2007
Ross Kinzler
With MH industry since 1989 Chief lobbyist for the industry
Mike Zenner
Over 35 years of manufactured housing experience Wick Quality Control Currently Inspection Services AC inspections under the HUD Code UDC Construction and other creditials
Key to the Code Did you know? Commerce contacts Web links
Whats What
Home is covered by HUD Code which preempts state and local law New installation standards preempt local ordinances just like the UDC Pier installation standards are now a part of the UDC Watch out for places where codes interface Understanding the HUD Code
7
Inspectors may not be employees of home manufacturer, a salesperson involved in the sale or an installer involved with the particular home
8
Critical Websites
See page 6
Licensing
Trigger is installing a home on a foundation
10
Licensing
General supervision the installer does not need to be on the job site Homeowner is exempt from licensing but if people help and would otherwise need a license they must be licensed
11
Licensing of Installers
Qualifications 18 years old Not been found responsible in any court or agency hearing of a violation of the installation law during prior 2 years Not been found responsible in any court or agency hearing for failure to perform under installation contract or defrauding a person in the provision of installation services
12
13
Renewal
Renewal requires 12 hours of continuing education over the 4 year period Also must not have been found responsible for breaking the rule or defrauding a customer
14
15
Comm 21.40
Formerly Comm 27.18 Now a part of the UDC Applies to homes built before April 1, 2007
16
Comm 21.40
No footing on unprepared fill. All organic matter must be removed. Soil bearing test using pocket penetrometer Grade site to drain water away for minimum of 5 ft from home A footing for every pier, nominal 16 by 16 Consult others if soil is less than 2000 psi
17
A. one 4 by 16 by 16 solid blocks or two 4 by 8 by 16 solid blocks. B. 16 by 16 ABS pad rated at not less than 6000 lbs
C. 18 inch diameter hole bored below the frost line or to unfractured bedrock and filled with poured concrete D. Other materials or systems approved by Commerce
18
Concrete blocks, manufactured steel stands or manufactured concrete stands Single stack piers limited to 36 inches Single stack piers loads limited to 8,000 lbs 36 to 80 inch piers double blocked (layered in opposing layers) 80 inch or more double blocked laid in concrete mortar, cores filled with mortar and inch steel reinforcing rod
19
2 core design, construction grade 8x8x16 Cores placed with cores open vertically Block nearest main frame shall be perpendicular to the linear direction of frame No block may contact the frame
20
No more than 7 feet on center No more than 3 feet from exterior side of each end wall Can be varied to follow manufacturer tables Piers under clear-span openings of 4 feet or more in mating walls Piers must be plumb and centered under point of support
21
Solid concrete block or solid wood block having nominal thickness of at least 2 inches Cap must be same width and length as top of pier
No more than 2 pieces 2 piece caps positioned with joint perpendicular to frame if used
22
Where used, driven from opposing sides and be no less than 4 by 8 Wood caps and shims at least equal to #2 spruce pine fir with min bending stress rating of 1200 psi. All wood caps must be of same species of wood. All shims must be of same species of wood.
23
Combination of nominal 2 inch solid concrete block or wood cap plus shims must not exceed 3 inches Minimum clearance under home of 12 inches between lowest point of main frame in area of utility connections. Min clearance of 12 inches for 75% of home. Remainder may be less than 12 inches but cannot touch ground
24
25
The Standards
3280 HUD Construction Standards for the home 3285 HUD Model Installation Standards
26
27
28
Definitions
Words have meaning so read them carefully see 3285.5 A manufacturer must provide with each new home a DAPIA approved designs and instructions that are consistent with the standards 3285.2 DAPIA means Design Approval Primary Inspection Agency
29
Variations by Installer
If you vary support and anchorage from the manufacturers instructions, the installer must obtain site-specific instructions from the (1) manufacturer or (2) a registered professional engineer or (3) registered architect. 3285.2(b)
30
Temporary Storage
The manufacturers instructions must provide at least one method for temporarily supporting each section to prevent structural damage when those sections are sited at the plant, retailers lot or home site. 3285.2(c)
31
Reference publications
Some to remember ASTM American Society for Testing & Materials NFPA National Fire Protection Assn FEMA Federal Emergency Management Agency
32
Application
These standards apply to HUD Code manufactured Homes not modulars.
33
Fire Separation
Fire separation distances in accord with NFPA 501(a) must be maintained. Means 10 feet Fire separation distance must also comply with Comm 26 in a mobile home park (10 feet between basic structures) Local ordinances might have additional requirements
34
Flood Zones
Installer is responsible to determine if home is being installed in flood zone. 3285.102(c) If it is, special installation methods are required.
35
Zone Maps
3 maps in the HUD Code
Wind Wisconsin in Zone 1 Roof Load Wisconsin is South and Middle Zones Thermal Zone Wisconsin is Zone 3
U/O value must be less than 0.079 U/O is inverse of R value 0.079 = R 12.6
Homes may not be installed in a wind zone that exceeds the design load for the home.
36
Site Preparation
Soil Mechanics Soil tests can be conducted with a pocket penetrometer Footings must be sized and spaced according to soil bearing capacity Also see the tables in 3285.202 Poor soils peat, organic clays or uncompacted fill require a geologist, engineer or architects opinion
37
Site Drainage
Drainage must provided to direct surface water away from home and prevent build up under home. Minimum slope of inch per foot for the first 10 feet Where site is sloped, home must be protected from surface runoff
38
39
40
41
42
43
Foundations - Piers
Concrete blocks Must conform to ASTM standard C 90-02 Pressure treated wood think pilings Adjustable metal - Manufactured piers must be labeled or listed for loads and installed to the pier manufacturers instructions Listed means approved for use
44
Pier loads
Must be designed with load taken into consideration Spacing is dependant on factors such as soil bearing capacity and foot size
See tables at 3285.303 Pier spacing tables do not taken into consideration flood or seismic loads see an engineer or architect
45
Pier Configuration
Load bearing blocks not decorative Nominal 8 by 8 by 16 inches Stacked with hollow cores aligned vertically When stacked side by side, each layer at right angles to preceding one Center beam/mating line supports are always required for multi-section homes
46
47
48
49
Caps
Must evenly distribute loads across the capped hollow block piers May be made of solid concrete or masonry at least 4 inches nominal thickness OR hardwood lumber at least 2 inches thick OR corrosion protected min inch thick steel or other listed materials
50
51
Caps
Must be same length and width as piers Split caps on double stacked piers must be installed with long dimension across the joint in blocks below
52
Gaps
Must be filled with one of these methods Nominal 4 by 6 by 1 inch shims
a. b. c.
53
Manufactured Piers
Adjustable risers must not extend more than 2 inches when finally positioned
54
55
58
59
60
61
62
63
Piers over 67
Must be designed by registered professional engineer or registered architect Mortar not required unless specified
64
65
Mating line, marriage wall line, ridge beam all mean the point where sections join and they require support Be alert to extreme weight considerations in these locations!
66
67
68
Footings
Must be located on undisturbed soil or fill compacted to 90% of maximum relative density A footing for every pier
Footing size depends on the load bearing capacity of soil, footings and piers
3285.312
69
Footing Types
Concrete types
4 inch nominal pre-cast pads meeting ASTM C 90-02 with 28 day compressive strength of 1,200 psi 6-inch minimum poured in place concrete pads, slabs or ribbons with at least 28 day compressive strength of 3,000 psi
70
Footing Types
Pressure-treated wood
Minimum 2 layers of nominal 2 inch thick pressure treated wood Single layer of nominal inch pressure treated plywood with a max size of 16 by 16 (must be rated exposure 1 or exterior sheathing PS-1-95 rated Cut ends must be field treated
71
Footing Types
ABS footing pads
Installed according to pad manufacturer instructions and certified for use in soil classification at the site Must be listed for required load capacity
72
73
Frost Protection
Footings must be designed using methods and practices that prevent the effects of frost heave by:
1. 2.
Conventional below the frost line footing Monolithic slab above frost line must be designed by registered engineer or architect Insulated foundation system above frost line must be designed by registered engineer or architect
3.
75
76
77
Anchorage
After blocking and leveling, the manufactured home must be secured against the wind by an anchoring system Anchoring equipment means ties, straps, cables, turnbuckles, chains and other approved components including tensioning devices that are used to secure a manufactured home to anchor assemblies. Conventional anchors or alternative foundation system (Tie Down or Oliver Technologies type systems)
78
79
80
Anchorage
The anchors must be capable of meeting the loads the home was designed to withstand see data plate Follow the anchor companys instructions for spacing, angles, connections and so forth Install anchors to their FULL depth A diagonal anchor tie is intended to resist horizontal or shear forces, but may also resist vertical, uplift and overturning forces 3285.401
81
Ground Anchors
Must be listed (listed means approved) Steel coated with zinc to not less than 0.30 oz/ft2 of surface Capable to resist a min ultimate load of 4750 lb and a working load of 3150 lbs (check listing labels)
82
83
Tie Downs
Maximum spacing see the tables See drawings for near beam and second beam methods If sidewall or over the roof, mate-line or shear wall straps are installed, they must be connected Must be augured below the frost line unless the foundation is a frost protected above frost line system
84
85
86
On-site structures
Each expansion room or other on-site structure must be able to support its own weight including any garage unless pre-designed by manufacturer, engineer or architect Any addition must be designed by either the home manufacturer, a registered engineer or architect
87
88
Optional Equipment
Comfort systems (HVAC) must be installed by a licensed HVAC contractor if not factory installed Air conditioning equipment must be properly sized All heat producing equipment must be properly vented thru the skirting or exterior wall as appropriate When not installed by home manufacturer, must be installed according to the appliance manufacturers instructions
89
90
Skirting
Must be weather resistant
Attached so no water is trapped between siding and trim or forced up into the wall cavity trim it is attached to All wood skirting within 6 inches of the ground must be pressure treated or be naturally resistant to decay and termites This would include lumber and sheathing extension if any of the wood is less than 6 inches above the ground
91
92
93
94
95
Crawlspace Venting
NEW - One square foot for every 1,500 sq ft of floor area Important Check with your manufacturer before proceeding with reduced venting Vent openings as high as practicable Vents must located on at least two opposite sides of home Openings must be covered with a perforated corrosion and weather resistant covering to prevent rodent entry
96
97
Access Opening
Not less than 18 wide by 24 high and not less than 3 sq ft Must be located so that any utility connections under the home are accessible
3285.505
98
99
Must pass through skirting to the outside This includes fireplace air inlets
100
101
Water
When local water supply pressure exceeds 80 psi, a pressure reducing value must be installed An identified and accessible shutoff value must be installed underneath or adjacent to the home Crossovers and lines must be protected from freezing Only listed for MH heat tape is permitted Water system must be inspected and tested for leaks after completion at the site. Disconnect water heater if test is air only
102
Piping support
Water lines supported every 3 feet Drain lines supported every 4 feet See 48 inch on center max - 3280.608
103
Gas Supply
Home design calls for system pressure of 10 to 14 inches of water column pressure (0.036 psi)
104
Ductwork Crossovers
All ductwork connections must be sealed Galvanized metal straps or tape and mastics listed to UL 181 A or B must be used around duct collar and secured tightly Metal straps required metal sheet screws Metal ducts must be fastened with at least 3 galvanized sheet metal screws equally spaced around the collar
105
Ductwork
Max distance for duct supports is 4 feet
If straps are used they must be wider than spacing of spirals in flex duct Arrange so that straps cannot slip between spirals and to prevent kinking Cannot contact ground Listed for exterior use only Crossovers outside the envelop must be insulated with proper materials In-floor or ceiling crossover connections must be sealed to prevent air leakage
106
Subpart H - Electrical
Snap connections may or must be fastened to adjacent stud CHECK instructions If a fixture is mounted on a combustible surface a limited combustible or non-combustible ring must be installed Wires connected black to black, white to white and ground to ground Test all connections
107
Smoke Alarms
Additional shipped loose alarms for basement set models are typically provided by the manufacturer They may be wired to communicate with factory installed units at main floor
108
Exterior close-up
Manufacturers provide instructions for joining sections. Pay particular attention to directions on fasteners The mate-line gasket must be installed following manufacturer instructions Exterior close up strips are trim that must be fastened securely and sealed with an exterior sealant
109
110
111
Gaps
UPON COMPLETION no gaps are permitted between structural elements
PRIOR TO COMPLETION minor gaps not exceeding one inch are permitted PROVIDED they are filed upon completion Fill gaps must be shimmed with dimensional lumber and fastener lengths used to make connections must be increased to provide adequate penetration into receiving lumber. Pay particular attention to end wall and floor completion gaps May have marriage wall sheathing in from end wall ends
112
Close up
All shipping blocking, strapping or bracing must be removed from appliances, window and doors.
At a minimum, shipped loose wall panels must be installed using PVA adhesive on all framing members and fastened with 1 inch long staples or nails 6 inch on center panel edges and 12 inches on center in the field unless manufacturer directs other methods
113
Bottom Board
Bottom Board is an industry term for barrier installed by the factory on the bottom of the floor system. It is for rodent control. Inspect for loosing or areas damaged by transport or installation Tears must be repaired Any missing insulation must be replaced Splits or tears must be resealed with tape or patches P traps must be checked to be sure they are well insulated and covered All repaired edges must be taped or otherwise sealed
114
Access to site
The installer is responsible to ensure that transportation routing is possible and permits obtained Effective 4/01/07 disturbed soil areas of 1 acre or more at property site are subject to permits and UDC erosion control regulations
(This also includes entire driveway areas!)
115
Gas appliances
Make sure orifices match the fuel supply Inspect vents to make sure they were not damaged in transit
116
Habitable basements
117
Two Similar Right Triangles Maintain 6'-4" Headroom In Required 3' Long Landing Unit Rise Max. 8" Unit Run Min. 9"
Headroom + Floor/Ceiling Depth (HFCD) Unit Rise So to solve for FSL, FSL = Unit Run x HFCD Unit Rise
118
119
120
121
122
123
124
Comm. 21.02 (Structural Analysis Standards.) Structural analysis shall conform to the following nationally recognized standards.
( c ) Concrete. Plain, reinforced or pre-stressed concrete construction shall conform to the following standards: 1. ACI Standard 318, Building Code Requirements for Reinforced Concrete. 2. ACI Standard 318.1, Building Code Requirements for Structural Plain Concrete.
(2) Exceptions. (a) Floating slabs constructed on grade need not be installed below the minimum frost penetration line provided measures have been taken to prevent frost forces from damaging the structure.
Also, ( c ) Stoops or ramps need not be installed below the minimum frost penetration level provided measures are taken to prevent frost forces from damaging 125 the structure.
126