Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
int j
at all other generators,
i.e. j = nb + 1, nb + ng - 1. (Only two variables are associated
with each generator internal bus bar as the
three-phase voltages are balanced)
The three voltage magnitudes (V
i
p
) and angles (
i
p
) at
every generator terminal bus bar and every load bus bar
in the system, i.e. i = 1, nb and p = 1,3
The equations necessary to solve for the above set of
variables are derived from the specified operating
conditions,
The individual phase real and reactive power
loading at every system bus bar.
The voltage regulator specification for every
synchronous machine.
The total real power generation of each
synchronous machine, with the exception of slack
machine.
At slack machine, fixed voltage in phase and
magnitude, is applicable to the three-phase load
flow.
The mathematical statement of the specified
conditions in terms of Y matrix is as follows
1. For each of the three phases ( p ) at every load
and generator terminal bus bar (i),
2. For every generator j,
where k is the bus number of the j
th
generators
terminal bus bar.
3. For every generator j , with the exception of the
slack machine, i.e. j nb + ng,
the mutual terms G
jk
and B
jk
are nonzero only when
k is the terminal bus bar of the j
th
generator.
The mathematical formulation of 3 phase LF
problem is given by the above three set of
independent algebraic eqn in terms of system
variables.
Load Flow solution is the set of variables which
makes up on substitution the mismatches in the
eqn equal to zero.
The solution is obtained in an iterative manner
using the Fast Decoupled algorithm.
The problem is defined as
The effects of on reactive power flows and V
on real power flows are ignored, therefore
[ I ] = [M] = [J] = [ N ] = 0
and [C] = [GI = 0.
In addition, the voltage regulator specification is
assumed to be in terms of the terminal voltage
magnitudes only and therefore
[D] = [H] = 0.
The equation in decoupled form is
for i, k = 1, nb and j, I = 1, ng - 1 (i.e. excluding the
slack generator), l refers to generator internal bus bar
and
for i, k = 1, nb and j , I = 1, ng (i.e. including the slack
generator).
Jacobian elements are given as follows
Consider for a generator internal bus bar l
the sub matrix A &B is given by
Similarly E & F is given by
Where [F
jl
]=0 for all jl because the j
th
generator has no
connection with the l
th
generators internal bus bar
Sub matrix K,P,L&R is given by
[L
m
jk
]=0, when k is not the terminal bus bar of j
th
generator
[R
jl
]=0 for all j, l as the voltage regulator
specification does not include the variables V
int
Jacobian approximations
1. At all nodes (all phases of all bus bars)
2. Between connected nodes of same phase,
3. The phase angle unbalance at any busbar will be
small
4. The angle between different phases of connected
bus bars will be 120
o
i.e.
Applying approximation to the jacobians we get the
eqns as
where
All the terms in matrix [M] are constant and is
same as [B] matrix except for the off diagonal
terms which connects nodes of different phases.
The reliability and speed of convergence can be
improved with some modification in the defining
function.
1. The left-hand side defining functions are
redefined as [P
p
i
/ V
p
i
] , [P
gen j
/V
int j
] and
[Q
p
i
/ V
p
i
]
2. In equation (1), the remaining right-hand-side V
terms are set to 1 p.u.
3. In equation(2), the remaining right-hand-side V
terms are cancelled by the corresponding terms
in the right-hand-side vector.
There fore the eqn becomes,
As V
reg
is normally a simple linear function of
the terminal voltages, [L] will be a constant
matrix
Therefore, the Jacobian matrices [B] and [ B ] in
equations have been approximated to constants.
The final algorithmic eqn may be written as
The eqns are now solved iteratively using the
algorithms
Starting values for the iterations are assigned as
1. The non voltage-controlled bus bars are assigned 1
p.u. on all phases.
2. At generator terminal bus bars all voltages are
assigned values according to the voltage regulator
specifications.
3. All system bus bar angles are assigned 0, - 120
0
, +
120
0
for the three phases respectively.
4. The generator internal voltages and angles are
calculated from the specified real power.
5. For the slack machine the real power is estimated as
the difference between total load and total
generation plus a small percentage (say 8%) of the
total load to allow for losses
Form the system admittance model from the raw data
for each system component.
Constant Jacobians B' and B" are formed from the
system admittance matrix.
Each equation are then solved using the iterative
technique.
The iterative solution process yields the values of the
system voltages which satisfy the specified system
conditions of load, generation and system
configuration.
The three-phase bus bar voltages, the line power flows
and the total system losses are calculated.