Product Selector

Marketing Team Stafford Centre of Excellence


09/08/2010

GRID

Index

* Click on the product range for navigation

Feeder Protection
Voltage & Frequency Protection

P3 P4 P5 P6 P7 P8 P9 P10

Busbar Protection
Line Terminal IEDs Autoreclose and Back-up for EHV/HV

P11
P12

Motor Protection Generator Protection Distance Protection


Line & Cable Differential Protection Phase Comparison Line Protection

Phasor Measurement Solutions

P13
P14 P15

Accessory & Auxiliary Devices Measurement Centres

Transducers
Disturbance Recorders

P16
P17

Transformer Protection

Product selector - 08.2010 - P 2


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Feeder Protection
Selector
START
With voltage vector Shift & dynamic line rating ?

Yes No

P341
Distributed Generation Interconnection Feeder Protection

One box solution With mimic diagram ?

Yes No

C264P
Feeder relay with Integrated bay control

8 binary inputs +8 relay contacts Sufficient ?

No

Autoreclose required?

Yes

P145
Yes No
Function keys for control & test operations Required?

Yes No

Feeder Management Relay with autoreclose, Check synchronism & Function keys

P141
Feeder management relay

Check Synchronism Required?

P142
Feeder management Relay with autoreclose
Product selector - 08.2010 - P 3
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

P143
No

Yes

Feeder management Relay with autoreclose & check synchronism

Voltage & Frequency Protection


START

Selector
With IEC 61850 Protocol?
No Yes
16 binary inputs +14 relay contacts Sufficient ?

Yes

P941
Voltage & Frequency Management relay

No

P943
Voltage & Frequency Management relay

No

Function keys for control & test operations required?

Yes

P145
Feeder management relay With auto-reclose, check synchronism & function keys

8 binary inputs +8 relay contacts Sufficient?

No Yes

Sum total of binary I/O points required greater than 23?

Yes

P143
Feeder management relay With auto-reclose & Check synchronism

P141
Feeder Management relay

No

P142
Feeder management relay With auto reclose

Product selector - 08.2010 - P 4


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Motor Protection
Selector
START
Is motor rated power 3 MW ?

P241
Yes
Motor Management relay

P242
Motor Management relay

No (> 3MW)

With differential Protection?

No

Yes

P243
Motor Management Relay with Differential Product selector - 08.2010 - P 5
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Generator Protection
Selector
START
Small generators (<1MVA) With underimpedance, loss of field Protection?

P342 Yes No P341 P141 Yes P343

Yes

No
Medium size generators (1-10MVA) or back-up protection for large generators

Yes

With differential?

Yes

100% stator earth fault, pole slipping dead machine?

P346 No No No
Economy model

P342 Yes
With differential & 2x neutral voltage inputs for earth fault and interturn protection?

Large Generators (>10MVA)

Yes

With 100% stator earth fault via low frequency injection?

P345 Yes

No
With 100% stator earth fault, pole slipping, dead machine ?

P344

Yes

No

P346
(With differential & 1 neutral voltage input for earth fault)

No
Product selector - 08.2010 - P 6
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Distance Protection
START

Selector
Typical Characteristic Preference?

Quad

Mho

Sub-cycle Distance required?

No

Sub-cycle Distance Required?

Yes

Yes Yes Yes


Dual Circuit Breaker Feeding Arrangement? Single-Pole Tripping required?

No
Single-Pole Tripping required?

No

Yes

P446
Sub-cycle dual CB quad/Mho distance Relay with single-pole autoreclose

No

No
8 Opto-inputs & 14 output contacts Sufficient?

P445 P443
Economy distance for Subtransmission & Distribution

No

16 Opto-inputs & 21 output contacts Sufficient?

No Yes Yes

Sub-cycle quad/mho Distance relay with Single-pole A/R

P441
Full-Scheme quad. Distance for 3 Pole Tripping Product selector - 08.2010 - P 7

P442
Full-scheme quad. Distance relay with Single pole Recloser

P444
Distance relay with Single pole A/R and Extended I/O

ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Line and Cable Differential Protection


Selector
START Yes
More than 16 digital inputs and 14 output contacts? Dual CB configuration?

Yes

No

No Yes
Compatible with SDH/SONET networks?

P544
Dual CB Differential with Optional Distance

P545
Differential / Distance With Extended Binary I/O

P546
Dual CB Diff. / Distance With Extended Binary I/O

No Yes

Yes
More than 16 digital inputs and 24 output contacts?

P541
Economy Model

With IEC61850 and Function Keys?

No
With Auto Reclose?

No

No Yes

P543
Differential with Optional Distance

No
Yes

With Voltage Inputs, Optional Distance Protection?

P542
Product selector - 08.2010 - P 8
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Phase Comparison Line Protection


Selector
START
Application Requires Distance Protection?

Yes

No Yes
With IEC61850?

P547
No Yes
Advanced Model Phase Comparison with Distance in 80TE case

With Function Keys?

No

P547
Phase Comparison with 8 binary inputs & 8 relay contacts in 40TE case Product selector - 08.2010 - P 9

No
More than 8 digital inputs and 8 output contacts?

Yes

ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Transformer Protection
START
Is any winding Supplied by more than 1 Circuit Breaker?

Selector

2 winding
Type of Transformer?

3 winding

Yes

Is any winding Supplied by more than 1 Circuit Breaker?

Yes

No
3 phase Voltages required for measurement, protection, Directionalising, records?

No
P642 No
Transformer Protect. For 2-End Schemes With or without Tertiary winding?

Auto Transformer

P643

P645

Yes

With

P643
Without One
Dual Breaker feeding One or both sides of transformer? Is any winding Supplied by more than 1 Circuit Breaker?

Yes

P645
Transformer Protect. For up to 5 Ends

Both

No
P643
Transformer Protect. For up to 3 Ends

P645
Product selector - 08.2010 - P 10

ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Busbar Protection
Low impedance (Biased)
START

Selector

Technology Preference?

High impedance

How many Discrete protection Zones?

3 or more

Economy Distribution Scheme

P145
Numerical Relay(s) Required?

Yes

Feeder Management Relay Used in High Impedance mode with Varistor

1 or 2

P14*
Feeder Management Relays Used in Interlock (Blocking) Scheme

No
Current Pickup
Preferred Operating principle

Number of feeder, Coupler, and section breakers

MCAG34
High Impedance, Current Calibrated ElectroMechanical Relay

Up to 18

More than 18

Voltage Pickup

P746
Busbar Differential for Small Schemes

P74* Scheme
P741 Central Unit P742 Peripheral Unit P743 Peripheral Unit

MFAC34
High Impedance, Voltage Calibrated ElectroMechanical Relay

Product selector - 08.2010 - P 11


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Line Terminal IEDs Autoreclose and Back-up for Selector EHV/HV


START
UK Mesh Corner Application ?

Yes

P842
Mesh corner Autoreclose Scheme for Three Pole Tripping

No No Yes

Dual Circuit Breaker Configuration ?

16 opto-inputs and 14 output contacts sufficient?

No

Yes

P841 model A
Single CB control, reclose, Check synchronising and back-up protection

P841 model B
Model for dual breaker, ring bus, and breaker and a half feeding

Product selector - 08.2010 - P 12


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Phasor Measurement Solutions


Selector

START
GPS Time Synch.
Required Component

PMU

Phasor Data Concentrator

P594
GPS Synchronising Unit

S800 sPDC
ALSTOM Phasor Data Concentrator

P847
Phasor Measurement Unit

Product selector - 08.2010 - P 13


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Accessory & Auxiliary Devices


Test Block START
Device Required?

Selector

Hinged Armature Relay

Automatic CT Shorting Required?

Trip Relay Required?

Yes

MVAJ

No

Yes

No
Trip Circuit Supervision Device?

Yes

MVAX

MMLG

P991

No Current

Operating Principle Required

MCAA

Voltage

PRiMA
Plug-in Auxiliary Relays and Timers Product selector - 08.2010 - P 14

Plug-in

Device Form Factor

4U Rack

MVAA

ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Measurement Centres
START
Class 1/0.5% or Class 0.5s/0.2% accuracy ?

Selector
0.5%
Do you require communications ?

Yes No

M232
0.5% Communicating Measurement Centre

0.2%

M212 M233
0.2% Communicating Measurement Centre

No
Data Recorder Required?

0.5% Non-Communicating Measurement Centre

Yes
Power Quality Recorder?

Yes

M253
0.2% Power Quality Analyser

No

M243
0.2% Communicating Measurement Centre with Data Logger Product selector - 08.2010 - P 15
ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Transducers
START
0.5% or 0.2% accuracy ?

Selector

0.5%

Mean or RMS Measurements ?

Mean RMS

I400
I4CA Current or I4VA Voltage

0.2%

I500 I5MS
0.2% single phase transducer Single or Multi function ?

Multi

I400
I4M* range

Single
Single Phase or Three Phase?

Data Recorder?

No Single

I400
Class 1 Non-Communicating Transducers

Three

I500 I5MT
0.2% 3 Phase transducer

Power Quality Recorder?

Yes

I500 I5MQ
0.2% Power Quality Analyser Select by Measurement required

I500 I5MR
0.2% 3 Phase Transducer with Data Logger

Three

Single Phase or Three Phase?

Single

I500 I5ML
0.2% single phase Transducer with Data Logger

Product selector - 08.2010 - P 16


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

Disturbance Recorders
Selector
START
Number of Feeders ?

Two

More than 4 digital inputs?

Yes

M872
Dual Line / Dual Bus Monitoring & Recording IED

No One

M572
Dual Line / Dual Bus Monitoring & Recording IED

More than 4 digital inputs?

Yes

M871
Single Line / Dual Bus Monitoring & Recording IED

No

M571
Single Line / Dual Bus Monitoring & Recording IED

Product selector - 08.2010 - P 17


ALSTOM 2010. All rights reserved. Information contained in this document is provided without liability for information purposes only and is subject to change without notice. No representation or warranty is given or to be implied as to the completeness of information or fitness for any particular purpose. Reproduction, use or disclosure to third parties, without express written authority, is strictly prohibited.

www.alstom.com