Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Outline
Basic Introduction
Reactive power ; Voltage Stability ; PV curves
Frequency Stability
Small Disturban ce
Transient Stability
Short Term
Long Term
Large Disturbance
Small Disturbance
Short Term
1. P. Kundur, J. Paserba, V. Ajjarapu , Andersson, G.; Bose, A.; Canizares, C.; Hatziargyriou, N.; Hill, D.; Stankovic, A.; Taylor, C.; Van Cutsem, T.; Vittal, V Definitions and Classification of Power System Stability IEEE/CIGRE Joint Task Force on Stability Terms and Definitions , IEEE transactions on Power Systems, Volume 19, Issue 3, pp. 1387-1401 August 2004 3
Voltage Stability
It refers to the ability of a power system to maintain steady voltages at all buses in the system after being subjected to a disturbance. Instability may result in the form of a progressive fall or rise of voltages of some buses
4
A run down situation causing voltage instability occurs when the load dynamics attempt to restore power consumption beyond the capability of the transmission network and the connected generation
6
Instability is due to the loss of long-term equilibrium In many cases static analysis can be used For timing of control Quasi-steady-state time domain simulation is recommended
8
10
PF
0.95
Proposed WECC Low Voltage Ride-Through (LVRT) requirements for all generators1
Most grid codes now require that wind power plants assist the grid in maintain ing or regulatin g the system voltage
1. R. Zavadil, N. Miller, E. Mujadi, E. Cammand B. Kirby, Queuing Up: Interconnecting Wind Generation into The Power System November/December 2007, IEEE Power and Energy 12 Magazine
DS: Distribution Transmission 2. Florin Iov, Anca Daniela Hansen, Poul S rensen, Nicolaos Antonio Cutululis , Mapping of grid faults and grid codes Ris-R-1617(EN), July 2007
TS:
13
2. Florin Iov, Anca Daniela Hansen, Poul Srensen, Nicolaos Antonio Cutululis ,Mapping of grid faults and grid codes Ris-R-1617(EN), July 2007 14
In general all generators which are coupled to the network either with inverters or with synchronous generators are capable of providing reactive power ( for Example Doubly Fed Induction Generator) In DFIG real independently and reactive power can be controlled
Grid
Source: http://www.windsimulators.co.uk/DFIG.htm
15
Voltage Controller
A voltage controller placed at the Point of Interconnect (POI) measures utility line voltage, compares it to the desired level, and computes the amount of reactive power needed to bring the line voltage back to the specified range .
Monitors POI or remote bus PI control adjusts stator Qref signal from Verror Qmx/n
Qmax = Poutput tan(cos (0.95))
16
MVAR
Impact of Grid Side Reactive Boosting with (green) and without ( red ) Control
17
Rated electrical power Rated generator power Rated stator voltage Rotor to stator turns ratio Machine inertia Rotor inertia Inductance: mutual, stator, rotor Resistance: stator, rotor Number of poles Grid frequency Gearbox ratio Nominal rotor speed Rotor radius Maximum slip range
1.5 MW
1.3 MW
575 V 3 30 kgm2 610000 kgm2 4.7351, 0.1107, 0.1193 p.u. 0.0059, 0.0066 p.u. 3 60 Hz 1:72 16.67 rpm 42 m +/- 30%
18
Converter Sizing
Ptot [p.u.]
1 2 3 4 5 6
Qtot [p.u.]
0.80 0.72 0.63 0.49 0.37 0.33
slip [%]
25.26 11.50 1.33 -9.28 -25.14 -25.14
Vrotor [V]
244 108 8 97 254 254
Irotor [A]
Vdc-link [V]
440 195 14 175 460 460
Sconvert [kVA]
258.5 146.2 10.2 125.4 357.9 348.6
Various Wind Penetration Levels at 15, 20, 25 & 30% are simulated At each penetration level, total wind generation is simulated at 2, 15, 50 & 100% output
20
Penetration Level =
21
TM =
PVMARGIN MWactual
22
Power Transfer Margin at Different Penetration Levels (50 MVAr at 204 and 3008)
Base power transfer without wind is 13.5%
Penetration Level Plant Output
20%
25 %
30%
0% 15.1 33% 17.1 66% 19.5 100% 22.5 19.4 20.6 18.5 15.3 17.1
18.1
13.5
Unstable
23
n-1 outages
20% penetration at cut-in speed 20% penetration at 15% output 20% penetration at 100% output
25
PEC crowbar protection does not activate reactive injections during fault. Extended reactive capability stabilizes system
26
Q limits
CC control provides enhanced post fault voltage response Reduced V overshoot / ripple Increased reactive consumption at plant 3005
27
Q limits
28
29
For each PV curve the amount of wind generation is kept constant and the load and generation is increased according to a set loading and generation increase scenario
WIND GENERATION
Methodology Flowchart
The power flow data for the system under consideration.
The assumed level of wind generation in the base case and wind variability that is to be studied.
32
Observations
A larger power transfer margin available over the entire range of variability with Capability Curve Leads to higher penetration levels This tool helps determine the wind level at which minimum power transfer margin is obtained. This power level need not be at minimum wind or maximum wind. The tool also provides the most restrictive contingency at each wind level.
Conclusions
As levels of wind penetration continue to increase the responsibility of wind units to adequately substitute conventional machines becomes a critical issue
Recent advancement in wind turbine generator technology provides control of reactive power even when the turbine is not turning. This can provide continuous voltage regulation. A performance benefit , not possible with the conventional machines Wind generators can become distributed reactive sources. Coordination of this reactive power is a challenging task
The FERC order 661-A, gives general guidelines for interconnecting wind parks, but for specific parks employing DFIG units 38 the restriction on power factor can be lifted