xo

E1

E2

X2

I2

V2

N1
N1

E1
E2
I 2 R2 jX 2 V2
N2
N2
El-Sharkawi@Univers

68

Referred impedance

V1

X1

R1

'
2

N1 N2

R2

Io

I1
Ro

Xo

E1

E2

X2

I2

V2

N1
N 1 ' N1
R2 jX 2 V2
E1
E2
I2
N2
N2
N2

El-Sharkawi@Univers

69


N1
N 1 ' N1
R2 jX 2 V2
E1
E2
I2
N2
N2
N2

Define:
R'2
X '2
V2'

N1

N2

N1

N2

N1

V2
N2

N1

E1 I
N2
'
2

N1
R2 jX 2 V2
N2

R2
X2

Then:

E1 I 2' R2' jX 2' V2'


El-Sharkawi@Univers

70

Equivalent Circuit Referred to


Source Side

X1

R1

Ro

N1 N2
E1

R2

Xo

R'2

Io

I1
Ro

Xo

E1

El-Sharkawi@Univers

X2

I2

E2

X1

R1

V1

'
2

Io

I1

V1

E1 I 2' R2' jX 2' V2'

I 2'

V2
X '2

V2'
71

Practical
Considerations
'

X1

R1

V1

R2

Io

I1
Ro

'
R1 Ro R2
'
X 1 X o X 2

Xo

E1

'
2

I1

V2'

'
I2 Io

'
I 2 I o

El-Sharkawi@Univers

X '2

I1
72

X1

R1

V1

Io

I1
Ro
R1

V1

X '2

R'2

'
2

V2'

Xo

X1

R'2

I1

X '2

I 2'
Io

Ro

El-Sharkawi@Univers

Xo

V2'

73

R1

V1

Define:

X1

R'2

X '2

I 1 I '2

V2'

'
Req R1 R2
'
X eq X 1 X 2
El-Sharkawi@Univers

74

Analysis of Transformer
X eq

Req

'
I1 I 2

V1

'
V1 V2

'
I2

V2'

Req jX eq

El-Sharkawi@Univers

75

V2
N1
V
V2
N2
'
2

Terminologies
Load Voltage
Load Voltage referred to Source side
Impedance referred to Source side
Load Current

I2

Load current referred to Source side

N2
I
I2
N1
'
2

El-Sharkawi@Univers

N1

R
N2

'
2

N1

X
N2
'
2

R2
2

X2
76

Analysis of Transformer
X eq

Req

'
I1 I 2

V1

'
V1 V2

'
I2

V2'

Req jX eq

El-Sharkawi@Univers

77

Req

'
I1 I 2

V1

'
I2

X eq

V2'

X eq
'
I2

'
I2

Req
El-Sharkawi@Univers

78

Req

V1

X eq

'
I1 I 2

V2'

V1 V2' I 2' Req j I 2' X eq

V1
I '2 Z eq

V2'

I '2 X eq

I '2 Req

'
I2
El-Sharkawi@Univers

79

Ratings of Actual 3phase Transformer


Apparent Power (3-phase)
100 MVA, 13.8/138 KV
'
2

V2

line-to-line

line-to-line

El-Sharkawi@Univers

80

Example
A transformer has the following parameters:

N1
10
N2
Req R1 R2' 1;

Z l 0.530
o

X eq X 1 X 2' 10; Ro 1000;

X 0 5000

The rated voltage of the primary winding is 1000V.


Compute the load voltage.

El-Sharkawi@Univers

81

Solution

N1

Z Z L
N2
'
L

'
I1 I 2

50

X eq

Req

V1

V2'

0
V
1000

0
o
1
I 2'

17
.
7

38
.
31
A
'
o
Req j X eq Z L 1 j 10 50 30

V I Z 17.7 38.31
'
2

'
2

'
L

50 30 885 8.31
o

N2
1
V2 V
885 88.5 V
N1
10
'
2

El-Sharkawi@Univers

82

Voltage Regulation VR

V1

'
I1 I 2

Vno load V full load


VR
V full load
Measured at the load side

V2'

Load

X eq

Req

V1 V2'
VR
'
V2

El-Sharkawi@Univers

83

Example
Calculate the voltage regulation of the transformer in the
previous problem.

Solution:

VR

'
V1 V2
'
V2

7209.5 7200
VR
100 0.14 %
7200
El-Sharkawi@Univers

84

Efficiency

Xeq

Req

V1

Io

I1
Ro

Output Power Pout


Input Power
Pin

Pin Pout Losses


Plosses Pcu Piron

Xo

Pcu

'
2

' 2
I2

V2'

Req

V12
Piron
Ro

Pout V2' I '2 cos

El-Sharkawi@Univers

85

Example
A 10 kVA, 2300/230 V, single phase distribution transformer
has the following parameters:

R1 5.8 ; X 1 X '2 12 ; R'2 6.05


Ro 75.6 k ; X o 69.4 k
At full load and 0.8 power factor lagging, compute the efficiency
of the transformer.

El-Sharkawi@Univers

86

Solution
Pout V2' I '2 cos S cos 10 0.8 8 kW

Pcu

S
10 ,000
'
I2

4.35 A
'
2300
V2

' 2
I2

Piron

Req ( 4.35 )2 5.8 6.05 224.23 W

V
V
2300

70 W
Ro
Ro
75,600
2
1

' 2
2

Pout
8000

100 96.45 %
Pin
8000 224.23 70
El-Sharkawi@Univers

87

Potrebbero piacerti anche