Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Contents
Introduction Frame leakage protection High impedance bus differential Low impedance bus differential Busbar configurations Breaker failure protection
2007 Protection Engineering And Research Laboratories 17th March 2007 2
Introduction
2007 Protection Engineering And Research Laboratories 17th March 2007 3
Busbar Protection
Busbar faults are very rare. Busbar protection not provided always Without busbar protection
No dislocation of system due to accidental operation of busbar protection. Slow fault clearance.
Busbar faults are cleared by remote time delayed protection on circuits feeding the faults:
Time delayed over current or Time delayed distance protection
17th March 2007 4
THEREFORE :
Circuit breakers should be tripped and locked out by busbar protection
2007 Protection Engineering And Research Laboratories 17th March 2007 5
Busbar Protection
BUSBAR ZONE F1 F2
Busbar Protection
RELIABILITY
Failure could cause widespread damage to the substation
STABILITY
False tripping can cause widespread interruption of supplies
to customers
DISCRIMINATION
Should trip the minimum number of breakers to clear the
fault
SPEED
To limit damage and possible power system instability
Differential Protection :
High Impedance
Low Impedance
Switchgear insulated by standing on concrete plinth Only one earthing point allowed on switchgear C.T. mounted on single earth conductor used to energise
instantaneous relay
All cable glands must be insulated
17th March 2007 10
Generator
Earth bar
I1 + I2
I1 Frame insulation resistance to earth (> 10) I1 I2
Disadvantages
Insulation of switchgear frame and between sections. Insulation of cable glands to prevent spurious currents during through faults.
0.2-1 sec.
64 Z1
64 Z2
B1
B2
Trip A
Trip B
Trip C
Both check and discriminating relays must operate before tripping can occur.
Check relays are normally self-reset in order to avoid having to reset the relay after each external fault.
A B C N
87A 87A 87A
Differential relay
2007 Protection Engineering And Research Laboratories 17th March 2007 18
Requires stabilising resistors, RST May require non-linear resistors (Metrosils) If CT requirements are met, scheme performance may be predicted by calculation without heavy current conjunctive tests
2007 Protection Engineering And Research Laboratories 17th March 2007 20
RST METROSIL 87
Effective Setting
Since in each zone of protection there are several CTs in parallel with the relay and each other, the combined CT magnetising currents will increase the primary operating current (P.O.C). P.O.C. = CT ratio (IR + INLR + nIM)
where :IR IM n = = = Relay setting current CT magnetising current (one CT at relay setting voltage) Number of paralleled CTs Non linear resistor current at relay setting voltage
17th March 2007 22
INLR =
Generally this value is derived from the rating of the associated switchgear irrespective of existing fault level, since it can be expected that system can grow
up to limit of rating.
Check Feature
Provided by duplication of primary protection using second set
of CTs on all circuits other than bus section and coupler units.
Check system forms one zone only, covering whole of busbar systems and not discriminating between faults on various sections.
Zone A
87A
87A
Zone B
Check zone
87A
CT Wiring Supervision
Open circuit connections between CTs and relay circuit result in unbalance currents which may operate the protection. Supervision is applied by a voltage relay across
CT Wiring Supervision
I1
CT1 V
Supervision relay
RST
I3
I4
RR I1
Voltage measured by supervision relay V 1 (R || ZM2 || ZM3 || ZM4 ) If supervision relay setting VSP Out - of - balance current tooperate the supervision relay V V V V SP SP SP SP R ZM2 ZM3 ZM3
2007 Protection Engineering And Research Laboratories 17th March 2007 27
Supervision relay
Non-linear resistors
v
87
v
87
v
87
Stabilizing resistors
CT burden reduced in distributed architecture Continuous supervision of CT circuits and constant monitoring of vital circuits are included.
BS
F3
F4
FM 1
FM 2
BSM
FM 3
FM 4
Z1 ZCK
Z2 ZCK
Z1
ZCK
Z2
17th March 2007 33
BC1
F1
F2
F3
F4
BC2
BCM 1
Z1 Z3 ZCK
FM 1
FM 2
BSM
FM 3
FM 4
BCM 2
Z2 Z4 ZCK
Z1
Z3
ZCK
Z2
Z4
Bus Arrangements
2007 Protection Engineering And Research Laboratories 17th March 2007 35
Circuit protection
Interlocked over current relay Circuit protection Busbar protection Circuit protection Busbar protection
Busbar protection
Interlocked over current relay All C.T.s on line side of circuit breaker All C.T.s on Busbar side of circuit breaker
Overlapping C.T.s
132kV
BC
BC
Zone J
In order to maintain stability on switching, auxiliary switches should : 1) Close before the isolator
a b c d
r Bus wires
Tripping Circuits
One trip relay is required for each feeder breaker
The trip relays have to be lock-out type (hand reset) Both main and check relays must be energized for the tripping relays to trip all breakers associated with that zone.
Reserve / Transfer
By-pass Isolator
By-pass Isolator
Triple Busbar
Main
Transfer
1 Breaker Scheme
Bus 1
Bus 2
2007 Protection Engineering And Research Laboratories 17th March 2007 43
87
Mesh Busbar
F1 F3
T1
T3
T4
T2
F4
2007 Protection Engineering And Research Laboratories
F2
17th March 2007 45
F1
F3
87 R3
T1
T3
T4
T2
87 R4
87 R2
F4
2007 Protection Engineering And Research Laboratories
F2
17th March 2007 46
Inst. O/C
Td
Thank you
2007 Protection Engineering And Research Laboratories 17th March 2007 50