Sei sulla pagina 1di 24

DIAGNOSTICO ENERGTICO

AHORROS ILUMINACIN, AIRE ACONDICIONADO Y CONTROL DE LA DEMANDA BALANCE GENERAL

ILUMINACIN
DESCRIPCIN, RESULTADOS Y PROPUESTA DE AHORRO ENERGTICO

ILUMINACIN DE LA PLANTA
SITUACIN ACTUAL
ACTUALMENTE LA PLANTA CUENTA CON SISTEMAS T12 FLUORESCENTES DE 75 Y 39 WATTS, AS COMO ADITIVOS METLICOS DE 400 WATTS PARA LA ILUMINACIN DE LAS NAVES INDUSTRIALES, COMO SISTEMAS PRINCIPALES EN REAS GENERALES. ADEMS CUENTA CON SISTEMAS SUBURBANOS PARA EXTERIOR Y LMPARAS AHORRADORAS COMPACTAS PARA INTERIORES Y EXTERIORES AS COMO REFLECTORES, COMO SISTEMAS GENERALES SECUNDARIOS

DISTRIBUCIN DE LA DEMANDA EN ILUMINACIN (KW )


NAVE 1 NAVE 2 NAVE 3

DISTRIBUCIN DEL CONSUMO (KWH)


NAVE 1 NAVE 2 NAVE 3

15.1, 11% 33.0, 23% 8,301, 16%

3,817, 7%

94.3, 66%
40,151, 77%

RESULTADOS DE MEDICIONES
EDIFICIO DEMANDA CONSUMO KW KWH BASE KWH INTERM KWHPUNTA KWH TOTAL NAVE 1 13.63 9.50 5.69 58.12 1.62 2.34 3.42 94.3 490.08 511.17 318.96 8,294.86 102.06 133.38 187.27 10,038 1,143.53 1,192.74 744.24 19,354.68 238.14 311.22 436.97 23,422 326.72 340.78 212.64 5,529.91 68.04 88.92 124.85 6,692 1,960.33 2,044.70 1,275.84 33,179.44 408.24 533.52 749.09 40,151

BALANCE EN NAVES

COSTOS MENSUALES $ KW $ KWH $ TOTAL

COMEDOR REA DE CARGA Y ALMACEN OFICINAS EXTERIORES NAVE 1 INTERIOR NAVE 1 REAS DE FUGAS OFICINAS DE PRODUCCIN SUBESTACIN Y MANTENIMIENTO TOTAL INTERIOR NAVE 2 OFICINAS NAVE 2 SUBESTACIN

$1,766.79 $11.00 $736.83 $7,414.76 $209.97 $2.71 $27.09 $10,169.15

$2,270.26 $2,367.97 $1,477.55 $38,425.11 $472.78 $617.87 $867.52 $46,499.06

$4,642.61 $2,735.81 $2,546.54 $52,715.85 $785.16 $713.67 $1,028.80 $65,168.44

NAVE 2 26.4
0.6 0.7 3.8 1.6 33.0 5.2 8.0 1.3 0.6 15.1 142

1,663
36 24 238 114 2,075 329 505 79 41 954 13,067

3,881
83 57 556 266 4,842 NAVE 3 767 1,178 185 96 2,226 30,490

1,109
24 16 159 76 1,384 219 337 53 27 636 8,712

6,653
143 97 953 456 8,301 1,315 2,019 318 164 3,817 52,269

$
$ $ $ $

3,421.70
73.36 89.12 489.93 205.43

$
$ $ $ $

7,704.61
165.18 112.28 1,103.16 528.65

$12,795.26
$274.32 $231.61 $1,832.05 $844.19 $15,977.44 $2,529.97 $3,883.94 $610.68 $303.59 $7,328.19 $ 88,474.06

REA DE HERRAMENTALES Y PROTOTIPOS


EXTERIORES NAVE 2 TOTAL INTERIOR NAVE 3

$4,279.54 $ $ $ $ 676.56 1,038.64 163.31 73.88

$9,613.88 $ $ $ $ 1,523.41 2,338.70 367.72 190.11

SALAS DE PRUEBA E INGENIERAS


OFICINA Y FUNDICIN EXTERIORES NAVE 2 TOTAL TOTAL GENERAL

$1,952.39 $ 16,401.08

$4,419.94 $ 60,532.88

ILUMINACIN
RESULTADOS DEL LEVANTAMIENTO
DISTRIBUCIN DE LA DEMANDA DE ILUMINACIN NAVE 3 (KW)
1.3; 8% 0.6; 4% 5.2; 35%

DISTRIBUCIN DELCONSUMO DE ILUMINACIN NAVE 3 (KWH)


318; 8% 164; 4% 1,315; 35% 2,019; 53%

8.0; 53%

INTERIOR NAVE 3 OFICINA Y FUNDICIN

SALAS DE PRUEBA E INGENIERAS EXTERIORES NAVE 2

INTERIOR NAVE 3 OFICINA Y FUNDICIN

SALAS DE PRUEBA E INGENIERAS EXTERIORES NAVE 2

LOS RESULTADOS DE LOS CONSUMOS Y DEMANDAS DE LA NAVE 3, SON IGUALES EN PORCENTAJE PUESTO QUE ESTAS REAS TIENEN HORARIOS DE UTILIZACIN MUY SIMILARES.

ILUMINACIN
RESULTADO DEL LEVANTAMIENTO
DISTRIBUCIN DE LA DEMANDA DE ILUMINACIN NAVE 2 (KW)
1.6; 5% 0.7; 2% 0.6; 2% 97; 1% 3.8; 11% 143; 2% 953; 11%

DISTRIBUCIN DELCONSUMO DE ILUMINACIN NAVE 2 (KWH)


456; 6%

26.4; 80%

6,653; 80%

INTERIOR NAVE 2 OFICINAS NAVE 2 SUBESTACIN REA DE HERRAMENTALES Y PROTOTIPOS EXTERIORES NAVE 2

INTERIOR NAVE 2

OFICINAS NAVE 2
SUBESTACIN REA DE HERRAMENTALES Y PROTOTIPOS EXTERIORES NAVE 2

NO SE TOMO EN CUENTA QUE EN OCASIONES SE ENCONTR LA NAVE CON TODOS LOS ADITIVOS METLICOS ENCENDIDOS MUCHO TIEMPO DESPUS DE HABERSE RETIRADO EL PERSONAL. ESTO ORIGINA GASTOS INNECESARIOS EN EL HORARIO PUNTA QUE ES EL MAS CARO. LOS ADITIVOS METLICOS SON LOS SISTEMAS DE MAYOR CONSUMO CON 26 KW Y 6,653 KWH AL MES.

ILUMINACIN
RESULTADO DEL LEVANTAMIENTO
DISTRIBUCIN DE LA DEMANDA DE ILUMINACIN NAVE 1 (KW)
2.34; 2% 3.42; 4% 1.62; 2% 13.63; 14% 408.24; 1% 9.50; 10%

DISTRIBUCIN DELCONSUMO DE ILUMINACIN NAVE 1 (KWH)


749.09; 2% 533.52; 1% 1,960.33; 5% 2,044.70; 5% 1,275.84; 3%

58.12; 62%

5.69; 6% 33,179.44; 83%

COMEDOR REA DE CARGA Y ALMACEN EXTERIORES NAVE 1 REAS DE FUGAS SUBESTACIN Y MANTENIMIENTO

OFICINAS INTERIOR NAVE 1 OFICINAS DE PRODUCCIN

COMEDOR REA DE CARGA Y ALMACEN EXTERIORES NAVE 1 REAS DE FUGAS SUBESTACIN Y MANTENIMIENTO

OFICINAS INTERIOR NAVE 1 OFICINAS DE PRODUCCIN

LA NAVE 1 ES LA QUE TIENE LA MAYOR CARGA DE ILUMINACIN, CON 58.1 KW DE ADITIVOS METLICOS TRABAJANDO LAS 24 HORAS, LO QUE IMPLICA EL MAYOR CONSUMO DE ILUMINACIN DE LA PLANTA CON 33,179.4 KWH DE CONSUMO AL MES.

ILUMINACIN
PROPUESTA DE AHORRO ENERGTICO
LA PROPUESTA DE AHORRO SUGERIDA INCLUYE LA DISMINUCIN DE LA CARGA TOTAL DE ILUMINACIN DE 142 KW A 74 KW DE DEMANDA Y EL CONSUMO DE REDUCIRLO DE POCO MAS DE 52,000 KWH A 27,500 KWH AL MES. ESTO SE LOGRARA CON LA INSTALACIN DE SISTEMAS MAS EFICIENTES COMO LAS LMPARAS T8 QUE VENDRN A SUSTITUIR A LAS T12 EN LAS REAS DE MAYOR CONSUMO, AS COMO LMPARAS T5 EN ARREGLOS DE 4 X 54 WATTS MONTADAS EN GABINETES CON REFLECTOR ESPECULAR PARA SUSTITUIR A LOS ADITIVOS METLICOS DE 400 WATTS, OCASIONANDO ADEMS UNA MEJORA EN LA CANTIDAD DE ILUMINACIN Y UNA VIDA TIL MAS PROLONGADA. LA SITUACIN GENERAL PARA EL AHORRO EN LAS NAVES SE PUEDE VER EN LAS SIGUIENTES GRAFICAS:

150.00 100.00 50.00 NAVE 1 NAVE 2 NAVE 3 Total kW Actuales kW Propuestos

60,000.00 50,000.00 40,000.00 30,000.00 20,000.00 10,000.00 NAVE 1 NAVE 2 NAVE 3 Total kWH Actuales kWH Actuales kWH Propuestos

kW Propuestos

kW Actuales kWH Propuestos

ILUMINACIN
PROPUESTA DE AHORRO ECONMICO
EL AHORRO ECONMICO GENERADO POR EL CAMBIO DE LOS SISTEMAS DE ILUMINACIN ACTUALES ASCIENDE A $ 43,202.40 MENSUALES, LO QUE SIGNIFICA UN AHORRO DE $ 518,428.8 PESOS ANUALES.
EDIFICIO COMEDOR REA DE CARGA Y ALMACEN OFICINAS EXTERIORES NAVE 1 INTERIOR NAVE 1 REAS DE FUGAS OFICINAS DE PRODUCCIN SUBESTACIN Y MANTENIMIENTO TOTAL INTERIOR NAVE 2 OFICINAS NAVE 2 SUBESTACIN REA DE HERRAMENTALES Y PROTOTIPOS EXTERIORES NAVE 2 TOTAL INTERIOR NAVE 3 SALAS DE PRUEBA E INGENIERAS OFICINA Y FUNDICIN EXTERIORES NAVE 2 TOTAL TOTAL GENERAL DEMANDA KW 7.0 5.3 0.4 26.9 1.0 1.4 KWH BASE 241.9 287.3 24.7 3825.2 62.9 82.2 CONSUMO KWH INTERM KWHPUNTA NAVE 1 564.5 670.3 57.7 8925.5 146.7 191.7 161.3 191.5 16.5 2550.1 41.9 54.8 KWH TOTAL 967.7 1149.1 98.9 15300.9 251.5 328.6 $ KW $902.97 $684.51 $50.03 $3,484.95 $129.34 $186.83 COSTOS MENSUALES $ KWH $1,120.71 $1,330.83 $114.51 $17,719.93 $291.23 $380.61 $ TOTAL $2,327.24 $2,317.64 $189.22 $24,385.62 $483.66 $652.55

1.3 43.2
12.1 0.3 0.3 2.3 1.5 16.6 3.2 4.7 0.7 0.0 8.6 68

78.0 4,602
765 21 8 147 106 1,047 203 298 42 3 545 6,194

182.0 10,738
1,785 49 18 342 248 2,442 473 695 97 7 1,272 14,452

52.0 3,068 NAVE 2 510 14 5


98 71 698 NAVE 3 135 199 28 2 363 4,129

312.0 18,409
3,060 84 30 587 425 4,186 810 1,192 166 12 2,180 24,775

$166.22 $5,604.85
$ $ $ $ 1,573.98 43.11 39.85 301.79

$361.38 $21,319.20
$ $ $ $ 3,544.12 97.08 35.28 679.55

$606.74 $30,962.66
$5,885.82 $161.22 $86.39 $1,128.54 $785.78 $8,047.75 $1,558.46 $2,291.63 $319.65 $22.24 $4,191.98 $ 43,202.40

$ 191.22 $2,149.96 $ $ $ 416.76 612.83 85.48

$ 492.07 $4,848.09 $ $ $ 938.42 1,379.90 192.48

$ 5.41 $1,120.48 $ 8,875.29

$ 13.93 $2,524.72 $ 28,692.01

ILUMINACIN
RESUMEN AHORROS ECONMICOS POR CAMBIOS DE SISTEMAS DE ILUMINACIN
$20,000.00 $12,225.00 $15,000.00 $10,000.00$6,620.14 $5,000.00 $0.00 NAVE 1 NAVE 2 $4,279.54 $2,129.59 $9,581.64 $1,952.39 $831.91 $18,456.93 $100,000.00 $80,000.00 $60,000.00 $67,532.66 $90,838.29

$40,000.00
$20,000.00 $ - kW Actuales $ - kW Propuestos

$25,179.86 $15,977.44 $31,840.88 $7,328.19 $4,765.79 $1,895.22 NAVE 1 NAVE 2 NAVE 3

$0.00

$ - kWH Actuales $ - kWH Propuestos

NAVE 3

Total $ - kWH Propuestos

Total

$ - kW Propuestos

$ - kW Actuales

$ - kWH Actuales

EL AHORRO TOTAL EN CONCEPTO DE DEMANDA ES DE 68 kW Y EN CONSUMO DE ENERGA ES DE 24,775 KWH AL MES. EN LA GRFICA SE MUESTRA LA DIFERENCIA DE COSTO POR DEMANDA Y CONSUMO ENTRE LOS SISTEMAS ACTULES Y LOS PROPUESTOS. SE PUEDE OBSERVAR QUE EL MAYOR AHORRO OBTENIDO ES EN LA NAVE 1 POR LOS CONCEPTOS DE CONSUMO Y DEMANDA , SIENDO DE 43 kW DE DEMANDA Y 18,409 KWH, LO QUE REPRESENTA UN AHORRO DE $30,962.66 PESOS MENSUALES POR CARGOS DE DEMANDA Y CONSUMO DE LA NAVE 1.

AIRE ACONDICIONADO
DESCRIPCIN, RESULTADOS Y PROPUESTA DE AHORRO ENERGTICO

AIRES ACONDICIONADOS
SITUACIN ACTUAL
ACTUALMENTE LA PLANTA CUENTA CON SISTEMAS DE VENTANA Y MINISPLIT DE CAPACIDADES DE 12,000; 18,000; 24,000 Y 36,000 BTU, ASI COMO TRES UNIDADES DE PAQUETEDE 60,000 BTU, PARA CLIMATIZACIN DE SUS REAS. LAS CAPACIDADES MAS ENCONTRADOS FUERON LOS DE 24,000 BTU. CON EL 56% DE LA CARGA INSTALADA EN A.A.
GRAFICA DE DEMANDA INSTALADA POR SISTEMAS GRAFICA DE CONSUMO POR SISTEMAS

SISTEMAS DE 60,000 BTU, 10.76, 14% SISTEMA S DE 36,000 BTU, 16.56, 21%

SISTEMA 5,000 BTU, 0.46, 0%

SISTEMAS DE 12,000 BTU, 2.90, 4% SISTEMAS DE 18,000 BTU, 3.73, 5%

SISTEMAS DE 60,000 BTU, 1,891.06 , 11% SISTEMAS DE 36,000 BTU, 2,970.90 , 17%

SISTEMA 5,000 BTU, 107.77 , 1%

SISTEMAS DE 12,000 BTU, 634.82 , 4% SISTEMAS DE 18,000 BTU, 1,374.46 , 8%

SISTEMAS DE 24,000 BTU, 44.18, 56%

SISTEMAS DE 24,000 BTU, 10,302.13 , 59%

AIRES ACONDICIONADOS
SITUACIN ACTUAL
Sistema
SISTEMA DE 5,000 BTU, MARCA FREYVEN DE VENTANA UN SISTENMA DE VENTANA Y TRES TIPO MINI SPLITDE 12,000 BTU, MARCAS SAMSUNG, RHEEM Y PRIME SISTEMAS DE 18,000 BTU MARCAS CARRIER Y LG SISTEMAS DE 24,000 BTU MARCAS RHEEM, LG, LENNOX, TOSHIBA, PRIME,CLASSIC, COMODAIRE Y SAMSUNG

Cant.
1

Capacid Factor Capacid Relacin ad Capacid de ad Eficienci Horas de Consumo Unitaria ad Total Utilizaci Entrega encia Carga Uso Mensual T.R. T.R. n (%) da T.R. kW/TR Total kW Hrs/Mes kWh
0.42 0.42 100.00% 0.42 1.10 0.46 235.71 107.77

4 3

1.00 1.50

4.00 4.50

80.00% 90.00%

3.20 4.05

0.91 0.92

2.90 3.73

218.57 368.25

634.82 1,374.46

21 7 3 39

2.00 3.00 5.00

42.00 21.00 15.00 86.92

90.00% 90.00% 90.00%

37.80 18.90 13.50 77.87

1.17 0.88 0.80

44.18 16.56 10.76 78.60

233.18 179.37 175.71

10,302.13 2,970.90 1,891.06 17,281.14

SISTEMAS DE 36,000 BTU MARCAS FRESH, CLASIC, COMODAIRE


SISTEMAS DE 60,000 BTU MARCAS RHEEM Y PRIME

Total

LA CARGA TOTAL DEMANDADA POR LOS SISTEMAS DE ACONDICIONAMIENTO DE AIRE ES DE 78.6 kW, LO QUE REPRESENTA UN CONSUMO AL MES DE 17,281.14 KWH.ESTO REPRESENTA UNA EROGACIN MENSUAL POR ESTE CONCEPTO DE $23,119.97. M.N. (Tomando en cuenta el costo medio de kWh en $1.1581).

AIRE ACONDICIONADO
PROPUESTA DE AHORRO ENERGTICO
20.00 15.00 10.00 5.00 0.00 TRES DOS SISTEMAS DE SISTEMAS DE 24,000 BTU 36,000 BTU KW PROPUESTOS TOTAL 8.87 6.52 8,000.00 15.39 4,755.95 6,000.00 4,000.00 1,467.05 KWH ACTUALES 2,368.61 TRES SISTEMAS DE 24,000 BTU 987.58 DOS SISTEMAS DE 36,000 BTU 3,356.19 TOTAL KWH PROPUESTOS 6,223.00

2.14

2.12

4.26
KW ACTUALES KW PROPUESTOS

2,000.00
0.00

KW ACTUALES

KWH PROPUESTOS

KWH ACTUALES

SE PROPONEN SUSTITUIR LOS SISTMAS DE 24,000 BTU POR TRES AIRES ACONDICIONADOS TIPO DIVIDIDO RESIDENCIAL MARCA CARRIER MOD. 53FKXP363C 1 X 24000, 2 X 12000 Y DOS AIRES ACONDICIONADOS TIPO DIVIDIDO RESIDENCIAL MARCA CARRIER MOD. 24ANA736A003 SOLO FRIO. LOS AIRES ACONDICIONADOS DE MAYOR CONSUMO CON RESPECTO A LA CAPACIDAD DE ENFRIAMIENTO QUE GENERAN SON: TRES UNIDADES DE 24,000 BTU, CUYA IBICACIN ESTA DETERMINADA EN EL REPORTE Y DOS UNIDADES DE 36,000 BTU, CUYA UBICACIN SEDETERMINA EN EL REPORTE. ESTAS UNIDADES REPRESENTAN UN AHORRO DE 4.73 KW DE DEMANDA AL MES Y 2,866.81 KWH DE CONSUMO AL MES, COMO SE HACE EVIDENTE EN LAS GRAFICAS ANTERIORES.

AIRE ACONDICIONADO
RESUMEN DE LA PORPUESTA DE AHORRO ENERGTICO Y ECONMICO
Concepto
Demanda (kW) Consumo Mensual (kWh) Precio Medio ($/kWh), no incluye IVA Importe Mensual ($), IVA Incluido Importe Anual ($), IVA Incluido Inversin IVA Incluido=

Sistema Actual Sistema Propuesto


15.39 6,223 $1.16 $8,308.38 $99,700.60 $80,000.00 10.67 3356.19 $1.16 $4,484.03 $53,808.33 Recuperacin =

Ahorro
4.73 2,866.81 $3,824.36 $45,892.26 1.74

EL AHORRO ECONMICO MENSUAL SE ESTIMA EN $3,824.36 PESOS LO QUE IMPLICA UN AHORRO ANUAL DE $45,892.26 PESOS.

AIRE ACONDICIONADO
RESUMEN DE AHORROS ECONMICOS
EN LA GRFICA SE PUEDE VER LA DIFERENCIA ENTRE LOS SISTEMAS ACTUALES Y LOS PROPUESTOS, DENTRO DE LOS RUBROS DE COSTO DE LA DEMANDA ($/KW) Y COSTO DEL CONSUMO ($/KWH).

$1,995.05 $2,000.00 $1,500.00 $1,000.00 $500.00 $$- KW ACTUALES $277.88 TRES SISTEMAS DE 24,000 BTU $274.47 DOS SISTEMAS DE 36,000 BTU $552.35 TOTAL $- KW PROPUESTO $1,149.97 $845.09

$8,000.00 $6,000.00

$7,206.85 $5,507.86

$4,000.00
$2,000.00 $$2,743.09

$1,698.99

$- KWH ACTUALES $3,886.80 TOTAL $- KWH PROPUESTO

$1,143.71 TRES DOS SISTEMAS SISTEMAS DE 24,000 DE 36,000 BTU BTU $- KWH PROPUESTO

$- KW PROPUESTO

$- KW ACTUALES

$- KWH ACTUALES

BALANCE ENERGTICO DE LA PLANTA


El BALANCE ENRGTICO DE LA PLANTA SE HA DETERMINADO TOMANDO EN CUENTA A LOS EQUIPOS DE MAYOR DEMANDA Y LAS REAS QUE EQUIPARAN EN DEMANDA A LOS PRIMEROS. SE REALIZ EL BALANCE EN HORARIO PUNTA Y EL GENERAL PARA DETERMINAR LAS CARGAS DE MAYOR APORTE A LA PLANTA.

BALANCE ENERGTICO DE LA PLANTA


RESUMEN DEL LAS DEMANDAS Y CONSUMOS HISTRICOS SEGN LOSHISTORIALES DE CFE. LOS MXIMOS MNIMOS Y PROMEDIOS SE PRESENTAN EN LA SIGUIENTE TABLA.
DEMANDA ( kW ) CONSUMO ( kWh )

F.P.

PUNTA
MAXIMO MINIMO PROMEDIO 766 391 643

INTER.
918 668 778

BASE
940 679 744

FACT.
796 513 683

BASE
86,473 34,292 61,919

INTER.

PUNTA
41,388 11,588 24,742

TOTAL
350,637 167,931 254,196 98 83 88

241,769 119,296 172,123

1000.00 900.00 800.00 (kW) 700.00 600.00 500.00 400.00 300.00 200.00 100.00 0.00

DEMANDA MENSUAL
FACT. PUNTA INTER. BASE

BALANCE NERGTICO DE LA PLANTA


PARA EL BALANCE DE LA DEMANDA EN HORARIO PUNTA NO SE CONSIDERARON ESTRACTORES DEL REA DE INYECTORAS, NO SE CONSIDERO LOS MOTORES DE LAS ETAPAS DE DEGREASER, SECADO Y ROCIADO DE LOS HORNOS. EN LAS REAS SE CONSIDERARON LOS TABLEROS QUE ALIMENTAN A LAS PRINCIPALES MQUINAS. NO SE CONSIDER EL APORTE DE ILUMINACIN DE LAS REAS, SOLO LA ILUMINACIN DE LOS ADITIVOS METLICOS DE LAS REAS MAYORES DE LA NAVE1. EL MOLINO NO SE CONSIDERO Y ALGUNAS MQUINAS DEL REA DE HERRAMENTALES Y PROTOTIPOS TAMPOCO. SI SE TOMO EN CUENTA EL APORTE POR A.A. DE LAS REAS. TODO LO ANTERIOR FUE DESCARTADO POR QUE NO SE USABAN LOS EQUIPOS EN ESTE HORARIO O SE USABAN ALEATREAMENTE Y EN EL CASO DE LA ILUMINACIN DE LAS REAS, SU VALOR NO REPRESENTA UN APORTE SIGNIFICATIVO PARA LA DEMANDA PUNTA. EN EL BALANCE DE LA DEMANDA Y ENERGTICO GENERAL SE DIVIDIO CLARAMENTE LOS EQUIPOS, MQUINAS Y REAS CONSIDERADOS PARA CADA PARTE DEL BALANCE. LOS QUE APARECEN EN LA COLUMNA CARGAS SON LOS CONSIDERADOS.

BALANCE NERGTICO DE LA PLANTA


CARGAS

HORARIO PUNTA

1.-Inyectoras 2.-Hornos 3.-rea de Herramentales (Maquinas y A.A.) Compresor 75 HP, Torre de enfriamiento 4.-y Secadoras 5.-Chiller y Bombas 6.-Cabinas de prueba de fugas 7.-Iluminacin (Fija) 8.-A.A. (Fija) TOTAL

% 36% 32% 3%

KW 248.89 223.22 18.50

11% 6% 2% 8% 2% 100%

76.93 41.65 12.46 58.45 10.90 691

BALANCE GENERAL
TARIFA HM N1 Y N2 CARGAS % KW CARGAS % N1 Y N2 KW CARGAS % N3 KW

INYECTORAS Y 1.-ESTRACTORES HORNOS (SOPLADORES, 2.-BANDAS Y BOMBAS) 3.-REA HERRAMENTALES N2 COMPRESOR 75HP, TORRE DE ENFRIAMIENTO Y 4.-SECADORES
CHILLER , BOMBAS Y MOLINO DE PLASTICO

29% 27% 7% 12% 6% 1% 4% 15% 100%

254.95 232.94 65.73 107.25 48.62 5.96 30.84 132.50 879

REA DE OIL 1.-COOLER


OFICINAS N2 2.3.-107 MAQUINADO N2 106 PLASTICOS, 101 ENSAMBLE, 122 4.-SUAJADO N2 213 CONDENSADORES, 5.-103 MANGUERAS N2 6.7.8.117 MANIFOLD N2

3% 2% 3% 0% 1% 1% 0% 0%

26.05 16.817 24.33 0 8.73 4.59

1.2.3.4.5.6.7.8.-

IP N3

5% 0% 0% 0% 0% 0% 0% 0%

45.94

5.-

CABINAS DE PRUEBAS DE 6.-FUGAS 7.-A.A. DE LA PLANTA ILUMINACIN DE LA 8.-PLANTA TOTAL

TOTAL

9%

81

TOTAL

5%

45.94

BALANCE ENERGTICO DE LA PLANTA


EL BALANCE ENERGTICO DE LA PLANTA SE SIMULO PARA COMPARARSE CONTRA PAGO DE ENERGA DEL MES DE AGOSTO DEL 2007. EN ESTE MES EL PAGO DE ENERGA FUE DE $ 513,503 PESOS.
TARIFA HM (N1 Y N2) CARGAS INYECTORAS Y 1.-ESTRACTORES HORNOS Y MOTORES 2.-PERIFERICOS 3.REA HERRAMENTALES N2 COMPRESOR 75HP, TORRE DE ENFRIAMIENTO Y SECADORES 4.5.CHILLER Y BOMBAS 48.62 5.96 34.07 6% 1% 4% 16% 100% 397 207 184 368 19,302.14 1,232.69 6,268.88 48,760.00 302,795.36 6.37% 0.41% 2.07% 16.10% 100% $ $ $ $ $ 32,008.52 2,413.54 12,764.80 82,112.62 510,685.45 6.27% 0.47% 2.50% 16.08% 100% KW 232.03 232.94 65.73 % 28% 28% 8% HRAS AL MES 396 398 184 KWH 91,883.30 92,711.51 12,093.89 % 30.35% 30.62% 3.99% $ TOTALES (INCLUYE IVA) $ $ $ 152,444.78 153,666.39 24,625.79 % 29.85% 30.09% 4.82%

76.93

9%

397

30,542.95

10.09%

50,649.02

9.92%

CABINAS DE PRUEBAS DE 6.-FUGAS 7.8.A.A. DE LA PLANTA

ILUMINACIN DE LA PLANTA 132.50 TOTAL 829

RESUMEN DE AHORROS OBTENIDOS


MEDIDAS DE AHORRO DE ENERGA AHORROS MAE DESCRIPCIN Kw (D.F.) Kwh/mes Kwh/ao $/ao INVERSIN $ PAY-BACK Aos

SUSTITUCIN DE SISTEMAS DE ILUMINACIN

68

24,774

297,300

$ 518,428.76

$ 1,000,000.00

1.92

SUSTITUCIN DE AIRES ACONDICIONADOS

4.73

2,866.81

34,401.72

$ 45,892.26

$ 87,000.00

1.89

TOTAL

72.73

27,640.81

331701.72

$564,321.02

$1,087,000.00

1.92

Nota: El promedio anual pagado por AIR TEMP DE MEXICO SA DE CV, segn su historial es de $/kW = 129.61 y $/kWH = 1.1581 (El precio por kWH de $1.1581, es considerando que ya la correccin del factor de potencia, el precio actual es de $1.2035). Los cuales fueron utilizados para los clculos de ahorros presentados. Los ahorros incluyen IVA.

CONCLUSIONES
ILUMINACIN.
LOS SISTEMAS DE ILUMINACIN ACTUALES SON MUY DEFICIENTES EN CUANTO A CANTIDAD DE ILUMINACIN Y AHORRO DE ENERGA, ADEMS DE QUE REQUIEREN DE LIMPIEZA. LA CANTIDAD DE ILUMINACIN QUE SE REQUIERE DURANTE EL DIA EN LAS NAVES INDUSTRIALES PUEDE SER FACILMENTE OBTENIDA DE LA LUZ NATURAL MEDIANTE LA COLOCACIN DE LAMINAS TRANSLUCIDAS. EL USO DE CONTROLADORES PARA EL ENCENDIDO Y APAGADO DE LOS SISTEMAS DE ILUMINACIN PUEDEN OFRECER BENEFICIOS AL CONTROLAR LA CANTIDAD DE LMPARAS ENCENDIDAS EN HORARIO PUNTA.

AIRE ACONDICIONADO.
LOS SISTEMAS DE ACONDICIONAMIENTO DE AIRE PRESENTAN UN DESEMPEO ADECUADO QUE PUEDE SER MEJORADO CAMBIANDO ALGUNOS DE SUS HBITOS DE USO. ESTOS HABITOS SE DESCRIBEN EN EL APARTADO DE RECOMENDACIONES. EN GENERAL EN EL REA DE ACONDICIONAMEINTO DE AIRE SE CUENTAN CON EQUIPOS QUE AUN PUEDEN BRINDAR SERVICIO POR UN TIEMPO SIN UNA CLARA DIFERENCIA EN CUANTO A SU EFICIENCIA CON RESPECTO A LOS EQUIPOS DE TECNOLOGA MAS RECIENTE. SIN EMBARGO, ES IMPORTANTE RECALCAR QUE LA EFICIENCIA DE ESTOS EQUIPOS NO SOLO ESTA SUPEDITADA A LA PARTE MECANICA INTERNA DEL MISMO SINO, SOBRE TODO, A LA PARTE DEL ENVOLVENTE DE LA SUPERFICIE A CLIMATIZAR. POR LO QUE SE DESCRIBEN ALGUNAS RECOMENDACIONES AL RESPECTO.

RECOMENDACIONES
ILUMINACIN:
INSTALAR LMINAS TRANSLUCIDAS EN LAS NAVES INDUSTRIALES PARA LA OBTENCIN DE LUZ NATURAL. DAR LIMPIEZA PERIODICA A LAS LMPARAS A INSTALAR. IMPLEMENTAR UN CONTROLADOR DE ENCENDIDO Y APAGADO DE LAS LMPARAS AUTOMTICO, PUES EXISTEN REAS QUE SE QUEDAN PRENDIDAS EN HORARIO PUNTA SIN NECESIDAD, COMO LA NAVE 2, Y ALGUNAS REAS DE LA NAVE 1.

AIRE ACONDICIONADO:
AJUSTAR LOS TERMOSTATOS DE LOS AIRES ACONDICIONADOS AL MNIMO RECOMENDADO (24C). NO OBSTRUIR LA CIRCULACIN DEL AIRE DE INYECCIN NI DE RETORNO DE LOS EQUIPOS. EVITAR INFILTRACIN DE CALOR POR PUERTAS Y/O VENTANAS, SELLNDOLAS. REALIZAR MANTENIMIENTOS PREVENTIVOS DE LOS EQUIPOS PARA MANTENER SU EFICIENCIA. LIMPIAR CONDENSADORES CADA 6 MESES. PINTAR TECHOS DE BLANCO EN LAS NAVES. PINTAR LAS PAREDES CON INCIDENCIA SOLAR DE COLORES CLAROS.

Potrebbero piacerti anche