Sei sulla pagina 1di 26

10 May 2014

VOTANO 100
OMICRON
Sophisticated voltage transformer testing
> Mobile and accurate voltage transformer testing
> Inductive and capacitive coupled
voltage transformers (VTs)
> Testing in power system grids, production
facilities, and test/development labs
> Protection and metering applications
> Determination of all important
transformer parameters:
> VT ratio accuracy
> VT phase angle accuracy
> VT winding resistance of secondary windings
> Class verification of VTs with
up to 5 secondary windings

Page 2 OMICRON
Your benefits
> Mobile: compact size and low weight
(< 15 kg / 33 lbs)
> Accurate: field calibration of VTs up to
the 0.1 accuracy class
> Fast: software-guided test procedure ensures
short testing time (< 20 min)
> Convenient: automatic result assessment as per
IEEE and IEC standards directly after the test
> Efficient: simulation and re-assessment
with changed VT parameters
> Safe: 4 kV maximum test voltage and
local isolation between high voltage and
measuring equipment

Page 3 OMICRON
VOTANO 100
Page 4 OMICRON
Generator
output
Measurement
input 1
Measurement
input 2
Grounding
terminal
Communication
interface to VBO1
PC connection
Compact Flash
card slot
Voltage booster VBO1
Page 5 OMICRON
Ratio tests
Winding resistance,
short-circuit impedance,
and excitation tests
Grounding
terminal
VOTANO 100
interface for
ratio test
VOTANO 100
interface for
all other tests
Communication
interface to
VOTANO 100
Emergency
stop button
Test procedure
Voltage transformer testing with VOTANO 100
Page 6 OMICRON
Step 1: measurement of parameters Step 2: modeling
Software-guided measurement of different
VT parameters such as winding resistance,
magnetization characteristics, etc.
Determination of VT model elements and
calculation of VT accuracy through
embedded mathematical functions
Test procedure
Voltage transformer testing with VOTANO 100
Page 7 OMICRON
Step 3: IEEE/IEC assessment Step 4: reporting
Automated comparison of test results with
the defined values in accordance with the
selected IEEE or IEC standard
All data can be saved in Excel and XML
format or can be printed as a test report.
Test procedure
Maximum safety during testing
> Supplied voltage booster VBO1: located in
high-voltage environment
> User and VOTANO 100: located in safe area
outside the high-voltage environment
> VBO1 provides 4 kV maximum test voltage
for ratio measurement
> Grounding and plausibility check
> Acoustic warnings
> Emergency stop button or
optional dead man switch
Page 8 OMICRON
Safe area
High-voltage
environment
VOTANO 100 VBO1
Test procedure
Test sequence
Page 9 OMICRON
VT or
CVT?
Specification of
voltage
transformer data
3. Secondary
short-circuit
impedance
measurement
2.
Winding
resistance
measurement
1.
Short-circuit
impedance
measurement
4.
Excitation
measurement
5.
VT ratio
measurement
4b.
CVT
inductive ratio
measurement
4a.
CVT ratio
measurement
* if more than two
secondary windings
are available
...
...
*
VT
CVT
VOTANO 100
Emergency
switch
Test procedure
1. Short-circuit impedance measurement
Page 10 OMICRON
VT CVT
VOTANO 100
Emergency
switch
VOTANO 100
Test procedure
2. Winding resistance measurement
Page 11 OMICRON
CVT / VT
Emergency switch
Test procedure
3. Secondary short-circuit impedance measurement
Page 12 OMICRON
VOTANO 100
CVT / VT
Emergency switch
Test procedure
4. Excitation measurement
Page 13 OMICRON
VOTANO 100
CVT / VT
Emergency switch
VOTANO 100
CVT
Emergency switch
Test procedure
4a. CVT ratio measurement
Page 14 OMICRON
VOTANO 100
CVT
Emergency switch
Test procedure
4b. CVT inductive ratio measurement
Page 15 OMICRON
VOTANO 100
Emergency
switch
VT CVT
VOTANO 100
Emergency
switch
Test procedure
5. VT ratio measurement
Page 16 OMICRON
Device operation
Operation via VOTANO 100 display
> Guided workflow with connection diagrams
> Ideal for use with intense solar irradiation

Operation via PC software
> Control whole measuring procedure
with your PC
> Guided software workflow
> Remote control allows integration into
automated procedures of production line
> Automated pass/fail assessment of results
> Export reports in Excel and XML format
> Firmware upgrade
Page 17 OMICRON
1
2
2
1
Result assessment
> Automated assessment as per IEEE and IEC standards
> Assessment is completed within seconds after measurement
> Complete class assessment considering;
> different burden values
> different primary voltage values
> other secondary windings under load and no-load conditions
> protection and metering class, simultaniously assessed per winding
> up to five windings in assessment matrix
> open delta winding

Page 18 OMICRON
Unloaded Burden in % cos Phi VA 2% 5% 80% 100% 120%
Ratio
Voltage ratio error in % at % of rated voltage, other winding unloaded
100 0.8 15 0.088% 0.123% 0.177% 0.177% 0.176%
25 0.8 3.75 0.033% 0.362% 0.415% 0.417% 0.415%
Phase angle
Phase angle error in min. at % of rated voltage, other winding unloaded
100 0.8 15 4.825 min. 4.287 min. 3.180 min. 3.186 min. 3.245 min.
25 0.8 3.75 2.802 min. 2.263 min. 1.155 min. 1.161 min. 1.220 min.
Loaded Burden in % cos Phi VA 2% 5% 80% 100% 120%
Ratio
Voltage ratio error in % at % of rated voltage, other winding loaded
100 0.8 15 -0.57% -0.54% -0.482% -0.481% -0.483%
25 0.8 3.75 -0.33% -0.30% -0.246% -0.245% -0.246%
Phase angle
Phase angle error in min. at % of rated voltage, other winding loaded
100 0.8 15 2.320 min. 1.783 min. 0.678 min. 0.683 min. 0.737 min.
25 0.8 3.75 0.302 min. -0.235 min. -1.340 min. -1.335 min. -1.300 min.
Result assessment
> Error parallelogram as per IEEE standard
Page 19 OMICRON
-20 -15 -10 -5 0 5 10 15 20
Phase angle in min.
RCF
1.004
1.003
1.002
1.001
1.000
0.999
0.998
0.997
0.996
5 % U
PR
25 % U
PR
90 % U
PR
100 % U
PR
110 % U
PR
ZZ
Z
Y
M
X
W
O
Supported standards
> IEC 60044-2 (inductive VTs)
> IEC 60044-5 (capacitive VTs)
> IEC 61869-3 (additional requirements for inductive VTs)
> IEC 61869-5 (additional requirements for capacitive VTs)
> IEEE C57.13 (standard requirements for conventional transformers)
> ANSI C93.1 (requirements for capacitive VTs)
Simulation and re-assessment of results
> Simulation and re-assessment of existing measurement data at any time
> No further on-site measurement necessary when the following
transformer parameters have changed:
> Burdens
> Nominal voltage factor
> Accuracy class
Page 21 OMICRON
Reporting
> Generate customizable reports
> Data can be exported in Excel and XML format

Page 22 OMICRON
Technical specifications
Page 23 OMICRON
Ratio measurement
Voltage ratio Voltage level Typical accuracy
1 ... 350 0.6kV ... 35kV 0.05%
> 350 ... 1100 > 35kV ... 110kV 0.07%
> 1100 ... 2450 > 110kV ... 245kV 0.07%
Test restrictions for
inductive voltage
transformers
> Combined instrument
transformers cannot be
tested with the mentioned
accuracy
Phase displacement measurement
Voltage ratio Voltage level Typical accuracy
1 ... 350 0.6kV ... 35kV 1 min
> 350 ... 1100 > 35kV ... 110kV 2 min
> 1100 ... 2450 > 110kV ... 245kV 2 min
Winding resistance measurement
Resolution Guaranteed accuracy Typical accuracy
1m 0.1% + 1m 0.05%
Inductive voltage transformers
Technical specifications
Page 24 OMICRON
Capacitive coupled voltage transformers
Ratio measurement
Voltage ratio Voltage level Typical accuracy
300 ... 8000 > 30kV ... 800kV 0.07%
Phase displacement measurement
Voltage ratio Voltage level Typical accuracy
300 ... 8000 > 30kV ... 800kV 2 min
Winding resistance measurement
Resolution Guaranteed accuracy Typical accuracy
1m 0.1% + 1m 0.05%
Test restrictions for
capacitive coupled
voltage transformers
> CVTs with integrated
damping unit which cannot
be accessed from outside
cannot be tested with the
mentioned accuracy.
> CVTs where the connection
of the NHF terminal to
ground cannot be opened
cannot be tested.
Ordering information and accessories
Ordering information
> VOTANO 100 Standard Package
(VE000800)
> VOTANO 100, VBO1, accessories
> Testing up to class 0.3
> VOTANO 100 Advanced Package
(VE000801)
> Content of Standard Package
> Increased accuracy: testing up
to class 0.1
> Simulation tool
> VOTANO 100 Capacitive VT
Upgrade Option (VESM0801)
> Standard to Advanced
Upgrade Option (VESM0802)

Page 25 OMICRON
Accessories






Dead man switch

Thanks for your attention.
> Please visit our website www.omicron.at