Step1: Install PMU and PSU, Connect AC input, disconnect battery, Disconnect Load1 and Load2, Put off Power switch of the battery; Measure the Voltage between BAT.(+) and BAT.(-), voltage between RTN(+) and Load1(-), Voltage between RTN(+) and Load2(-). All of the voltage should be about 53.5V.
Step2: Uninstall (take off, hot plug ) PMU;
Measure the Voltage between BAT.(+) and BAT.(-), it should be 0V;
Measure the Voltage between RTN(+) and Load1(-), it should be 53.5V.
Measure the Voltage between RTN(+) and Load2(-). it should be 53.5V.
HUAWEI TECHNOLOGIES CO., LTD.
Huawei Confidential
Page 1
Step3: Install PMU, Put on Power switch of the battery;
Use one cable to short circuit BAT.(-) and LOAD2(-), the voice of contactor be put on should be heard.
Step4: Remove the short circuit cable;
Measure the Voltage between BAT.(+) and BAT.(-), it should be 53.5V.
Step5: Uninstall (take off, hot plug ) PMU;
Measure the Voltage between BAT.(+) and BAT.(-), it should be 53.5V. If all results as same as the up-step, the EPS90 sub-rack is working normally.