MODULE THREE
10/5/2013
Module Three
INTRODUCTION
The electrical commissioning and acceptance testing of electric power systems is essential for the energization of any electrical system for the first time.
10/5/2013
Module Three
INTRODUCTION
Module Three Discuss theory and ratings Safety issues Test equipment operation & hands on testing
10/5/2013
Module Three
INTRODUCTION
Skills learned in MODULE THREE: Acceptance testing for CTs and VTs Operate CT tester Apply safe work practices Analyze test values Complete test forms
10/5/2013
Module Three
INSTRUMENT TRANSFORMERS
A general classification Current transformers (CT) Voltage transformers (VT) Standard secondary rating: 5A for CT 120V for VT < 24 kV 115V for VT > 24 kV
Isolate primary quantities and convert into useable secondary values via transformation
Measurement values from CTs and VTs: Voltage, current, frequency, real / reactive power, energy, power factor, impedance
5
10/5/2013
Module Three
INSTRUMENT TRANSFORMERS
Polarity markings A designation of the relative instantaneous direction of currents
Current flowing into the polarity mark in the primary is relatively in phase with current flowing out the polarity mark in the secondary As if the primary and secondary are connected straight through
10/5/2013 Module Three 6
INSTRUMENT TRANSFORMERS
10/5/2013
Module Three
INSTRUMENT TRANSFORMERS
Nameplate Data Manufacturers name or trademark Manufacturers type Serial number Rated Voltage, maximum voltage or nominal system voltage Rated frequency Basic impulse insulation level (N/A for bushing CTs) Continuous rating factor for CT (1.0 or more) Thermal burden rating for VT (VA) Accuracy rating
10/5/2013
Module Three
INSTRUMENT TRANSFORMERS
Nameplate Symbols (: colon) Ratio expression between winding groups Example: VT with one primary and one secondary winding 14,400 : 120 V Ratio 120 : 1 Ratio between primary and secondary amperes
Example: CT with one primary and one secondary winding 100 : 5 A Ratio 20 : 1
10/5/2013
Module Three
INSTRUMENT TRANSFORMERS
Nameplate Symbols (x multiplication sign) Voltage rating or ratios between winding groups Current rating with two or more coils for series of parallel connection Example: CT with two primary windings for series or parallel conn. 100 x 200 : 5 A
Example: VT with two windings for series or parallel connection 2,400 x 4800 V Ratio 20 x 40 : 1
10/5/2013
Module Three
10
INSTRUMENT TRANSFORMERS
Nameplate Symbols (// double slant lines) (Not used for VT) Ampere rating of separate secondary winding with independent core Example: CT with two secondary windings and two cores. 100 : 5 // 5A
10/5/2013 Module Three 11
INSTRUMENT TRANSFORMERS
Nameplate Symbols (& ampersand) Voltage rating or ratios of separate winding on one core. Ampere rating of separate primary winding on one core.
Example: VT with one primary and two secondary winding 14,400 V: 120 & 72 V Ratio 120 & 200:1
10/5/2013
Module Three
12
INSTRUMENT TRANSFORMERS
Nameplate Symbols (& ampersand) Example 2: Totalizing CT with four primary windings designed to be used simultaneously. 5 & 5 & 5 & 5 : 5A
10/5/2013
Module Three
13
INSTRUMENT TRANSFORMERS
Nameplate Symbols (& ampersand) Example 3: CT for threewire single phase.
10/5/2013
Module Three
14
INSTRUMENT TRANSFORMERS
Nameplate Symbols (/ single slant line) Two or more primary or secondary ratings obtained by taps in the secondary winding Example 1: VT with secondary tap for more primary voltage rating Different primary current ratings obtained by taps in the secondary winding
INSTRUMENT TRANSFORMERS
Nameplate Symbols (/ single slant line) Example 2: VT with secondary tap for additional secondary voltage ratings 14,400 : 120/72 V Ratio 120/200:1
10/5/2013
Module Three
16
INSTRUMENT TRANSFORMERS
North American Standards
CSA Originated in 2007 An adoption of IEC 60044 part 1 to part 7 ANSI/IEEE IEEE C57.13-2008 Standard Requirements for Instrument Transformers ANSI/IEEE C57.13.1-1981 Guide for Field Testing of Relaying Current Transformers
10/5/2013
Module Three
17
INSTRUMENT TRANSFORMERS
CSA Standards CAN/CSA-C60044-1 to -8 (part 1 to part 8), 2007 Part 1: Current Transformers Part 2: Inductive Voltage transformers Part 3: Combined Transformers Part 4: N/A Part 5: Capacitive Voltage transformers Part 6: Requirements for Protective Current Transformers for Transient Performance Part 7: Electronic Voltage Transformers Part 8: Electronic Current Transformers
10/5/2013 Module Three 18
INSTRUMENT TRANSFORMERS
What is a CT ? A device that isolates and transforms the primary current quantity into a proportional secondary current quantity
The CT has: Primary winding or primary conductor Magnetic core Secondary winding
10/5/2013
Module Three
19
INSTRUMENT TRANSFORMERS
INSTRUMENT TRANSFORMERS
How does a CT work ? Primary current flows generates magnetic field around the conductor Magnetic field flows in the magnetic core Magnetic field induces a voltage in the secondary winding Burden connected to secondary winding completes the circuit and allows current to flow
10/5/2013
Module Three
21
INSTRUMENT TRANSFORMERS
Ipri x Npri = Isec x Nsec Ipri = Isec = Npri = Nsec = Current flowing in primary winding Current generated in secondary winding Number of turns in primary winding Number of turns in secondary winding
10/5/2013
Module Three
22
INSTRUMENT TRANSFORMERS
What is the secondary current ? CT ratio: 5000:5A; 1000:1 Iprimary = 1000A
INSTRUMENT TRANSFORMERS
Never open the secondary of a CT when primary current is flowing because dangerous high voltages will appear. IEEE C57.13 allow open circuit crest voltages up to 3500 V peak without voltage limiting devices.
10/5/2013 Module Three 24
INSTRUMENT TRANSFORMERS
CT Types Torroidal Wound Primary Bar Type Split Core Tororoidal Low flux leakage Typical of bushing and window CTs Primary conductor pass through center 600V insulation can be used in MV application with insulated primary conductors
10/5/2013
Module Three
25
INSTRUMENT TRANSFORMERS
CT Types
Wound Primary Has an internal primary winding Wound more than 1 full turn on the core Core can be torroidal Must be inserted in series with the conductors Bar provides primary connection points, often mistaken for bar type
26
10/5/2013
Module Three
INSTRUMENT TRANSFORMERS
CT Types Torroidal (donut) Wound Primary Bar Type Split Core Bar Type Has a continuous bar for the primary winding Only 1 turn primary Core can be torroidal Must be inserted in series with the conductors Primary insulation part of CT construction
10/5/2013
Module Three
27
INSTRUMENT TRANSFORMERS
CT Types Torroidal (donut) Wound Primary Bar Type Split Core Split Core Core is separated into two parts For use where primary conductor cannot be easily removed
10/5/2013
Module Three
28
INSTRUMENT TRANSFORMERS
10/5/2013
Module Three
29
INSTRUMENT TRANSFORMERS
CT Ratio Ratio or primary current to secondary current
10/5/2013
Module Three
30
INSTRUMENT TRANSFORMERS
Adjusting CT Ratio (low V) For some applications KA = (KN NSA) / NP KA = Actual ratio KN = Nameplate ratio NSA = Number of adjusted secondary turns adjusted To Add: loop X1 lead through H1. To Subtract: loop X1 opposite H1) NP = Number of primary turns
31
10/5/2013
Module Three
INSTRUMENT TRANSFORMERS
CT Ratio Adjustment 20:5 CT needed 50:5 CT available
10/5/2013
Module Three
32
INSTRUMENT TRANSFORMERS
CT Standard Burden @ 5A, @ 60 Hz
10/5/2013
Module Three
33
INSTRUMENT TRANSFORMERS
Basis for Accuracy class for Metering CTs and VTs correction factor is within specified limits for specified load conditions
.6 lagging to unity PF
CT operating between 10% to 100% rated current
10/5/2013
Module Three
34
INSTRUMENT TRANSFORMERS
IT Standard Accuracy Class for Metering @ 60 Hz
10/5/2013
Module Three
35
INSTRUMENT TRANSFORMERS
CT Accuracy Rating for Metering Accuracy for a specified burden Example: 0.3 B 1.8 .3% accuracy for all other burden up to 1.8 Example: 0.3 B @ 0.2 .3% accuracy for burden of .2 and 3
10/5/2013
Module Three
36
INSTRUMENT TRANSFORMERS
CT Accuracy Rating for Relaying @ 60 Hz
10/5/2013
Module Three
37
INSTRUMENT TRANSFORMERS
Relaying CT Class C (Calculated) T X Class C Low leakage flux CTs Torroidal type 3% error @ 5A 10% error @ 100A
10/5/2013
Module Three
38
INSTRUMENT TRANSFORMERS
Relaying CT Class C T (Tested) X Class T High leakage flux CTs Primary Wound type % error obtained from testing Tested to 100A or > until 10% error is establish at specified burdens Test curve plotted for Ipr Vs Isec, the overcurrent curve
Module Three 39
10/5/2013
INSTRUMENT TRANSFORMERS
Relaying CT Class C T X (Defined) Class X User defined along with expected accuracy rating for protection application Minimum knee point voltage; Vk Maximum excitation current Ik at Vk Maximum secondary winding resistance at 75C, Rs
Module Three 40
10/5/2013
INSTRUMENT TRANSFORMERS
Secondary Terminal Voltage Saturation voltage level at 20X rated current
100 A
Vsat = 100 A x Burden
10/5/2013
Module Three
41
INSTRUMENT TRANSFORMERS
Saturation Curve B-H Curve Excitation Current Vs Excitation voltage Knee Point voltage, Vk 10% Ve 50% Ie
10/5/2013
Module Three
42
INSTRUMENT TRANSFORMERS
Transformer Formula Erms = 2 f N a Bpeak / 2 4.44 f N a B
Where: f = the supply frequency N = number of turns a = cross sectional area of the core B = peak magnetic flux density
10/5/2013
Module Three
43
INSTRUMENT TRANSFORMERS
Class C Saturation Curve Plotted on log-log scale Induced voltage Y-axis Excitation current X-axis Voltage begins at 1% Voltage ends at 5X Irated Vk identified where curve is at 45 tangent axis
10/5/2013
Module Three
44
INSTRUMENT TRANSFORMERS
10/5/2013
Module Three
45
INSTRUMENT TRANSFORMERS
Class T O/C Ratio Curve Plotted of linear scale Secondary current Y-axis Primary current X-axis 1 to 22 x rated I-primary for all standard burdens Curve identifies the burden which causes 50% ratio correction
10/5/2013
Module Three
46
INSTRUMENT TRANSFORMERS
What is a VT ? Isolate and transform the primary voltage into proportional secondary voltage Construction Primary winding Magnetic core Secondary winding
10/5/2013
Module Three
47
INSTRUMENT TRANSFORMERS
5 Groups of VT All capable of operating at 110% for emergency condition Emergency for 1 minute Some have special emergency rating conditions All must operate within thermal limits and or specified temperature rise
10/5/2013
Module Three
48
INSTRUMENT TRANSFORMERS
10/5/2013
Module Three
49
INSTRUMENT TRANSFORMERS
VT Accuracy Rating Accuracy rating for each standard burden For maximum burden For specified burden Example: 0.3 Z; 0.3 Y, 0.6 Z and 1.2 ZZ; 0.3 Z @ Y Accuracy for two 2ndary or tapped 2ndary windings Burden is the total for the VT Accuracy class apply with the burden divided between the 2ndaries outputs in any manner
10/5/2013 Module Three 50
INSTRUMENT TRANSFORMERS
Thermal Burden Rating The maximum volt-ampere (VA) it can carry within temperature design limits Each winding can have its own rating One specified rating is for combined distribution between the 2ndaries, including taps
10/5/2013
Module Three
51
10/5/2013
Module Three
52
10/5/2013
Module Three
53
10/5/2013
Module Three
54
DC Voltage test
Isolate Primary Isolate & Gnd Secondary Connect HV lead to H1/H2 Connect LV to Gnd / 2ndary Test for 1 minute Record test value
10/5/2013
Module Three
55
10/5/2013
Module Three
56
AC Voltage test
Isolate & Gnd Secondary Connect HV lead to H1/H2 Connect LV to Gnd / 2ndary Test for 1 minute Record test value
10/5/2013
Module Three
57
10/5/2013
Module Three
58
10/5/2013
Module Three
59
10/5/2013
Module Three
60
10/5/2013
Module Three
61
10/5/2013
Module Three
62
Total burden ()
DC Winding resistance () Lead resistance () Device impedance ()
RCT = RL = ZB =
10/5/2013
Module Three
63
10/5/2013
Module Three
64
10/5/2013
Module Three
65
10/5/2013
Module Three
66
10/5/2013
Module Three
67
10/5/2013
10/5/2013
Module Three
69
10/5/2013
Module Three
70
10/5/2013
Module Three
71
10/5/2013
Module Three
72
10/5/2013
Module Three
73
10/5/2013
Module Three
74
10/5/2013
NETA STANDARD
5. NETA Acceptance Testing Procedure
10/5/2013
5.1 Visual and Mechanical Inspection 5.2 Electrical Test 5.2.1 Current Transformer 5.2.2 Voltage Transformer 5.3 Test Value Analysis 5.3.1 Visual and Mechanical 5.3.2 CT Electrical Test 5.3.3 VT Electrical Test
Module Three 76
10/5/2013
Module Three
77
TEST FORMS
Current Transformer Test Form Voltage Transformer Test Form
10/5/2013
Module Three
78
10/5/2013
Module Three
79
10/5/2013
Module Three
80