Clinica de Aire Acondicionado

Trane
Psicrometria
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Psicrometria
Parte 1
La carta Psicrometrica
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Carta
Psicrometrica
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Propiedades del aire
Temp Bulbo Seco (Dry-bulb temperature)
Temp Bulbo Humedo (Wet-bulb temperature)
Temp punto de rocio (Dew-point temp)
Humedad Relativa (Relative humidity)
Humedad Absoluta (Humidity ratio)
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Termometro de Bulbo Seco
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Termometro Bulbo Humedo
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
La condensacion ocurre en el
punto de rocio
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
La niebla ocurre cuando el aire esta
saturado
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Humedad Relativa
Relative
Humidity
Cantidad de humedad que una
cantidad de aire contiene
=
Cantidad de humedad que una
cantidad de aire puede cargar
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
50% 100%
(saturado)
Humedad Relativa
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Radio de Humedad (Humedad
Absoluta)
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Propiedades del aire
Temp Bulbo Seco (Dry-bulb temperature)
Temp Bulbo Humedo (Wet-bulb temperature)
Temp punto de rocio (Dew-point temp)
Humedad Relativa (Relative humidity)
Humedad Absoluta (Humidity ratio)
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Condiciones de Verano
95F DB (Bs)
78F WB (Bh)
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Punto de interseccion
95F
78F
72F
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
25F
30F
35F
40F
45F
50F
55F
19.14
24.19
29.94
36.51
44.34
53.63
64.63
60F
65F
70F
75F
80F
85F
90F
77.61
92.89
110.82
131.83
156.38
185.03
218.42
Temp Bulbo
Seco.
Radio
Humedad
Propiedades del Aire Saturado
Temp Bulbo
Seco.
Radio
Humedad
0
30
Temperatura Bulbo Seco (F)
R
a
d
i
o

H
u
m
e
d
a
d


(
g
r
a
n
o
s
/
l
b
s

a
i
r
e

s
e
c
o
)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110
20
40
60
80
100
120
140
160
180
200
220
Localizacion puntos de saturacion
218.42
185.03
156.38
131.83
110.82
92.89
77.61
64.63
53.63
44.34
36.51
29.94
24.19
19.14
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Curva de saturacion
100% Humedad Relativa
30
Temperatura Bulbo Seco (F)

R
a
d
i
o

d
e

H
u
m
e
d
a
d

(
g
r
a
n
o
s
/
l
b

d
e

a
i
r
e

s
e
c
o
)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110
20
40
60
80
100
120
140
160
180
200
220
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Bulbo Seco, Bulbo Humedo, Punto
de Rocio
60F
Bulbo Humedo
60F
Bulbo Humedo
A B C D
Bulbo Seco 60F 62F 75F 90F
Bulbo Humedo 60F 60.8F 65.2F 70F
Punto Rocio 60F 60F 60F 60F
Humedad Rel 100% 92% 60% 37%
D C B
A
30
Temperatura de Bulbo Seco (F)
R
a
d
i
o

d
e

H
u
m
e
d
a
d


(
g
r
a
n
o
s
/
l
b
s

d
e

a
i
r
e

s
e
c
o
)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110
20
40
60
80
100
120
140
160
180
200
220
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Adicionando Calor sensible
100% Saturacion
30
Temperatura Bulbo Seco (F)
R
a
d
i
o

d
e

H
u
m
e
d
a
d

(
g
r
a
n
o
s
/
l
b

d
e

a
i
r
e

s
e
c
o
)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110
20
40
60
80
100
120
140
160
180
200
220
60F
Punto Rocio
60F
Bulbo Seco
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Curvas de Humedad Relativa
Humedad Relativa
0%
30
Temperatura de Bulbo seco (F)
R
a
d
i
o

d
e

H
u
m
e
d
a
d


(
g
r
a
n
o
s
/
l
b

d
e

a
i
r
e

s
e
c
o
)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110
20
40
60
80
100
120
140
160
180
200
220
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Propiedades del aire
Humedad Absoluta
Bulbo Seco
Humedad Relativa
30
Temperatura de Bulbo Seco (F)
H
u
m
e
d
a
d

A
b
s
o
l
u
t
a

(
g
r
a
n
o
s
/
l
b

d
e

a
i
r
e

S
e
c
o
)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110
20
40
60
80
100
120
140
160
180
200
220
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Determinando las lineas de bulbo
humedo
A
B
I

C
I

D
I

B C D
A
I

30
Temperatura de Bulbo (F)

H
u
m
e
d
a
d

A
b
s
o
l
u
t
a

(
g
r
a
n
o
s
/
l
b

d
e

a
i
r
e

s
e
c
o
)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110
20
40
60
80
100
120
140
160
180
200
220
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Propiedades del aire
Bulbo
Humedo
Punto Rocio
30
Temperatura de Bulbo Seco (F)
H
u
m
e
d
a
d

A
b
s
o
l
u
t
a

(
g
r
a
n
o
s
/
l
b

d
e

a
i
r
e

s
e
c
o
)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110
20
40
60
80
100
120
140
160
180
200
220
Humedad Absoluta
Bulbo
Seco
Humedad Relativa
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Volumen especifico
Linea Volumen especifico
(pies3 / libras de aire seco)
30
Temperatura bulbo seco (F)
H
u
m
e
d
a
d

A
b
s
o
l
u
t
a

(
g
r
a
n
o
s
/
l
b

d
e

a
i
r
e

s
e
c
o
)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110
20
40
60
80
100
120
140
160
180
200
220
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Aadiendo calor sensible
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Removiendo calor sensible
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Aadiendo humedad
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Removiendo Humedad
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Removiendo Calor sensible y humedad
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
A
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Removiendo Calor sensible y humedad
Psicrometria
Parte 2
Mezcla de Aires
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Ventilador
Suministro
Mezcla
Aire Exterior
(AE)
Aire de Retorno (AR)
A
C
B
Serpentin de
Enfriamiento
Determinando las condiciones
80F
95F
Determinando condiciones de
entrada
B
A
Aire Exterior
Aire de retorno
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
1,000 cfm
4,000 cfm
= 0.25
AE
RA
mezcla
=
=
=
25%
75%
100%
A
C
B
4,000 cfm
Aire Mezclado
1,000 cfm
AE
3,000 cfm
RA
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Determinando condiciones de
entrada
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
95F 0.25 = 23.75F
80F 0.75 = 60.00F
mezcla = 83.75F
Determinando condiciones de
entrada
83.75F
70F
B
80F
95F
C
A
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Determinando condiciones de
entrada
Psicrometria
Parte 3
factor de calor sensible
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Efecto de remover calor sensible
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Efecto de remover calor latente
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Removiendo calor sensible y latente
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Aire de suministro
Calor Sensible
Calor Latente
Aire de
Retorno
Calor y transferencia de humedad
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Frio y Humedo
Caliente y seco
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Removiendo calor sensible y latente
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Ganancia de Calor
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
SHR
Ganancia de calor sensible

Ganancia Calor sensible + Ganancia calor latente
=
factor de calor sensible (SHR)
78F BS
65F BH
Punto de Referencia
Escala de factor de calor sensible
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Dibujando la linea SHR
A
Punto de Referencia
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
A
El SHR determina las condiciones
de suministro
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
C
D
B
80F
Dibujando una linea de SHR
Punto de Ref
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Psicrometria
Parte 4
Cantidad de aire
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Curvas de Serpentin
Curvas de serpentin
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
80,000 Btu/hr calor sensible
20,000 Btu/hr calor latente


Paso 1: Calcule el factor de calor sensible (SHR)
Determinando el caudal de
suministro
= 0.80
80,000 Btu/hr

100,000 Btu/hr
SHR =
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Cuarto 78F DB, 50% RH

Aire Exterior (OA) 95F DB, 78F BH

Ventilacion 25% AE
Determinando el caudal de
suministro
95F 0.25 = 23.75F
78F 0.75 = 58.50F
mixture = 82.25F
PASO 2: Ubique condiciones aire exterior y del cuarto
A
C
B
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Determinando el caudal de suministro
56.5F 78F
PASO 3: Identifique las condiciones de suministro
A
C
B
D
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Determinando el caudal de suministro
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Ganancia calor sensible

1.085 (Bs Cuarto Bs Suministro)
Caudal de
suministro
=
PASO 4: Resuelva la ecuacion para el aire de suministro
Determinando el caudal de suministro
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
80,000 Btu/hr

1.085 (78F 56.5F)
3,430 cfm =
Paso 4: Resuelva la ecuacion de suministro de aire
Calculando el aire de suministro
D
A
C
B
3,430 cfm
56.5F BS
55.2F BH

AR
AE
82.2F BS
68.6F BH
mixture
Calculando el aire de suministro
SA
56.5F
D
A
C
B
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
47,000 Btu/hr Ganancia de calor sensible
20,000 Btu/hr Ganancia de calor latente


= 0.70
47,000 Btu/hr

67,000 Btu/hr
SHR =
Usando arbitrariamente 55F Como
condicion de suministro
A
C
B
D
55F
D
I

A
I

49F
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Usando arbitrariamente 55F Como
condicion de suministro
Psicrometria
Parte 5
Toneladas de
Refrigeracion
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Que es entalpia?
Entalpia (h) = Calor Sensible + Calor Latente
Es la cantidad de energia en una libra de
aire (Btu/lb) a su condicion presente.
Calculando las toneladas de refrigeracion
Paso 1:
Encuentre las
Entalpias entrando y saliendo
del serpentin
A
B
C
D
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Paso 2: Resuelva la ecuacion de carga de refrigeracion
4.5 CFM suministro (h
1
h
2
)
Carga de
Refrigeracion
(Btu/hr)
=
h
1
= entalpia de aire entrando al serpentin (Btu/lb)
h
2
= entalpia a la salida del serpentin (Btu/lb)
Calculando las toneladas de refrigeracion
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
= 11.8 tons of refrigeration
4.5 3,430 cfm (32.7 23.5) = 142,000 Btu/hr
142,000 Btu/hr

12,000 Btu/hr/ton
Calculando las toneladas de refrigeracion
Paso 2: Resuelva la ecuacion de carga de refrigeracion
Cargas sensibles y latentes
A
B
C
D
Carga
Sensible
Carga
Latente
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
4.5 3,430 cfm (29.6 23.5) = 94,150 Btu/hr

7.8 Toneladas de refrigeracion (sensible)
Cargas sensibles y latentes del
serpentin
4.5 3,430 cfm (32.7 29.6) = 47,850 Btu/hr

4.0 toneladas de refrigeracion (latente)
Psicrometria
Parte 6
Analisis Psicrometrico
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
SHR at Full-Load Conditions
56.5F 78F
D
A
B
C
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
80,000 Btu/hr
80,000 Btu/hr + 20,000 Btu/hr
SHR Carga Total :
= 0.80
47,000 Btu/hr
47,000 Btu/hr + 20,000 Btu/hr
= 0.70
Cambios en el SHR con la carga del
cuarto
SHR Carga
parcial :
D
A
B
C
SHR con condiciones de carga parcial
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
D
A
B
C
A
I

D
I

47,000 Btu/hr

1.085 (78F Supply DB)
= 3,430 cfm
BS Suministro = 65.4F
65.4F
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
SHR con condiciones de carga parcial
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Temperatura variable y cantidad constante de aire
AE
AR
AS
B
D
C
A
Serpentin de
enfriamiento
modulante
Sistema de volumen constante
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Serpentin
Calefaccion
Serpentin
Enfriamiento
Termostato
del cuarto
Aadiendo calefaccion se
mejora el control de
humedad
B
E
D
C
A
Volumen constante con calefaccion
A
C
B
47,000 Btu/hr

1.085 (78F Supply DB)
= 3,430 cfm
BS Suministro = 65.4F
Efecto de Aadir calefaccion
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
D
E
65.4F
56.5F
D
E
65.4F
56.5F
Efecto de aadir calefaccion
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
A
C
B
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
El by-pass de mezcla de aire mejora el control de humedad
OA
RA
SA
B
D
C
A
Dampers
de mezcla
By-pass de mezcla de aire
Efecto del By-pass de mezcla de aire
D
A
C
B
E
82.25F 0.455 = 37.4F
51.40F 0.545 = 28.0F
mezcla = 65.4F
65.4F
51.4F
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
A
C
B
A
I

65.4F
51.4F
D
E
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Efecto del By-pass de mezcla de aire
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
AE
AR
AS
B
D
A
C
Cantidad variable de aire temperatura constante
Variador de
frecuencia
Sistema de volumen variable (VAV)
D
A
C
B
47,000 Btu/hr

1.085 (78F 56.5F)
= 2,015 cfm
A
I

55.5F
Caudal de suministro a cargas parciales
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Herramientas de software
Psicrometria
Parte 7
Repaso
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999 Traducido a espaol por Gabriel Jimenez lvarez
Propiedades del aire
Bulbo
Humedo
Punto Rocio
30
Temperatura de Bulbo Seco (F)
H
u
m
e
d
a
d

A
b
s
o
l
u
t
a

(
g
r
a
n
o
s
/
l
b

d
e

a
i
r
e

s
e
c
o
)

25 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110
20
40
60
80
100
120
140
160
180
200
220
Humedad Absoluta
Bulbo
Seco
Humedad Relativa
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
80F
95F
83.75F
70F
C
B
A
Determinando las condiciones de
la mezcla
95F 0.25 = 23.75F
80F 0.75 = 60.00F
mezcla = 83.75F
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
A
C
B
D
coil curve
Carga de calor sensible

1.085 (BS Cuarto BS Suministro)
Caudal de
suministro
Calculando condiciones de salida del
serpentin
=
supply DB
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
A
Calculando el factor de calor
sensible
SHR =
Calor Sensible
Calor sensible + Calor latente
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
A
C
B
D
Calculando toneladas de
refrigeracion
Carga de refrigeracion = 4.5 Caudal de suministro (h
1
h
2
)
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999
C
OA
RA
B
A
D
SA
Analisis
Psicrometrico
A
B
C
D
Air Conditioning Clinic TRG-TRC001-EN American Standard Inc. 1999