Sei sulla pagina 1di 13

3 PHASE STAR DELTA STAR AND POWER

MEASURMENT REPRESENTATION

ANKIT GAMIT
ID.NO:13BEEEG120

Introduction
Power may be defined as the rate at which energy is transformed oe
made available
In almost all cases the power in a d.c. circuit is best measured by
separately measuring quantities, V and I and by computing P=VI
In case of a.c. circuits the instantaneous power varies continuously
as the current and voltage go through a cycle of values
The fact that the power factor is involved in the expression for the
power means that a wattmeter must be used instead of merely an
ammeter and voltmeter.

Wattmeter
A wattmeter is essentially an inherent combination of an ammeter
and a voltmeter and, therefore , consists of two coils known as
current coil and pressure coil.
Wattmeter connection:

Wattmeter Errors

Error due to inductance of pressure coil


True power

cos
Re ading of wattmeter
cos cos

Error due to pressure coil capacitance


sin
sin cot

Error due to Eddy currents : soild metal parts are removed as far away from
the current coil as possible

Error due to power loss in pressure coil or current coil


There are two method of connecting wattmeters in the circuit for
measurement of power, as shown in figure below (a) and (b).
Fig (a) :
Wattmeter reading W I r

Fig (b) :

Wattmeter reading W

V2
R rp

Measurement of Power in Single Phase A.C. Circuit

3-voltmeter method
P

V32 V12 V22


2R

V32 V12 V22


cos
2V1V2

Disadvantages : (i) Even small errors in measurement of voltages may


cause serious errors in the value of power, (ii) Supply voltage higher than
normal voltage is required

3-Ammeter method

R
P I 32 I 12 I 22
2

cos

I 32 I 12 I 22
2I 1 I 2

The disadvantages of measurement of power by 3 voltmeters are overcome


in this method

Measurement of power in conjuction with instrument


transformers
This method is used when the currents and voltages of the circuits
to be measured are high
Figure below shows a measurement of power with wattmeter in
conjunction with instrument transformers in single phase A.C.
circuits

Vector diagram for inductive load


cos
cos cos

Vector diagram for capasitive load


cos
cos cos

Measurement of Power in 3-Phase Circuit

Measurement of power in 3phase, 4-wire circuits-----------

P=W1+W2+W3

Measurement of power in 3phase, 3-wire circuits-------------

P=W1+W2+W3

3-wattmeter method of measuring


3-phase power of delta connected
P=W1+W2+W3

1-wattmeter method of measuring


balanced 3-phase power (a) star
connected, (b) delta connected
P=3W

2-wattmeter method of measuring


3-phase 3-wire power :
(a) star connected,
P=W1+W2

(b) delta connected


P=W1+W2

Determination of P.F. from Wattmeter Reading

If load is balanced, then p.f. of the


load can be determined from the
wattmeter readings
Vector diagram for balanced star
connected inductive load -----
cos cos tan 1

3 W1 W2
W1 W2

The watt-ratio Curve ----------

p.f. can be determined from


reading of two wattmeters