Lecture Objectives:
Discuss the final project assignment Finnish with Review of HVAC systems
Air-conditioning in Air Handling Units (AHU) Refrigeration cycles
Building-System-Plant connection
Final project
Today and on Monday Extended office hours for project topic and objective discussion After that you will prepare more detailed project proposal (1 2 pages) with
- Project objective - Methodology - Expected results Any schematic drawing is welcome
Detailed analysis!
Water 120F
Water 52F
Building
Inside 75F
Task: analyze COP for the whole year and different locations
Summer
Winter
In the summer, the earth acts as a cooling tower. The Cooling Machine loads the loop with heat, sending warmed water to be cooled by the earth
In the winter, the earth acts as the boiler. The Heat Pump extracts heat from the loop, sending cooled water to be warmed by the earth.
Residential buildings
It is very expensive to optimize each residential building We optimize example buildings to develop local codes
Your ideas
Project Timeline
11/12/12 - project defined and approved 11/20/12 - generated model 11/29/12 - report the preliminary results 12/04/12 - oral presentations 12/06/16 - project paper submission
Project Grading
GRADING CRITERIA (30% of your final grade): 1) Analysis approach: 60% - Modeling quality 20% - Result accuracy 20% - Result analysis 20% 2) Deliverables: 40% - Quality of the final report 25% - Quality of oral presentations 10% - Submission timeline 5%
Undergraduate students
Engineering report
Graduate students
Research report
Building-System-Plant
HVAC System (AHU and distribution systems)
Building
AHU
Distribution systems
Air transport
Electricity Secondary systems Heating (boilers) Building envelope HVAC systems affect the energy efficiency of the building as much as the building envelope
Cooling (chiller)
(or Gas)
Gas
AHU schematic
Exhaust From room Return fan
Supply fan
To room
Gas/Electric Heater
cool water
hot water
OA
Refrigeration Cycle
Released energy (condenser)
T outdoor air
T cooled water
- What is COP? - How the outdoor air temperature affects chiller performance?
Integrated models
Building
Heating/Cooling System
Plant
QC
QH
mS TS wS room TR wR
(1-r)mS TO wO
mS
TM wM
rmS
fans
cooler
heater
TR wR
Qroom_sensibel Qroom_latent
m - mass flow rate [kg/s], T temperature [C], w [kgmoist/kgdry air], r - recirculation rate [-], Q energy/time [W]
Energy and mass balance equations for Air handling unit model steady state case
The energy balance for the room is given as:
Qroom_ sensible mS c p TR TS
mS is the supply air mass flow rate cp - specific capacity for air, TR is the room temperature, TS is the supply air temperature.
TM (1 r ) TO r TR
r is the re-circulated air portion, TO is the outdoor air temperature, TM is the temperature of the air after the mixing box.
wM (1 r ) wO r wR
wO is the outdoor air humidity ratio and wM is the humidity ratio after the mixing box
QHeating mS c p (TS TM )
The energy balance for the cooling coil is given as:
Tw_in
Q rad_pan
rad iat ion
Tzone_air
Ro om (zone 1)
m s ,Ts = const. air supply system
Tsurounding
Qzone
Qair (mc p ) sup ply _ air (Tsup ply _ air Troom _ air )
Qrad _ pan
The energy extracted/added by the radiant panel is the sum of the radiative and convective parts:
Qrad _ pan Qradiation Qconv hradiation ,i Apanel (Tpanel Tsurface,i ) hconv Apanel (Tpanel Tair )
The radiant panel energy is: