1. Generator Differential 2. Inter turn protection. 3. 95% Stator Earth fault protection 4. 100% Stator Earth fault protection. 5. Under frequency protection 6. Over frequency protection. 7. Rotor Earth fault Protection.
Generator Protection
8. Reverse Power Protection. 9. Low forward Power Protection. 10. Negative Phase sequence Protection. 11. Field failure Protection. 12. Pole slip Protection. 13. Under Voltage Protection. 14. Over Voltage Protection.
Generator Protection
15. Voltage Balance Protection. 16. Dead Machine Protection.
1. 2.
95% Earth fault Protection 95% Stator Stator Earth fault Protection
For indirectly connected applications , the time delayed earth fault protection in one of two ways. 1. To measure earth fault current directly,via a CT in the secondary circuit of a distribution Transformer earthing arrangement. 2. To measure earth fault directly via a CT in the Generator Winding. With the first mode of application , the current operated protection function(51N) may be used in conjunction with voltage operated protection(59N).
Under frequency Consequences Generator * Reduced output Capability * Thermal Damages * Over Fluxing Turbines * Blade Stresses * Mechanical Resonance
Gas turbine
Hydro turbine
10 % to 15 %
0. 2 % to 2%
Mechanical
Blade &Runner Cavitations Thermal Stress Damage
Steam Turbine
0. 5% to 3 %
Contd..
In the event of the current supplied to the Power system becoming unbalanced. The degree of susceptibility will depend on the generator Rotor design.(cylindrical,or salient construction), methods of forced cooling employed and the presence of any ancillary metallic rotor components. The I22t for Thermal 30 Hydel 40 And continuous negative sequence current(I2) is 8%.