Sei sulla pagina 1di 79

August

What is Protection System ?


Def: A COMPLETE ARRANGEMENT OF PROTECTION EQUIPMENT AND OTHER DEVICES REQUIRED TO ACHIEVE A SPECIFIED FUNCTION BASED ON A PROTECTION PRINCIPLE. Need: WHEN EQUIPMENT FAILS, THE ENERGY IS RELEASED AND EVERY COMPONENT IN THE SYSTEM IS AT RISK. THE PROTECTIVE RELAYING SYSTEM MONITORS THE SYSTEM AND INITIATE ACTION ACCORDINGLY.

Purpose of Protection System:


The protective relaying system senses the abnormal condition of power system and gives an alarm or isolates the defective system from the healthy system. A fault in an electrical system is defined as a defect in its electrical circuit due to which the current is diverted from the intended path. Faults are generally caused by breaking of conductors or failure of insulation. Some other causes of fault conditions include: Mechanical failure Environment disturbances Excessive internal & external stresses Operating error Equipment malfunctions The fault impedance being low, the fault current are relatively very high and flows towards the fault.
3

Requirements of Protection system:


Selectivity - ability to select the faulty part of in system & disconnect the faulty part without disturbing rest of the healthy system. Speed of Operation The faulty section should be isolated as fast as possible to minimize the damage to equipments and increase the stability of operation of healthy system. Sensitivity - ability to operate with low value of actuating quantities. Reliability - ability to operate under the faulty conditions only.

Types of Protective equipment


FUSES
MINIATURE CIRCUIT BREAKERS (MCB) PROTECTIVE RELAYS

FUSES
A Fuse is a short piece of metal, inserted in the circuit, which melts when excessive current flows through the circuit and thus breaks the faulty circuit. The fuse element is generally made of material having low of low melting point, high conductivity and least deterioration due to oxidation, e.g. silver, copper etc. it is inserted in series in the circuit to be protected.

Classification of Fuses:
i.
Low-voltage fuses Semi-enclosed rewirable fuse High rupturing capacity (HRC) cartridge fuse HRC fuse with tripping device

ii. High-voltage fuses Cartridge type Liquid type Metal clad fuses
7

Miniature Circuit Breakers (MCBs)


MCBs is a type of switch with thermal contacts. It can open or close a circuit under all conditions viz. no load, full load or fault conditions. It can be operated manually under normal conditions and automatically under fault conditions.

Protection Relay
A protection relay is a device that detects the fault and initiates the operation of the circuit breaker to isolate the defective system from the rest of the healthy system. The relay detects the abnormal condition by constantly measuring the electrical quantities e.g. voltage, current, frequency, phase angle, status of circuit breakers , etc. In changes of one or more quantities, the relay senses the faults, its type and location of the fault.

10

Essential Requirements of Protective System:1. Current Transformers or CT :CT,s are required to scale down the primery current to suitable level so that relay can use it. CT,s can be single core or multi core. Each core can be single ratio or multi-ratio. Separate cores are needed for metering or protection purposes. Normally secondary current is 1A or 5A as per requirement.
11

2. Potential Transformers or Voltage Transformers or PT/ VT,s :PT,s are needed to scale down the Primery voltage to suitable level so that it is useful for the relay. Normally secondary voltage is 110 V or 110/3 Volts as per requirement. PTs or VT,s are of single or three phase system.

12

3-Auxiliary AC or DC Supply:Reliable and steady auxiliary supply is needed so that in all adverse operating conditions, it is available to the protective system to detect the faulty condition, and the relay could isolate the faulty system from the healthy system with the aid of circuit breakers. Normally DC with battery chargers are used as reliable and steady auxiliary supply system. Normally 12 V, 24 V, 48 V, 110 V or 220 V DC auxiliary supply system are used.

13

4. Circuit Breakers:
Circuit breakers or CB,s are very much needed to operate the electrical circuits in all the operating conditions i.e. on no-Load, on Full-load. CB are also required to isolate the faulty system from healthy system on receipt of command from the protective system in the shortest possible time. CB status is also available to the protective system to properly take the decision of the fault.

14

5.Precautions while developing/ studying schematics:

- All the schematics are made without

any ac/dc supplies, - All the pressure switches are in zero pressure state, - All relays are in non-operating state and their contacts are in normal state, - No current/ voltage from CT/ PT is available.
15

Various types of Relays according to principle of operation are as follows:


1)
i. ii. iii.

Electromagnetic Attraction Relay


Attracted armature type Solenoid type Balanced beam type

The relay operates by virtue of a plunger being attracted into a solenoid or an armature being attracted towards the pole of an electromagnet which in turn operates the associated contacts bank. These types of relays may be operated by dc or ac quantities like as voltage, current etc. Normally this type of relays are used for supply status, CB status, Contact multiplication etc. 16

2) Electromagnetic Induction Relay


These relays operate on the principle of Induction motor and are widely used for protective relaying purposes involving a.c. quantities. An Induction relay essentially consists of a pivoted aluminium disc placed in two alternating magnetic fields of same frequency but displaced in time and space. The torque is produced in the disc by the interaction of one of the magnetic fields with the currents induced in the disc by the other. In order to obtain the phase difference in the flux and hence the operating torque, following three types of structures are used: a) Shaded-pole structure b) Watt-hour meter structure c) Induction cup structure.
17

Electromagnetic Induction Relay

18

STATIC RELAY
In Static Relays, the measurement is performed by electronic/magnetic/optical or other components without mechanical motion. Static relays have versatile characteristics, offer low burden and incorporate several protective/control/monitoring functions in one compact unit.

19

MICROPROCESSOR based Numerical Relays:


In 1980s, programmable static relays incorporating Microprocessor have been introduced. A programmable protection & control system has a Microprocessor or Microcomputer in its circuit. With the help of the logic and the Microprocessor, the integrated system can perform several functions of Data acquisition, Data processing, Data transmission, protection & control. Earlier for each of these functions, separate Electromagnetic or Static units were used along with complex inter module wiring.
20

Block Diagram of a simple Microprocessor based Digital Static Relay

CT

CB

VT Input Unit Input Unit A/D Converter

Trip coil

MICROPROCESSOR

Setting

Data Request & Display


Data Logger
21

Relay Based on actuating parameters


-Over-current Relays, -Under/ Over voltage relays, -Over/ under frequency relays, -Power directional relays, -Over-fluxing relays etc.

22

Relays based on Operating Characteristics:-Instantaneous Relays, -Definite time delay relays, -Inverse definite minimum time delay relays (IDMT), -Voltage restraint over current relay,

23

Relays based on their uses:


1-Differential Protection Relay 2.Restricted E/F Relay, 3.Distance Protection Relay, 4. Negative Phase Sequence Relay, 5. Neutral Over-current Relay, 6. Neutral Voltage Displacement Relay, 7. Over Fluxing Relay,
24

8. Over/ under voltage Relay, 9. Over-current Relay, 10. Bus-bar Protection Relay, 11. Breaker Failure Relay, 12.Direction O/C & Directional E/F Relays 13.Over/ Under Frequency Relay,

25

Other type devices used as Relays:

Oil Temperature Relays, Winding Temperature Relays, Oil surge Relays (OSR), Buchholtz Gas Relay, Pressure Relief valves (PRV), Pressure Switches, Level Gauges, Flow meters, etc
26

27

The Protection scheme of Vishnuprayag Hydro Power Project(4x100MW) is


classified as :

Generator Protection Generator Transformer Protection Bus-bar Protection Bus Coupler protection Transmission Line Protection Shunt Reactor protection
28

Generator/ Unit Protections


Relay : Model-REG216, Make-ABB Main-I (GRP-1) Protection comprising :
Generator Differential ii. Under Impedance iii. Negative Phase Sequence iv. Gen. Over Current (Inst. & IDMT type) v. 100% Stator Earth Fault vi. Reverse Power vii. Over Voltage viii. Loss of Excitation ix. Balance Voltage x. Gen. Thermal Protection
i.
29

Main-II (GRP-2) Protection comprising :


Gen.-transformer Over all Differential ii. 95% Stator Earth Fault iii. Under Frequency iv. Over Frequency v. Under Voltage vi. Over Flux vii. UAT Restricted Earth Fault viii. UAT Over Current ix. UAT Earth fault
i.
30

Single Line Diagram of Protection scheme of Generator Unit

31

Single Line Diagram of Protection scheme of Generator Unit

32

Trip Logic of Protection scheme of GRP-1 (Main-I)

33

LED Indications provided on GRP-1 (Main-I)

34

Details of LED Indications provided on GRP-1 (Main-I)

35

Trip Logic of Protection scheme of GRP-2 (Main-II)

36

LED Indications provided on GRP-2 (Main-II)

37

Details of LED Indications provided on GRP-2 (Main-II)

38

Unit Protection Settings Main-1 Settings ( GRP-1 Panel )


Sl.No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 Protection Over Voltage Stage-1 (59) Over Voltage Stage-2 (59) Under Voltage (27) Balance Voltage-1 (60) Balance Voltage-2 (60) Inst. Over current (50) LED No. 06 23 07 05 28 21 22 31 30 04 26 25 32 29 24 18 17 Function Alarm ESD Alarm Alarm PSD ESD Curve/Setting 1.15 Un 1.25 Un 0.70 Un 0.20 Un 0.20 Un 1.60 Un Time Delay 2.00 sec Inst. 2.00 sec 0.04 sec 1.00 sec 0.50 sec

Time Delayed Over Current (51) UAT E/f Protn. (51)


UAT O/C Protn (Inverse time) (51)

ESD PSD
PSD

1.30 In 5.00 In
IB =0.50 In, k=0.05

2.00 sec 0.02 sec


IDMT

Definite Time NPS-1 (46)


Inverse Time NPS-2 (46) Reverse Power (32) Loss of Excitation (40) GT Restricted E/F Protn. (51 N) 100% Stator E/F(64 S) Under Impedance (21) Gen Differential (87 G)

PSD
PSD PSD ESD ESD ESD ESD ESD

I2 =0.05 In
IB =0.78 In -0.05 PN XA = -1.11 Un/In XB = -0.18 Un/In IB =0.10 In T/f ratio-50 REs-0.91k 0.176 Un/ In g setting = 0.10 In v setting = 0.25

5.00 sec
IDMT 3 sec 0.2 sec As per curve 1 sec 3 sec Inst.

39

Unit Protection Settings

Main-2 Settings : ( GRP-2 Panel )


Sl.No . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Protection LED No. 03 17 04 20 07 23 06 22 05 21 26 27 18 24 25 Function Curve/Setting Time Delay

Over Voltage Stage-1 (59) Over Voltage Stage-2 (59) Under Voltage Stage-1 (27) Under Voltage Stage-2 (27) Over Frequency Stage-1 (81) Over Frequency Stage-2 (81) Under Frequency Stage-1 (81) Under Frequency Stage-2 (81) Over Fluxing Stage-1 (24) Over Fluxing Stage-2 (24) UAT Restricted E/F Protn. (51 N) GT/F Time Delayed O/C (51) Gen. Trans. Neu. O/C (51 N) 95% Stator E/F(59/27) Overall Differential (87 T)

Alarm ESD Alarm ESD Alarm PSD Alarm PSD Alarm PSD PSD ESD PSD ESD ESD

1.15 Un 1.25 Un 0.85 Un 0.80 Un 52.0 Hz 52.5 Hz 48.5 Hz 47.0 Hz 1.15 Un/fn 1.1 UB/fn IB =0.4 In, k=0.01 1.3 In IB =0.30 In 0.05 Un g setting = 0.20 In v setting = 0.5

2.00 sec 0.00 sec 10.0 sec 3.20 sec 1.00 sec 1.00 sec 1.00 sec 2.00 sec 2.00 sec 0.05 min As per curve 3.00 sec As per curve 0.05 sec Inst.

40

Generator Transformer Protection :


Differential Protection ii. Back-up Over Current iii. Neutral Over Current iv. Restricted Earth Fault v. Winding Temperature High vi. Oil Temperature High vii. Buchholz Gas Relay viii. Pressure Relief Valve
i.

41

Bus-Bar Protection & Breaker failure Protection :


Relay : Model-REB500, Make-ABB

-Bus bar protection is provided so that in case of fault on any of the bus-bar, the faulty bus will be isolated and other bus will continue to function without any interruption. - Breaker failure protection is provided to isolate the faulty breaker from the system, in case CB fail to isolate the fault.
42

The Central unit & Bay relay comprising of :


i.

Bus bar Differential protection,

ii. Breaker Failure Protection (LBB)

43

Single Line Diagram of Protection scheme of Bus Bar

44

45

Bus-Coupler Protection
Relay : Model-SPAJ140C, Make-ABB
Provided to trip the buscoupler CB in case of over-loading of bus-coupler or fault on any of the bus-bar
i . Over Current Protection,
ii. Earth Fault Protection

46

Single Line Diagram of Protection scheme of Bus Coupler

47

Trip Logic of Protection scheme of Bus Coupler

48

Transmission Line Protections


Main-I (Relay-REL521), Main-II (Relay-REL316) & Back-up (Relay-REX521) protection comprises of following functions :
i. ii. iii. iv. v. vi.

Under Impedance Over Voltage Back-up Over Current Back-up Earth fault Breaker Failure protection Auto-Reclosure Scheme

49

Single Line Diagram of Protection scheme of Transmission Lines

50

Trip Logic of Protection scheme of Transmission Lines

51

Setting Criterion of Line Protection:


1. Zone-1: 80% of Principal Line Section;
2. Zone-2: 100% of Principal Line Section + 50% of the Adjoining Shortest Line (check that Zone-2 > 120% of Principal Line Section

52

3. Zone-3: 1.2 x (100% of Principal Line Section + 100% of the Adjoining longest Line )
4. Zone-4 : 1.2 x (100% of Principal Line Section + Single T/F of remote end ) 5. Reverse Zone: 25% of Zone-1

53

Shunt Reactor Protection


Relay : Model-REG316, Make-ABB
Differential Protection ii. Restricted Earth Fault iii. Back-up Impedance Protection, iv. Winding Temperature High v. Oil Temperature High vi. Buchholz Gas Relay protection vii. Pressure Relief Valve
i.

54

Some Additional Features/ Schemes Used in Protective Circuits:


1.Trip Circuit Supervision Scheme: It is used to continuously monitor the tripping circuit & trip coil of circuit breakers, 2.Trip Coil supervision Scheme: It is used to continuously monitor the trip coil of the tripping relays,
55

3.Pole discrepancy scheme : In single pole circuit breakers, If due to any reason, one or two poles of the CB trips, the remaining pole trips after a short time delay. Normally it is of the order of 0.8 to 1.0 sec. It may be with CB schematic or outside. 4. Auto-reclosing Scheme: On tripping of Line CB on Temporary line fault, the scheme provides auto Reclosure of Line CB after a pre-set short time delay.
56

The scheme may be single phase autoreclosing or three phase auto-reclosing or both. Normally single phase auto-reclosing scheme are employed. Three phase auto-reclosing scheme are best suited for radial lines.

57

5. Carrier Inter-tripping Schemes :Normally 80% of Principal Line Section is covered by Zone-1 of the Line protection, the rest of the 20% is covered by Zone-2 protection with a minimum delay of 0.4 sec. To cover end 20% line fault in Zone-1 time also, Various carrier based carrier inter-tripping schemes are used:58

A. Permissive Under-reach carrier inter tripping Scheme, B. Permissive Over-reach carrier inter tripping Scheme, C. Carrier Blocking Scheme, D. Carrier Acceleration Scheme

59

Testing of Protective Relays schemes & Associated Equipments.

60

Testing of Current Transformers :


- Insulation Test 1. Primary winding to Earth by 5kV megger 2. Secondary winding to Earth (For each core) by 250V or 500 V megger, 3. Primary winding to all the secondary winding by 5kV megger, 4. Core to core of secondary windings by 250V or 500 V megger,
61

- Ratio Test of each core by Primary injection, - Polarity Test of cores, - Magnetizing Characteristics or knee point voltage test for identifying metering/ Protection cores

62

Testing of Potential Transformers:


- Insulation Test 1. Primary winding to Earth by 5kV megger after isolating from earth 2. Secondary winding to Earth (For each core) by 250V or 500 V megger, 3. Primary winding to all the secondary winding by 5kV megger, 4. Core to core of secondary windings by 250V or 500 V megger,
63

- Ratio Test of each core by injecting voltage on Primary terminal and measuring voltages on secondary cores, - Polarity Test of cores with reference to Primary Terminal,

64

Primary Injection of CT,s:


- Primary injection of current transformers is carried out with the help of Primary Injection Test Kits. The current is measured in all the current circuits of all the phases one by one to ensure that during actual operation current will flow only in the correct phase and not otherwise,
65

- During Primary injection we have to ensure that the current in metering circuit is flowing from the metering core only and current in protection circuit is flowing from the protection core only otherwise the protection is likely fail during fault conditions.

66

Secondary Injection Of PT,s:


- Injection of Potential circuit is carried out with the help of Secondary Injection Test Kits or with the help of Single phase variac, Rheostat etc. The voltage is measured in all voltage circuits of all the phases one by one to ensure that during actual operation voltage will flow in the correct phase only and not otherwise,
67

Checking of DC Schemes:
-The wiring of complete scheme is checked and corrected according to scheme. - Auxiliary DC supply is given to the panel and DC supply is checked at various points in the scheme/ Relays - The operation of DC relays checked as per schematics.
68

Testing Of Relays:
-All the relays are tested for operation on various settings with the help of Secondary Relay Testing Kit Like as Doble, Omricon, TURH, ZFB etc. -The operating time of the relays is also measured to ensure the operation of relays within permissible limits.
69

Power System Simulator (DOBLE Test Kit)

70

Power System Simulator (DOBLE Test Kit)

71

72

Closing/ Opening operation of Circuit Breakers:


-Closing/ Opening operation of Circuit Breaker is checked from Control/Relay Panels - Tripping of Circuit Breaker is checked by operation of Protective Scheme with the aid of secondary injection test Kit.

73

Checking of Alarm & Indications:


- All the alarms & Indications are
actuated one by one and their operation is checked/ ensured on the panels.

Checking of Stability of Relays : - Check for the stability of Differential

Relays, Restricted Earth Fault Relays, Bus-bar protection Relays etc.


74

On load checking the system:


After the system is energized, the following checks are required to be carried out :- Checking of DC auxiliary supply at various points in the panels, - Checking of CT/ PT supplies to relays, meters etc., - Checking of healthiness of relays - Checking of proper operation of voltmeter/ Ampere meter in all the phases 75

- Operation of MW meter, PF meter,

Energy meter etc and their running in proper direction, - Trip circuit supervision in healthy state, - Relays are measuring correct voltage & currents as per load condition.

76

Testing Of Transformers
Following Tests are performed to Check the healthiness of Transformers:1.Insulation Resistance- HV-E, LV-E, HVLV by 5KV/ 10KV Megger. 2. Turn ratio Test 3. Open circuit Test from HV & LV side, 4. Short Circuit Test from HV to LV, 5. Magnetic Balance Test from Star side 6. Checking proper operation of OLTC.
77

Testing Of Reactors:
Following Tests are performed to Check the healthiness of Reactors:1. Insulation Resistance- HV-E by 5KV/ 10KV Megger. 2. Open circuit Test from HV,
3. Magnetic Balance Test from HV
78

79 THANK YOU

Potrebbero piacerti anche