SIPROTEC 4 7UT6 differential protection relay for transformers, generators, motors and busbars
for two end protection objects (1/3 x 19 housing 7XP20) for three end protection objects (1/2 x 19 housing 7XP20) for three end protection objects (1/1 x 19 housing 7XP20) for five end protection objects (1/1 x 19 housing 7XP20)
PTD PA 7UT6 Present 11/04 No. 2
Hardware options
Device
Current Inputs (normal) Current Inputs (sensitive) Voltage Inputs (Uph / UE) Binary Inputs Binary Outputs Life contact LC Display
7UT612
7 (7)* 1 --3 4 1 4 lines
7UT613
11 (6)* 1** 3/1 5 8 1 4 lines
7UT633
11 (6)* 1** 3/1 21 24 1 Graphic
7UT635
14 (12)* 2** --29 24 1 Graphic
ANSI No.
87T/G/M/L
Protection Objects
Three-phase transformer
Single-phase transformer Auto-transformer Generator / Motor
Overcurrent-time, earth
Overcurrent-time, single phase Negative sequence Overload IEC 60255-8 Overload IEC 60354 (hot spot) 46
50G/51G
49 49
Overexcitation V/Hz
Breaker failure External temperature monitoring Lockout Measured value supervision Trip circuit supervision Direct coupling Operational measured values 38
24
50BF 86 74TC
Communication features
Flexibility due to plug in modules Compatibility to international standards
Front interface
DIGSI4 WEB Monitor
System interface
IEC60870-5-103 Profibus FMS Profibus DP DNP3.0 Modbus ASCII/RTU
Time synchronising
IRIG-B (GPS) DCF77
Connection Example
M3 side 3 L1 L2 L3 L1 L2 L3 M2
direct connection to the main Cts no matching transformers / no matching connections numerical vector group adaptation without zero sequence current correction depending of the type of earthing of the winding. increased sensitivity by 33% by measuring of the zero sequence current (7UT6) for single-pole faults.
side 2
side 1
M1
L1 L2 L3
IL1M2
IL2M2 IL3M2
IX1
IX3
1A/5A main Cts adaptation in the relay permissible ratio Ct nominal current to transformer nominal current up to 1 : 4
7UT613
PTD PA 7UT6 Present 11/04 No. 7
(1 of 4)
WEB server in the relays firmware Server sends its HTML-pages and JAVA-code to the WEB Monitor after a DIAL-UP connection
2. HTML page view in a WEB Monitor with the IP-address of the relay http://141.141.255.160
PTD PA 7UT6 Present 11/04 No. 8
(2 of 4)
(3 of 4)
(4 of 4)
Flexible adaptation of the tripping characteristic to various main Cts, tapped transformers.
Exact discrimination between the short circuit condition and the inrush condition by on-line analysis of the harmonics. Fast tripping for high-current faults. Ct saturation detector for external faults.