Boiler Drum and Drum Level Control Boiler Drum Boiler Drum a standard feature of water tube boilers
Boiler Drum and Drum Level Control Boiler Drum Boiler Drum as an input output system Riser Water, steam, foam, sludge, floating impurities Steam outlet Steam, water droplet Feed water Water + chemical
Boiler Drum and Drum Level Control Boiler Drum Two unique features of drum type boilers Carry under entrainment of steam bubbles in the water stream of downcomer, reduces the circulation, increases the pressure drop in the down comer Carry over entrainment of water droplets in the steam leaving the boiler drum , dissolved solid gets deposited in super heater and other downstream components, creates the problem of over heating and failure. Carry over is a general term,
Priming is the sudden gust of liquid slugs in the steam flow due to rapid change in steaming rate, increase in liquid level, improper circulation etc. It not only makes the steam dirty but can also create problems like flow fluctuation, water hammer, thermal stress. Foamnig occurs due to the saponification in presence of oil, grease, floating impurities. It restricts the release of the bubbles as the liquid has a high surface tension. During bubble rapture droplets are formed which are also carried away by steam Apart from mechanical cleaning of steam chemical correction is also applied. Tri-sodium phosphate or tannin is injected to induce precipitation of the dissolved salts in the form of sludge.
Boiler Drum and Drum Level Control Boiler Drum Mechanism of carry over
Normal bubble
Boiler Drum and Drum Level Control Boiler Drum Operation done on steam in a steam drum: Separation, Washing and Drying
3. Low cost
Prof. P. K. Das; Dept. of Mechanical Engineering; IIT Kharagpur
12
Boiler Drum and Drum Level Control Boiler Drum Gravity separation assisted by internals like baffles and screens Baffles are the first level separator- Impact separations or separation due to change of momentum Screen (wiremesh) are secondary separators- intersects fine droplets
Baffles and screens
13
Boiler Drum and Drum Level Control Boiler Drum At high pressure density difference between water and screen diminishes Cyclone utilize centrifugal forces Scrubbers are corrugated platehelps to remove the last stresses of moisture Finally perforated plates or screens are used at the drum exit Cyclone and scrubbers
14
Steam washing impurities are removed Steam is made to pass through a rain of Relatively pure incoming feed water.
15
Boiler Drum and Drum Level Control Boiler Drum Typical external cyclone separator 1- Header; 2- Steam-water mixture in; 3- Whirler; 4- Perforated plate; 5- Steam outlet pipe; 6- Air vent; 7- Blow-down; 8- Downtake tubes; 9- Water from drum; 10- Cross-piece Sometimes steams of high purity is required Separation inside the steam drum is not adequate External separators are used
Prof. P. K. Das; Dept. of Mechanical Engineering; IIT Kharagpur
18
Guide lines to avoid carry over: Drum level to be within +/- 50 mm Maintain silica below recommended value for the pressure Drum internal alignment to be maintained FW to be 0.2 to 0.3 mho s/cm Boiler water solids to be in recommended level Measure & maintain steam purity within limits FW conductivity to be on line Boiler water salt control Dosing of solid salts to be after spray water tap off Turbine Deposits Guide: Soft & friable, pinkish white, 1st stage blades- easy to remove by air/water Sparkling silver, silver gray mainly in 4th and 5th stage bladesHard to remove by air/water.
Prof. P. K. Das; Dept. of Mechanical Engineering; IIT Kharagpur
19
Test Facility
Blow Down : Intentional drainage of water from the boiler drum to control the level of dissolved solid
Surface Blow down Removes dissolved solids, foam, floating impurities often continuous
Inadequate blow down - the problem of deposition Excessive blow down wastage of water, chemical and energy
Prof. P. K. Das; Dept. of Mechanical Engineering; IIT Kharagpur
23
Boiler Drum and Drum Level Control Boiler Drum Impurities in = impurities out
fw * ppm fw BD ppmdrum 1 x s ppmcarryover fw rate of feed water entering the drum kg S s rate of steam flow from the drum kg S x quality of steam leaving the drum
24
Drum Level Control : Steam supply for variable demands changes the water level in the boiler drum Drum level control is important for both plant protection and equipment safety Excessive low level uncover boiler tubes leads to overheating. It also affects the circulation Very high level interferes with the process of steam water separation, leads to loss of boiler efficiency, priming and carry over. Excessive carry over may lead to surge or even water hammer Unique phenomena like shrink and swell are also associated.
Desirable In case of a large change in the level, bring the drum up to the level at boiler start up and maintain the level at that condition
Prof. P. K. Das; Dept. of Mechanical Engineering; IIT Kharagpur
26
Boiler specifications: 367.7 kW(500 bhp), 7840.9 kg/h (17,250 PPH) Operating pressure 1.55 Mpa (225 PSIG) Boiler Water temperature 476K (397 F) Boiler is operated with 75% firing rate with 80% efficiency i.e. 5863.6 kg/h
(235 kg) + 2% over capacity(157 kg) = 5% water recovery capacity (392 kg) )
Feed water cycle = 392/5863 hr = 4.01 min Feed water is supplied at 355.2 K with 261.4 kg/min.
Prof. P. K. Das; Dept. of Mechanical Engineering; IIT Kharagpur
Resultant impact
Total feed water delivery time = 392/ 261.4=1.5 min, temperature rise= 120 K 1.Sub-cooling of water occurs due to mixing of drum water with feed water. 95% of water at 476 K + 5% of water at 355.2 K= 469.7 K of boiler water i.e. 6.3 K of sub-cooling
2.Steaming pressure falls from 1.55 Mpa (@ 476 K) to 1.34 Mpa (@ 469.7 K) i.e.
specific volume changes nozzle discharge velocity increases from 20.6 m/s to 23.5 m/s. 2.03 m/s is critical velocity for carry over. Priming most likely to occur.
Prof. P. K. Das; Dept. of Mechanical Engineering; IIT Kharagpur
steam
4.
To recover steaming pressure, firing rate should be increased by 1640.8 kWh i.e. 26.76% of total firing rate in 1.5 min. So boiler would have to fire 75 + 26.76 =101.76 % to recover Steaming Pr. decreases drum water level rises 1.77 to 2.54 cm wrong signal send to feed water controller shut the feed 1.77 cm early. Operating steaming pressure reached water level shrinks.
5.
6.
30
Conductivity probe for level measurement Possible actions: Start or stop a valve Open or close a valve Sound an alarm Open or close a relay
31
Boiler Drum and Drum Level Control Drum Level Control Capacitance method of level measurement
Boiler Drum and Drum Level Control Drum Level Control Float type level indicator
33
34
35
Desirable features of a good drum level control Operator adjustment of the set point for drum level Compensation for the shrink & swell effects Automatic control of drum level Manual control of the feed water valve Bump-less transfer between auto and manual modes Indication of correct drum level and steam flow Indication of feed water valve position and feed water flow Absolute/deviation alarms for drum level Additionally a good controller should take care of Blow down variations due to changes in dissolved solids Variations in feed water supply pressure Leaks in the steam circuits.
Prof. P. K. Das; Dept. of Mechanical Engineering; IIT Kharagpur
36
Options for drum level control Manual control Single element control Two element control Three element control
Only one analogue input and one analogue output required Suitable for single boiler / single feed pump configurations Suitable for stable loads since there is no relationship between drum level and steam- or feed water flow Possible inadequate control option because of the swell effect
Prof. P. K. Das; Dept. of Mechanical Engineering; IIT Kharagpur
37
Increase of demand decreases steam pressure Gives rise to expansion of bubbles and drum level swell Feed water flow rate decreases while an increase of flow rate is needed to maintain mass balance Sudden or large load changes gives rise to phasing of shrink and swell Water level controller looses control Nuisance of low water trips or water priming and carry over
38
Boiler Drum and Drum Level Control Drum Level Control Suitable for moderate load swing Any size of boiler Uses steam flow and drum level As steam flow is very dynamic load change can be sensed before any change of drum level Steam flow is a large variable can over ride the trim effect of the drum level change
39
Can not adjust pressure or load disturbance of the feed water flow
Can not eliminate the phasing interaction between the feed water flow and drum level as only a slow process of drum level is controlled The second issue can lead to a high subcooling of the drum water on a large increase of steam demand due to excessive feed water entry
41
42