TESTING
TYPE TESTS ROUTINE TEST ACCEPTANCE TESTS SAMPLE TESTS SITE TESTS
TO BE DETACHED AFTER THE TRANSFORMER IS PLACED ON PLINTH AT SITE CHECK NITROGEN PRESSURE INSIDE THE TRANSFORMER AFTER RECEIPT AT SITE
IR MEASUREMENT
IR MEASUREMENT OF TRANSFORMER WITH 500V MEGGER CONTROL WIRING-1000M OHM TAP CHANGER
MOTOR-1000 M OHM CONTROL WIRING-1000M OHM
COOLING SYSTEM
MOTOR FAN- 10.4 G OHM MOTOR PUMP-8.6 G OHM CONTROL WIRING- 1000 M OHM
HV+IV TO LV
13.7
18.3
43.9
2.06
5.5
14.6
HV+IV TO E
LV TO E 15.4 19.9 45.7 4.41 8.55 22.7
1B1
1Y1
VECTOR GROUP
TERMINALS SITE RESULTS AT 415V FACTORY RESULTS AT 409V
1R1-1Y1
1Y1-1B1 1B1-1R1 3Y1-1B1 3Y1-1Y1 3R1-N 3Y1-N 1R1-N 2R1-N 2Y1-N 2B1-N
418V
414V 417V 411V 384V 239V 220V 239V 131V 131V 130V 236V 410V 384V
2R1-N=2Y1-N=2B1-N SHALL BE EQUAL 3R1-N GREATER THEN 3Y1-N & 3Y1-1B1 GREATER THEN 3Y1-1Y1, SO VECTOR GROUP Yn0d11 IS CONFIRMED
POLARITY TEST
POLARITY TEST IS DONE BY TRANSFORMER RATIO METER OF M/S ELTEL, TYPE TRM200 OR EQUIVALENT
WINDING RESISTANCE
TO BE MEASURED ON ALL TAPS DIRECT DIGITAL READING METERS MEASUREMENT AT 10A OR 25A NORMAL INDUCTIVE SUPPRESSED TAP VOLTAGE SITE RESULTS FACTORY
30 DEG C 1R1-2R1 1Y1-2Y1 1B1-2B1 2R1-N 2Y1-N 2B1-N 0.2231 0.2246 0.2231 0.2879 0.2886 0.2876 RESULTS 34 DEG C 0.2131 0.2153 0.2131 0.2854 0.2856 0.2857
1B1N=28V 106.9V
236V
128.0V
108.0V
1Y1-N 221.1V
236V
22.0V
220V
1R-N
238.5V
2R-N
130.4V
1Y-N
239.5V
2Y-N
131.4V
1B-N
240.2V
2B-N
131.1
N-EARTH
0.778
HV RATIO TEST
APPLY 3 PH ,4 WIRE,415V ON HV TERMINALS AND KEEP IV OPEN. IT SHALL BE MEASURED ON ALL TAPS. TO MEASURE BETWEEN HV/IV; HV/LV;IV/LV
VOLTAGE APPLIED IR-N 1Y-N 1B-N VOLTAGE MEASURED 2R-N 2Y-N 2B-N RATIO SITE/FACTORY SPECI FIED
231.5
IR-N 232.4
232.3
1Y-N 235.1
234
1B-N 234.4
128.9
3R-3Y 33.0
129.7
3Y-3B 33.1
130.2
3B-3R 33.1
1.796/ 1.797
1.804/ 1.796
1.797/ 1.795
1.796
7.042/ 7.011
7.103/ 7.005
7.082/ 7.011
6.998
OIL TESTING
SAMPLE TO BE TESTED AND SHALL CONFIRM TO IS 1866 BEFORE CHARGING
OIL BDV SAMPLE MIN. KV IS-1866 IS-1866 IS-1866 MAIN TANK 60 50 40 80KV MOISTU TAN RE DELTA PPM 15 20 25 9 90 DEG C 0.05 0.05 0.05 0.025 RESISTI VITY OHMCM 1X10 ^12 1X10 ^12 1X10 ^12 92.7 INTERF. REMAR TENSION KS DEG N/M 0.03 0.03 0.03 145KV ABOVE 145KV 72.5 KV 72.5KV BELOW TESTED 22.04.07
CORE 1
1S1-1S2
2.29 OHM
2.24 OHM
2.17 OHM
CORE 2
2S1-2S2
1.51 OHM
1.57 OHM
1.48 OHM
IR MEASUREMENT BUSHING CT IR MEASUREMENT WITH 500V MEGGER FOR HV, IV & LV & BETWEEN CORES OF BUSHINGS
BETWEEN HV G OHM, 39 DEG C R PH EARTH- CORE-1 12.7 Y PH 15.8 B PH 12.15
EARTH- CORE-2
16.8
17.3
14.8
EARTH- CORE-3
HV+IV TO E
15.4
19.9
45.7
CORE 1
1S1( + )-1S2( - )
OK
OK
OK
CORE 2
2S1( + )-2S2( - )
OK
OK
OK
CORE-1
80
800A
1000/1
993/1
0.7
CORE-2
80
480
0.805
600/1
594/1
0.6
1S1-1S2 R PH mA
10.2
1S1-1S2 Y PH mA
11.4
1S1-1S2 B PH mA
11.2
0.25X KVP
0.50X KVP
500V
17.4
13.6
16.0
0.75X KVP
750V
32.5
21.3
26.1
R
10KV ON HV 465
Y
467
B
464
R
465
Y
465
B
463
10KV ON IV
10KV ON LV
310
184
319
185
315
184
309
187
317
187
314
187
R 10KV ON HV 0.0040
Y 0.0039
B 0.0039
R 0.0033
Y 0.0036
B 0.0032
10KV ON IV
10KV ON LV
0.0021
0.0035
0.0023
0.0034
0.0021
0.0035
0.0018
0.0033
0.0019
0.0025
0.0020
0.0027
FACTORY
243
4.12
238
4.02
240
4.08
THIS DONE ON ALL WINDINGS HV, IV & LV AT DIFFERENT FREQUENCIES 10 TO 2000 HZ,100 TO 20000 HZ, AND 1000 TO 200000 HZ AND PLOTTED BETWEEN FREQUENCY AND DB
SITE TESTS ON CB
CHECK PRESSURE OF N2 210 BAR IN R,Y,B PH PUMP RUNNING TIME 4.5 MIN FOR R, Y, B PH TO ATTAIN 345 BAR PUMP START AT 325 BAR AUTO RECLOSE LOCKOUT AT 300 BAR GENERAL LOCKOUT AT 253 BAR SF6 DENSITY MONITOR- ALARM 7.1 BAR, BLOCK 6.1 BAR, NORMAL 8.4 BAR CHECKED SF6 LEAKAGE IN 24 HRS- NIL CHECKED THE ANTI PUMPING CONTACTOR
SITE TESTS ON CB
CHECK TRIPPING CIRCUIT OK CHECK CLOSING THROUGH CC-1 OK CHECK CLOSING THROUGH CC-2 OK ANTI PUMPING FEATURE- OK POLE DISCREPANCY FEATURE- OK BREAKER POSITION INDICATION- OK CHECK FOR ANNUNCIATION IN CONTROL ROOM
SITE TESTS ON CB
OIL PRESSURE DROP DURING OPERATION
R PH Y PH B PH
325
325
325
315
315
315
10 SEC
10 SEC
10 SEC
SITE TESTS ON CB
OPERATION TIME
R PH Y PH B P74H
BREAK I TRIP
27.2
29.3
29.7
BREAK 2 TRIP
CLOSE-I
27.3
29.1
29.7
78.6
74.2
74.9
CLOSE-2
78.6
74.7
76.9
SITE TESTS ON CB
COIL RESISTANCE MEASUREMENT IN OHM
R PH Y PH B PH
79.66
80.37
79.48
96.42
79.95
78.18
164.5
176.2
168.0
SITE TESTS ON CB
IR TESTING OF CONTROL CIRCUIT 500V MEGGAR IN M OHM
R PH Y PH B PH
34600
32200
23800
25200
16700
20400
15500
21800
20800
SITE TESTS ON CB
IR TESTING OF CB WITH 5000V MEGGAR IN M OHM
R PH WITH EARTH
INTERRUPTE 214000 R1 INTERRUPTE 505000 R2
Y PH WITH EARTH
234000
B PH WITH EARTH
115000
133000
115000
496.5
507.9
509.1
518.4
503.7
509.8
511
510.1
512.3
514.0
509.3
511.1
0.03484
0.0033
0.00245
0.00791
0.00935
0.00686
FACTOR Y
0.00133
0.00232
0.0011
0.00103
0.00072
0.00170
92.6
71.5
84.1
55.4
59.1
59.4
68.5
55.3
85.6
CORE5- 5S1-5S2
2.4
2.3
2.3
CORE5- 5S1-5S3
4.6
4.5
4.7
CORE5- 5S1-1S4
9.7
9.8
9.7
TAN DELTA
10KV 0.00185 0.00187 0.00185 0.0019 0.0019 0.0020
CORE 1 1S11S2 AT 80 %
799
801
807
CORE5- 5S1-5S2 AT 25%, 250V CORE5- 5S1-5S2 AT 50%, 500V CORE5- 5S1-5S2 AT 75%, 750V
6.6
7.4
9.5
9.8
10.6
14.1
13.8
14.6
20.2
NOT AVAILABLE
TAN DELTA
10KV 0.00311 0.00321 0.00294 NOT AVAILABLE
VOLTAGE RATIO TEST APPLY 230 V ON PRIMARY AND MEASURE THE VOLTAGE IN SECONDARY
SURGE ARRESTOR
IR TEST WITH 5KV MEGGER :MEASURE IR VALUES OF EACH STACK TEST LEAKAGE CURRENT METER. TEST COUNTER READING AND ITS WORKING BY INJECTING 500V. TOTAL LEAKAGE CURRENT = CAP CURRENT + RESISTIVE CURRENT. RESISTIVE CURRENT MEASURE WITH THIRD HARMONIC. IF THIS CURRENT EXCEED 500MA, THE SA TO BE REPLACED.
RELAY TESTING
INTERNAL PANEL WIRING CHECK EXTERNAL CABLES WIRING ,CONTINUITY TEST INDIVIDUAL RELAY TESTING AS PER RELAY SETTINGS, PRIMARY CURRENT INJECTION TESTING COMPLETE SCHEME TESTING