VM1: innovation in power technology

1VCP000238 en 2006.11

VM1

VM1
Rated voltage Rated current kV 12 17.5 24 A ...2500 ...2500 ...2500

Rated short-circuit kA ...31.5 ...31.5 ...25 breaking current

ABB PT / 3

VM1
Common look and feel
the same common look and feel according to PT Guidelines for Product Design

new VD4
ABB PT / 4

new look VM1

VM1
new VD4 and new look VM1 have common frame suitable for interchangeable plug-in actuators

new VD4
ABB PT / 5

new look VM1

VM1

Emergency manual breaking mechanism

Electronic controller

Magnetic actuator

Electrical energy store

Sensors for switching position detection

ABB PT / 6

VM1
Main characteristics

Electronic maintenance-free
Controller with sensor technology Magnetic actuator with extremely high number of operating cycles

up to 100,000 operating cycles for breaking capacity up to 25 kA and rated current up to 1250 A up to 50,000 operating cycles with rated current > 1600 A and/or breaking capacity > 31.5 kA

Embedding technology to protect vacuum interrupters High quality standard External dimensions compatible with VD4 Developed for universal applications worldwide

ABB PT / 8

VM1
-SO4 Undervoltage opening (only with ED2.0 Full Option) -SL1 Contact locking the CB closing -SO3 Auxiliary and safety open (2^ open command from remote) -SO2 Open command from remote -SC2 Close command from remote

DO7 DO6 DO5 DO2 DO1

CB Remote Open Unit Not Ready Unit Ready CB closed CB open

24 .. 48V AC / 24 .. 60 V DC 100 .. 240V AC / 110 .. 250 V DC


Auxiliary voltage supply

ABB PT / 10

VM1

Electronic controller
ABB PT / 11

Capacitor

Sensors

VM1

ABB PT / 12

Magnetic actuator

VM1
Representation of magnetic flux density distribution

Magnetic latching in end-of-run position

Magnetic latching and action of the magnetic field of a coil


Armature position: Ampere-turns: 0 mm 12500 A

Moving armature in opposing position and magnetic end-of-run latching


Armature position: Ampere-turns: 20 mm 5000 A

Armature position: Ampere-turns:

0 mm 0 A

ABB PT / 13

VM1

y
Reduction of the magnetic flux density of Koerdym 280 as a function of the lifetime t at an ambient temperature of 120 C
ABB PT / 14

VM1
Basic version
Closing pushbutton (SC1) Opening pushbutton (SO1) Mechanical operation counter

Mechanical signalling device for circuit-breaker open/closed


Emergency manual opening device Lever for manual emergency opening Lamp signalling READY for the operation (PRDY) Capacitors for storing energy for the operation Mobile connector for direct connection to the sockets of the electronic module, to cable the auxiliary circuits ED2.0 standard version control module
ABB PT / 15

VM1
ED2.0 control module standard version
Signalling contacts without potential, fitted with relay, with the following functions:
N 1 contact signalling circuit-breaker open (DO1) N 1 contact signalling circuit-breaker closed (DC1) N 1 contact signalling circuit-breaker ready for the operation (capacitors charged and check of circuit-breaker state) (DR) * N 1 contact signalling circuit-breaker not ready for the operation (DN, normally closed)

N 1 transient contact with momentary closing during the opening operation (DOR)
Remark: with the circuit-breaker not supplied (without auxiliary power supply) these contacts are open, except the contact signalling circuit-breaker not ready for the operation (DN). * Not available in withdrawable version
ABB PT / 16

VM1
ED2.0 control module standard version
2 feeder power supply:
Type 1: 24 ... 48 V AC / 24 ... 60 V DC Type 2: 100 ... 240 V AC / 110 ... 250 V DC Binary inputs (logical inputs) for remote control: N 1 input for closing control (-SC2) N 1 input for opening control (-SO2) N 1 input for additional opening control (-SO3) N 1 input for circuit-breaker opening on direct command from the protection release PR512 (-SO5) N 1 input for lock on closing control (the same function of the locking electromagnet in the mechanical actuator of the VD4 circuit-breaker) (SL1)

Binary inputs:
24 ... 240 V AC ( 15% ... + 10%) 24 ... 250 V DC ( 30% ... + 10%) (minimum duration of the impulse is 20 ms)
ABB PT / 17

VM1
ED2.0 control module standard version
Functions: Self-opening following determination of incorrect state of circuit-breaker Self-opening following load threshold of the capacitors lower than the minimum value required for the opening and closing operation Anti-pumping relay function Trip-free function Monitoring of capacitor load with feeder turning itself off in the case of exceeding the maximum load level (these functions can be disabled by means of dip-switches)

ABB PT / 18

VM1
ED2.0 control module full option version (on request)
Signalling contacts without potential, fitted with relay, with the following functions:
N 2 contacts signalling circuit-breaker open (DO1, DO2) N 2 contacts signalling circuit-breaker closed (DC1, DC2) N 1 contact signalling circuit-breaker ready for the operation (capacitors charged and check of circuit-breaker state) (DR) N 1 contact signalling circuit-breaker not ready for the operation (DN, normally closed)

N 1 transient contact with momentary closing during the opening operation (DOR)

Remark: difference respect to ED2.0 control module basic version

ABB PT / 19

VM1
ED2.0 control module full option version (on request)
Binary inputs (logical inputs) for remote control: N 1 input for closing control (-SC2) N 1 input for opening control (-SO2) N 1input for additional opening control (-SO3) N 1 input for circuit-breaker opening on direct command from the protection release PR512 (-SO5) N 1 input for lock on closing control (the same function of the locking electromagnet in the mechanical actuator of the VD4 circuit-breaker) (-SL1)

N 1 input as undervoltage control for (-S04)


Remark: difference respect to ED2.0 control module basic version

ABB PT / 20

VM1
ED2.0 control module full option version (on request)
Functions:
Self-opening following determination of incorrect state of circuit-breaker Self-opening following load threshold of the capacitors lower than the minimum value required for the opening and closing operation Anti-pumping relay function Trip-free function Monitoring of capacitor load with feeder turning itself off in the case of exceeding the maximum load level Undervoltage function with selection of the reference rated voltage and with possibility of delaying the opening from 0 to 5 s (-SO4) Watchdog of the electronic power circuit with feeder turning itself off in the case of overtemperature and/or overcurrent Slow capacitor charging function (the power load passes from 100 watt to 40 watt, doubling the charging time) Monitoring continuity of the opening and closing coils Watchdog (DN) Additional safety opening command function
ABB PT / 21

Remark: difference respect to ED2.0 control module basic version

VM1
Accessories available (on request)
Signalling auxiliary contacts circuit-breaker open/closed
Fixed circuit-breaker (-BB1; -BB2; -BB3; -BB8):
Set of 5 make contacts plus 5 break contacts Set of 10 make contacts plus 10 break contacts (alternatively)

Withdrawable circuit-breaker (-BB1; -BB2)


Set of 5 break contacts plus 5 make contacts

Transmitted contacts of the withdrawable circuit-breaker installed in the truck (-BT1; -BT2)
These contacts are either in addition or as an alternative to the position contacts (for signalling circuit-breaker racked out) located in the unit; they also carry out the function of the position contact (-BT3)

Position contact of the withdrawable circuit-breaker (-BT3)


With binary input SL1 prevents remote CB closing during translation of the truck; it is supplied when the transmitted contacts -BT1; -BT2 are not required
ABB PT / 22

Motorised truck (-MT) (only for VM1 for UniGear panel)

VM1
Features of the control module ED2.0 (standard version)
The closing coil can only be activated when VM1 is open The opening coil can only be activated when VM1 is closed Closing is disabled when an opening command is active at the same time De-activation of the opening or closing coil takes place when the relative limit position has been reached WRONG POSITION (auto trip) function: if the final CLOSED (or OPEN) position is not reached within 70 ms during a closing (or opening) operation, an opening operation is immediately started to guarantee reaching a defined safe position in any case. Anti-pumping function ensures that only one closing-opening cycle is carried out when a closing command followed by an opening command is active; active closing command must be cancelled and reset for the next closing operation. Activation of the input for the closing command can be locked by means of an external locking signal. Input for the lock on closing command must be energised to be able to close the circuit-breaker (without power it inhibits closing).


ABB PT / 23

VM1
Features of the control module ED2.0 full version
Undervoltage function controls VM1 opening if the voltage applied drops below the limit of tolerance (established by the Standards) rated voltage value to be monitored is set in the factory in conformity with the order specifications but it can be changed by dip-switches to prevent UVR intervention, when the voltage drops below the specified level (e.g. in the case of motor starting), it is possible to set a trip time UVR function can be disabled Monitoring function of the actuator closing and opening coil; if a fault is detected, the luminous READY signal on front of the circuit-breaker turns off and the READY/NOT READY signalling contacts are activated. Additional safety opening command function; the second input of the control module for the opening function is designed so that an opening command is carried out directly even in the case of a fault in the microprocessor.

ABB PT / 24

VM1
Features of the capacitor
The energy stored is suitable for an O-C-O operating cycle without recharging The energy stored is constantly monitored by measuring the voltage of the capacitor READY indication signals:
application of the power supply voltage ready status of VM1 for the next operation

READY signal switched on means


(VM1 in the open position) energy sufficient for one C-O operating cycle (VM1 in the closed position) energy sufficient for one opening operation; energy available is sufficient for one opening operation within 60 s from interruption of the auxiliary power supply (up to 120 s with 2 capacitors)

ABB PT / 25

VM1
y

Lifetime t of aluminium electrolytic capacitors as a function of the ambient temperature T


ABB PT / 26

VM1
Characteristic data
Switching energy for CO VM1: VD4: 150 J 115 J

Capacitor voltage
Closing cycle VM1 without capacitor Making current

80 V
max. 100 J max. 2.3 kW for 54 ms max. 29 A for 44 ms max. 50 J max. 2.1 kW for 27 ms max. 27 A for 30 ms 35 ... 45 ms 10 ...15 ms 45 ... 60 ms 50 ... 60 ms

Breaking capacity with capacitor without capacitor


Breaking current Opening time Arcing time Total interruption time Closing time

ABB PT / 27