Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Introduction
The 2391 Theory examination is closed book,
in other words you cannot take any reference
books into the examination room.
However in order to work through the questions
you will be required to make reference to the
following publications:
BS 7671, On-Site Guide and Guidance Notes 3
Please remember
You will find questions that you cannot attempt
because you have not yet covered those
particular items. Do not be put off. All areas
will be covered in due course
Please remember
When carrying out questions involving
calculations you will need to use factors from
IEE publications. During the examination
ALL factors will be given in the examination
paper
Sample Questions
These questions are similar to those
that you will find in the examination.
They are Centre devised and not taken
from past City & Guilds papers
Question 1.
State TWO statutory documents that an
inspecting engineer would need knowledge
of, in order to work safely.
1. The Health and Safety at Work Act 1974
2. The Electricity @ Work Regulations 1989
Question 2.
State 4 non- statutory documents that an
inspecting engineer would need knowledge
of, in order to work safely.
4. GS 38 HSE publication
Question 3.
State three requirements of GS 38
1. Probe lengths max- 4mm, preferably 2mm.
2. Finger guards
3. Fused leads
Question 4.
State three requirements relating to the isolation
of the mains supply prior to undertaking work on
a circuit.
1. Verify supply dead using approved voltage
indicator.
Question 5.
State the FIVE types of injury detailed within the
Electricity at Work Regulations 1989 that may
result from the use of electrical energy
1. shock
2. fire
3. arcing
4. explosion
5. burns
Question 6.
State the maximum and minimum values of voltage
covered by the Electricity at Work Regulations 1989
Question 7.
State the competence required by the person
undertaking an inspection and test of an electrical
installation
1. Must be experienced in the type of installation or system to be
worked on
2. Must have suitable electrical knowledge
3. Must have a good working knowledge of statutory and non-statutory
regulations appertaining to the work to be undertaken
4. Must understand the use of and be able to safely use test equipment
5. Must be aware of the dangers that may be present during the
inspection and testing process to oneself and others that may be
using the installation
Question 8.
State THREE requirements of the Electricity at
Work Regulations covering the use of test
equipment
1. Must be suitable for its intended use or purpose
2. Must be used in such a manner so as not to cause danger
3. Must be regularly maintained
Question 9.
Question 10.
Question 11.
Question 12.
State the name and colour of the conductor
which connects the main earthing terminal
of a consumers installation, to equipment,
in order for its correct operation.
Functional earthing conductor, coloured
cream
Question 13.
State THREE methods which may be used
to reduce the resistance of an earth
electrode
additional earth electrodes
increasing the buried depth
soil conditioning
Question 14.
State the test which produces standing
voltages on exposed metalwork
Earth fault loop impedance testing
Question 15.
In order to maintain the correct output
voltage, an insulation resistance tester
must be capable of delivering a current of:
1 mA
Question 16.
State the minimum level of operating
current required for an overcurrent device,
if the maximum tabulated value of
impedance Zs, for the circuit is 2 (Uo =230V)
Current required to cause operation:
I = Uo/Zs = 230/2 = 115A.
Question 17.
State the required test voltages when
undertaking an insulation resistance
test on the following:
1. a single phase domestic lighting circuit
2. a 750 V discharge lighting circuit
3. an SELV circuit
1. 500V minimum 0.5M
2. 100V minimum 1.0M
3. 250Vminimum 0.25M
Question 18.
State the tests, including operating times,
that would need to be applied to a 30mA
residual current device
Question 19.
State the tests, (including operating times),
that would need to be applied to a 100mA
residual current device
Question 20.
Question 21.
When undertaking an earth fault loop
impedance (Zs) test on an r.c.d. protected
circuit, the device operates before a reading
can be obtained. Explain:
a. why the device operates
b. what can be done to obtain a value of Zs
a. device operates due to test current being
passed to earth (r.c.d. assumes fault
condition)
b. use of D-LOK or by calculation:
Zs = Ze + (R1+R2)
Question 22.
When undertaking an earth fault loop
impedance (Zs) test on a lighting circuit
protected by a 6A type B, BS EN 60898 circuit
breaker, the device operates before a reading
can be obtained.
Explain:
a. why the device operates
b. what can be done to obtain a value of Zs
a. device operates due to test current being
applied between phase and earth
b. by calculation, Zs = Ze + (R1+R2)
Maximum tabulated
value of Zs
0.42
1.3
0.6
1.3
0.91
Answers to Question 23
Measured Zs
Maximum tabulated
value of Zs
0.21
0.9
0.4
1.1
0.57
pass
pass
pass
fail
pass
Question 24
When verifying the external earth fault loop
impedance Zs at the origin of an installation, state
why it is necessary to:
a. remove bonding conductors
b. isolate the supply prior to removing bonding
conductors
a. To remove parallel earth paths
b. Protective conductors must MUST NOT be
removed/disconnected whilst supply is live, due
to the possible risk of electric shock
Question 25
State TWO methods of protection against both
direct and indirect contact (shock) as recognised by
BS 7671
a. SELV
b. limitation of discharge energy
Question 26
State FOUR types of supply suitable for use with
SELV circuits
1. safety isolating transformer to BS 3535
Question 27
Question 28
The maximum breaking capacity of an M3 BS 3871
circuit breaker is:
a. 3A
b. 30A
c. 300A
d. 3000A
Question 29
When measured at the origin of an electrical
installation, the value of prospective earth fault
current and prospective short circuit current were of
equal value. The type of earthing arrangement
involved would be:
a. TT
b. TN-S
c. TN-C-S
Question 30
State the information contained within a periodic
inspection and test report :
a. details of the client
b. characteristics of the supply
c. extent and limitation of the inspection and test
Question 31
The end to end resistance of each of the three rings
of a 30A ring circuit were measured and gave the
following results:
phase/phase ring - 0.96
neutral/neutral ring - 0.99
c.p.c./c.p.c. ring
- 0.97
Determine an approximate value of R1+R2 for this
circuit.
By adding the phase and c.p.c. ring
= 0.96 + 0.97= 1.93
Therefore approximate value of R1+R2
= 1.93/4 = 0.482
Question 32
When measured at the furthest point on an A3 radial
circuit,(T & c.p.c. general purpose p.v.c. copper
conductor cable), the value of R1+R2 was found to be
0.488. (ambient temperature 20C).
Calculate the approximate length of the circuit.
Phase and c.p.c. for A3 radial - 2.5/1.5mm2.
From Table 1A GN3 (page 107) R1+R2/metre = 19.51m
Question 33
State FOUR items of electrical equipment that
would require functional testing during an
inspection and test.
R.C.D.s
switches of socket outlet
isolators
circuit breakers
Question 34
State the equation that may be applied in
order to reduce the cross-sectional area of
circuit protective conductors
The adiabatic equation
s=
2
I .T
Question 35
State in the correct sequence the first five tests to
be applied during a periodic inspection and test of
an electrical installation.
Continuity
Polarity
Earth fault loop
Insulation resistance
Functional
Can
Peter
Ever
Inspect
Forever
Question 36
Determine the maximum permitted earth electrode
resistance for a 100mA r.c.d protecting a circuit in a
domestic electrical installation.
Zs = 50V/0.1 = 500
In practice it is recommended that an earth electrode
resistance in excess of 200 is unacceptable.
Remember! Very shortly this value is to be reduced to
a maximum of 100
Question 37
When undertaking a ring final circuit test, which
other TWO tests are automatically carried out?
Determination of R1+R2, and
Polarity
Question 38
Which ONE of the following values of insulation
resistance may indicate a latent defect?
a. 1.5M
b. 2.5M
c. 10.0M
d. 25M
Remember! A value below 2.0M may be indicative of
a latent defect.
Question 39
When undertaking a site applied insulation test, the
following applied voltage and test duration should be
adhered to:
a. 3750V a.c. for a period of 60 seconds
b. 3750V d.c. for a period of 60 seconds
c. 5000V a.c. for a period of 60 seconds
d. 5000V d.c. for a period of 60 seconds
Remember! During the 60 seconds test period
flashover should not occur.
Question 40
Which ONE of the following tests would NOT be
applied to a 500mA residual current device?
a.
b.
c.
d.
0.5 x I
1.0 x I
5 I
Functional test
Question 41
State THREE items of electrical equipment/accessories
which according to BS 7671 should be verified for
correct polarity
Question 42
Explain why it would be necessary to undertake a live
polarity test on an electrical installation. State where
the test should be conducted and the type of test
equipment to be used.
Question 43
A continuity test was undertaken on four equipotential
bonding conductors. The results of these tests are
listed below. Which of the four readings is not
acceptable?
a. 0.01
b. 45m
c. 0.04
d. 55m
Resistance of any bonding conductor not to be greater
than 0.05, 50m
Question 44
State THREE requirements of BS 7671 with regard to
the inspection of installed electrical equipment:
Distribution
Board
Question 45 continued
Total resistance = 1 + 1 + 1 + 1
50
100 20
10
2 + 1 + 5 + 10 = 18 = 100 = 5.55M
100
100
18
This is not the easiest thing to present or,
understand - please see me if you found this
difficult
Question 46
State the unit of measurement for each ONE of the
following tests:
impedance
insulation resistance
prospective fault current
r.c.d. test
continuity
Ohms ()
meggohms
kilo-amps (kA)
milliseconds
Ohms ()
Question 47
The total resistance of one core of a 1000 metre drum
of 2 -core cable is 1.2. Calculate the following values
of resistance for this cable:
a. the total resistance of both cores for 1000 metres
b. the resistance of 500 metres of one core
c. the resistance of one core of 1000 metre length if the
cross-sectional are was doubled
a. 2.4
b. 0.6
c. 0.6
Question 48
Give TWO reasons why direct contact (shock) is
generally more dangerous than indirect contact
(shock)
full supply voltage
no automatic disconnection of supply
Question 49
Give FOUR examples of metalwork which would
be defined as exposed conductive parts
Question 50
Give FOUR examples of metalwork which would
be defined as extraneous conductive parts
Question 51
A permanent label to BS 951 should be fixed in
a visible position at points of connection to every
earth electrode or bonding position. The wording
on the label should state:
Question 52
State the information that should be contained
on a label adjacent to every fuse or circuit
breaker
the size and type of fuse or circuit breaker
identification of the protected circuit
Question 53
A notice should be fixed in a prominent position,
at or near the origin of the installation. Sate the
two pieces of information that should appear on
the notice.
The notice relates to periodic inspection and should
state:
the date of the last inspection
recommended date of the next inspection
Question 54
Identify Four locations within an electrical
installation where impedance tests would need
to be carried out
Question 55
An Installation Certificate should only be issued
when:
a. defects have been remedied
b. both live and dead tests have been completed
c. the inspecting engineer has identified all defects
d. the supply authority has inspected the installation
Question 56
When undertaking a high current continuity test
on a ferrous enclosure, the maximum current
need not exceed :
a.
b.
c.
d.
10 A
15 A
25 A
50 A
Question 57
State the title of:
Question 58
Describe the procedures involved in undertaking an
insulation resistance test on a filament lighting circuit
incorporating electronic dimmer control.
PES
transformer
exposed
conductive part
seat of fault
PEN conductor
R2
earthing
MET
cond
earthed point of supply
Question 60
Describe how you would carry out a phase/earth fault
loop impedance test at the terminals of a three phase
induction motor
warning notices
Question 61
An electrical contractor is requested to install a motor
circuit and replace several defective fluorescent
lighting fittings. The installation is approximately twenty
five years old and does not have a current test
certificate. Sate the type(s) of certification required for
this installation.
Question 62
An A1 ring circuit has a length 50 metres and wired in
general purpose p.v.c. insulated cables having copper
conductors. Determine:
a. the resistance of each ring when measured at 20C
b. the value of (R1+R2) of the ring circuit when
measured at 20C
Question 62 continued
Table 1A (GN3) R1 = 7.41m per metre
a. resistance of R1 (phase ring)
= 7.41x 50 = 370.5m = 0.3705
Therefore resistance of phase ring = 0.3705
As neutral conductor has same c.s.a. and
length its resistance will also be 0.3705
Question 62 continued
Resistance of c.p.c. (R2) = 12.10 m
For 50 metres = 12.10 x 50 = 605m
= 0.605
Question 63
State FIVE external influences which might affect the
integrity of an electrical installation:
1. mechanical damage
2. vandalism
3. extremes of temperature
4. moisture/water
5. corrosion
Question 64
State FIVE specific areas of inspection when
undertaking an inspection and test on a light industrial
workshop:
1.
2.
3.
4.
5.
6.
7.
8.
warning notices/labels
distribution charts, diagrams etc etc
presence of earthing and bonding conductors
selection of live conductors in relation to current
carrying capacity and voltage drop
rating/setting of overcurrent devices
identification of conductors
methods of protection against direct/indirect shock
Location of devices for isolation and switching
Question 65
State the first FIVE tests to be undertaken on an A1
ring circuit during an initial verification:
1.
2.
3.
4.
5.
Question 66
State the overall effect on the insulation resistance of
an installation when:
a. a circuit is added
b. a circuit is removed
a. adding circuits will decrease the overall value of
insulation resistance
Question 67
An instrument used to measure the impedance at the
incoming terminals of a 400/230V three phase TN-S
system indicates the following results:
phase - neutral 0.2
phase - earth 0. 5
Determine:
Question 67continued
a. If = 230/0.5 = 460A (0.46kA)
b. Ip (p-n) = 230/0.2 = 1150A (1.15 kA)
c. Ip (between two phases) 1.15 x 2 =2300A (2.3kA)
Question 68
State FIVE reasons why an installation will need to
undergo a periodic inspection and test:
Question 69
State FIVE bodies or organisations that may be
involved with the preparation of a specification for an
electrical installation:
designer
installer
PES
architect
fire prevention officer
Health & Safety Executive
Question 70
List THREE types of earth electrode recognised by BS
7671
rod
plate
lattice
Question 71
List the precautions to be observed when undertaking
an earth electrode test using and impedance tester:
isolate supply before removing earthing conductor
erect warning notices
erect barrier/appoint person to safeguard electrode
site during test
connect impedance tester between incoming phase
terminal at distribution board and take measurement
reconnect earthing conductor before reinstating
mains supply
Question 72
A periodic inspection and test report should be signed
by:
a. the person ordering the work
b. a competent person
Question 73
A periodic inspection and test report should be signed
by:
a. the person ordering the work
b. a competent person
Question 74
A minor works certificate would be issued when:
a. a single circuit is added to an existing installation
b. alterations or additions are made to an existing
installation
Question 75
A Short form of Electrical Installation Certificate may be
issued when:
Question 76
State the information that should be made available to
the person carrying out an inspection and test:
Maximum demand after the application of diversity
number and type of live conductors of the source of
energy and of the circuits used in the installation
the type of earthing arrangement
type and composition of circuits
description and location of devices performing the
functions of protection or isolation
methods selected to prevent danger from shock in
the event of an earth fault
any circuit or equipment vulnerable to testing
Question 77
Which ONE of the following will provide protection
against both direct and indirect contact?
a. Class II installation
b. SELV
c. EEBADOS
Question 78
Which ONE of the following will NOT provide protection
against indirect contact?
a. non-conducting location
b. SELV
c. barriers and enclosures
Question 79.
State 4 non- statutory documents that an
inspecting engineer would need knowledge
of, in order to work safely.
1. BS 7671:1992 (16th Edition IEE Wiring
Regulations).
2. IEE On-Site guide
3. Guidance Notes 3 (inspection and Testing)
4. GS 38 HSE publication
Question 80
Where an installation is protected by a residual current
device it should be manually tested by use of the
integral test button:
a. weekly
b. monthly
c. quarterly
d. annually
Question 81
Where diagrams, charts or tables are not available
during a periodic inspection:
a. all work should cease and the client informed
accordingly
b. testing should be carried out in place of the visual
inspection
c. a degree of exploratory work may be necessary
d. it should be recorded in the extent and limitations
Question 82
The minimum cross-sectional area of a supplementary
equipotential bonding conductor is:
a. 1.5mm2
b. 2.5mm2
c. 4.0mm2
d. 6.0mm2
Question 83
The minimum cross-sectional area of a main earthed
equipotential bonding conductor for use on a TN-S
system is:
a. 4.0mm2
b. 6.0mm2
c. 10.0mm2
d. 16.0mm2
Question 84
The minimum cross-sectional area of a main earthed
equipotential bonding conductor for use on a TN-C-s
system is:
a. 4.0mm2
b. 6.0mm2
c. 10.0mm2
d. 16.0mm2
Question 85
The minimum acceptable value of insulation resistance
for FELV circuits is:
a. 0.25M
b. 0.5M
c. 1.0M
d. 2.0M
Question 86
The minimum acceptable value of insulation resistance
for SELV circuits is:
a. 0.25M
b. 0.5M
c. 1.0M
d. 2.0M
Question 87
The minimum acceptable value of insulation resistance
for a 400V a.c. motor circuits is:
a. 0.25M
b. 0.5M
c. 1.0M
d. 2.0M
Question 88
The minimum acceptable value of insulation resistance
for a 650V discharge lighting circuits is:
a. 0.25M
b. 0.5M
c. 1.0M
d. 2.0M
Question 89
Which of the following actions would be INCORRECT
when undertaking an insulation resistance test on a
230V discharge lighting circuit.:
a. testing between live conductors with the local
switch in the on position
b. testing between phase conductor and earth with the
local switch in the on position
Question 90
As an alternative to the D-Lok, some instruments
reduce the possibility of r.c.d. tripping during impedance
testing by limiting the test current to:
a. 15mA
b. 30mA
c. 100mA
d. 150mA
Form No
/4
Instruments:
.................................................................
1 Type of Supply TN-S/TN-C-S/TT
.................................................................
2 Ze at origin .......................... ohms
Signature ..................................................
.................................................................
3 PFC ..................................... kA
Method of protection against indirect contact .......................................................................................................................
Wiring
Overcurrent
Device
Short-circuit
capacity
..............kA
Inst.
Ref.
Meth.
4
type
Test Results
Conductors
conductors
Insulation
Resistance
live cpc
Rating
In
live
cpc
mm 2
mm 2
Continuity
continuity
10
R1 + R2
R2
R1+R2
R2
11
12
Rin
g
i
n
g
13
Live/L
ive
Live
Po
rity
la
o
l
a
Live/E
rth
a
r
Earth
i
Earth
LoopIm
c
n
a
d
e
p
Impedance
Zs
Functional
Testing
RCD
time
Remarks
Other
t
M
14
M
15
y
16
ms
17
18
19
1
2
3
4
5
6
7
8
9
10
11
12
B, C or D (BS EN 60898)
1, 2 or 3 BS 3871
BS 3036, 1361,BS 88
Page
of
Form No
/4
Instruments:
.................................................................
1 Type of Supply TN-S/TN-C-S/TT
.................................................................
2 Ze at origin .......................... ohms
Signature ..................................................
.................................................................
3 PFC ..................................... kA
Method of protection against indirect contact .......................................................................................................................
Wiring
Overcurrent
Device
Short-circuit
capacity
..............kA
Inst.
Ref.
Meth.
4
type
Test Results
Conductors
conductors
Insulation
Resistance
live cpc
Rating
In
live
cpc
mm 2
mm 2
Continuity
continuity
10
R1 + R2
R2
R1+R2
R2
11
12
Rin
g
i
n
g
13
Live/L
ive
Live
Po
rity
la
o
l
a
Live/E
rth
a
r
Earth
i
Earth
LoopIm
c
n
a
d
e
p
Impedance
Zs
Functional
Testing
RCD
time
Remarks
Other
t
M
14
M
15
y
16
ms
17
18
19
1
2
3
4
5
6
7
8
9
10
11
12
Rating of overcurrent
device in amperes
Page
of
Form No
/4
Instruments:
.................................................................
1 Type of Supply TN-S/TN-C-S/TT
.................................................................
2 Ze at origin .......................... ohms
Signature ..................................................
.................................................................
3 PFC ..................................... kA
Method of protection against indirect contact .......................................................................................................................
Wiring
Overcurrent
Device
Short-circuit
capacity
..............kA
Inst.
Ref.
Meth.
4
type
Test Results
Conductors
conductors
Insulation
Resistance
live cpc
Rating
In
live
cpc
mm 2
mm 2
Continuity
continuity
10
R1 + R2
R2
R1+R2
R2
11
12
Rin
g
i
n
g
13
Live/L
ive
Live
Po
rity
la
o
l
a
Live/E
rth
a
r
Earth
i
Earth
LoopIm
c
n
a
d
e
p
Impedance
Zs
Functional
Testing
RCD
time
Remarks
Other
t
M
14
M
15
y
16
ms
17
18
19
1
2
3
4
5
6
7
8
9
10
11
12
Deviations from Wiring Regulations and special notes:
Page
of
Installation methods
Form 4
Form No
/4
Instruments:
.................................................................
1 Type of Supply TN-S/TN-C-S/TT
.................................................................
2 Ze at origin .......................... ohms
Signature ..................................................
.................................................................
3 PFC ..................................... kA
Method of protection against indirect contact .......................................................................................................................
Wiring
Overcurrent
Device
Short-circuit
capacity
..............kA
Inst.
Ref.
Meth.
4
type
Test Results
Conductors
conductors
Insulation
Resistance
live cpc
Rating
In
live
cpc
mm 2
mm 2
Continuity
continuity
10
R1 + R2
R2
R1+R2
R2
11
12
Rin
g
i
n
g
13
Live/L
ive
Live
Po
rity
la
o
l
a
Live/E
rth
a
r
Earth
i
Earth
LoopIm
c
n
a
d
e
p
Impedance
Zs
Functional
Testing
RCD
time
Remarks
Other
t
M
14
M
15
y
16
ms
17
18
19
1
2
3
4
5
6
7
8
9
10
11
12
Page
of
Conductor sizes
Form 4
Form No
/4
Instruments:
.................................................................
1 Type of Supply TN-S/TN-C-S/TT
.................................................................
2 Ze at origin .......................... ohms
Signature ..................................................
.................................................................
3 PFC ..................................... kA
Method of protection against indirect contact .......................................................................................................................
Wiring
Overcurrent
Device
Short-circuit
capacity
..............kA
Inst.
Ref.
Meth.
4
type
Test Results
Conductors
conductors
Insulation
Resistance
live cpc
Rating
In
live
cpc
mm 2
mm 2
Continuity
continuity
10
R1 + R2
R2
R1+R2
R2
11
12
Rin
g
i
n
g
13
Live/L
ive
Live
Po
rity
la
o
l
a
Live/E
rth
a
r
Earth
i
Earth
LoopIm
c
n
a
d
e
p
Impedance
Zs
Functional
Testing
RCD
time
Remarks
Other
t
M
14
M
15
y
16
ms
17
18
19
1
2
3
4
5
6
7
8
9
10
11
12
Deviations from Wiring Regulations and special notes:
Page
of
Continuity
Form 4
Form No
/4
Instruments:
.................................................................
1 Type of Supply TN-S/TN-C-S/TT
.................................................................
2 Ze at origin .......................... ohms
Signature ..................................................
.................................................................
3 PFC ..................................... kA
Method of protection against indirect contact .......................................................................................................................
Wiring
Overcurrent
Device
Short-circuit
capacity
..............kA
Inst.
Ref.
Meth.
4
type
Test Results
Conductors
conductors
Insulation
Resistance
live cpc
Rating
In
live
cpc
mm 2
mm 2
Continuity
continuity
10
R1 + R2
R2
R1+R2
R2
11
12
Rin
g
i
n
g
13
Live/L
ive
Live
Po
rity
la
o
l
a
Live/E
rth
a
r
Earth
i
Earth
LoopIm
c
n
a
d
e
p
Impedance
Zs
Functional
Testing
RCD
time
Remarks
Other
t
M
14
M
15
y
16
ms
17
18
19
1
2
3
4
5
6
7
8
9
10
11
12
Page
of
Form No
/4
Instruments:
.................................................................
1 Type of Supply TN-S/TN-C-S/TT
.................................................................
2 Ze at origin .......................... ohms
Signature ..................................................
.................................................................
3 PFC ..................................... kA
Method of protection against indirect contact .......................................................................................................................
Wiring
Overcurrent
Device
Short-circuit
capacity
..............kA
Inst.
Ref.
Meth.
4
type
Test Results
Conductors
conductors
Insulation
Resistance
live cpc
Rating
In
live
cpc
mm 2
mm 2
Continuity
continuity
10
R1 + R2
R2
R1+R2
R2
11
12
Rin
g
i
n
g
13
Live/L
ive
Live
Po
rity
la
o
l
a
Live/E
rth
a
r
Earth
i
Earth
LoopIm
c
n
a
d
e
p
Impedance
Zs
Functional
Testing
RCD
time
Remarks
Other
t
M
14
M
15
y
16
ms
17
18
19
1
2
3
4
5
6
7
8
9
10
11
12
Page
of
Insulation resistance
Form 4
Form No
/4
Instruments:
.................................................................
1 Type of Supply TN-S/TN-C-S/TT
.................................................................
2 Ze at origin .......................... ohms
Signature ..................................................
.................................................................
3 PFC ..................................... kA
Method of protection against indirect contact .......................................................................................................................
Wiring
Overcurrent
Device
Short-circuit
capacity
..............kA
Inst.
Ref.
Meth.
4
type
Test Results
Conductors
conductors
Insulation
Resistance
live cpc
Rating
In
live
cpc
mm 2
mm 2
Continuity
continuity
10
R1 + R2
R2
R1+R2
R2
11
12
Rin
g
i
n
g
13
Live/L
ive
Live
Po
rity
la
o
l
a
Live/E
rth
a
r
Earth
i
Earth
LoopIm
c
n
a
d
e
p
Impedance
Zs
Functional
Testing
RCD
time
Remarks
Other
t
M
14
M
15
y
16
ms
17
18
19
1
2
3
4
5
6
7
8
9
10
11
12
Page
of
Insulation resistance
Form 4
Form No
/4
Instruments:
.................................................................
1 Type of Supply TN-S/TN-C-S/TT
.................................................................
2 Ze at origin .......................... ohms
Signature ..................................................
.................................................................
3 PFC ..................................... kA
Method of protection against indirect contact .......................................................................................................................
Wiring
Overcurrent
Device
Short-circuit
capacity
..............kA
Inst.
Ref.
Meth.
4
type
Test Results
Conductors
conductors
Insulation
Resistance
live cpc
Rating
In
live
cpc
mm 2
mm 2
Continuity
continuity
10
R1 + R2
R2
R1+R2
R2
11
12
Rin
g
i
n
g
13
Live/L
ive
Live
Po
rity
la
o
l
a
Live/E
rth
a
r
Earth
i
Earth
LoopIm
c
n
a
d
e
p
Impedance
Zs
Functional
Testing
RCD
time
Remarks
Other
t
M
14
M
15
y
16
ms
17
18
19
1
2
3
4
5
6
7
8
9
10
11
12
Page
of
Polarity
Form 4
Form No
/4
Instruments:
.................................................................
1 Type of Supply TN-S/TN-C-S/TT
.................................................................
2 Ze at origin .......................... ohms
Signature ..................................................
.................................................................
3 PFC ..................................... kA
Method of protection against indirect contact .......................................................................................................................
Wiring
Overcurrent
Device
Short-circuit
capacity
..............kA
Inst.
Ref.
Meth.
4
type
Test Results
Conductors
conductors
Insulation
Resistance
live cpc
Rating
In
live
cpc
mm 2
mm 2
Continuity
continuity
10
R1 + R2
R2
R1+R2
R2
11
12
Rin
g
i
n
g
13
Live/L
ive
Live
Po
rity
la
o
l
a
Live/E
rth
a
r
Earth
i
Earth
LoopIm
c
n
a
d
e
p
Impedance
Zs
Functional
Testing
RCD
time
Remarks
Other
t
M
14
M
15
y
16
ms
17
18
19
1
2
3
4
5
6
7
8
9
10
11
12
Deviations from Wiring Regulations and special notes:
Page
of
Impedance
Form 4
Form No
/4
Instruments:
.................................................................
1 Type of Supply TN-S/TN-C-S/TT
.................................................................
2 Ze at origin .......................... ohms
Signature ..................................................
.................................................................
3 PFC ..................................... kA
Method of protection against indirect contact .......................................................................................................................
Wiring
Overcurrent
Device
Short-circuit
capacity
..............kA
Inst.
Ref.
Meth.
4
type
Test Results
Conductors
conductors
Insulation
Resistance
live cpc
Rating
In
live
cpc
mm 2
mm 2
Continuity
continuity
10
R1 + R2
R2
R1+R2
R2
11
12
Rin
g
i
n
g
13
Live/L
ive
Live
Po
rity
la
o
l
a
Live/E
rth
a
r
Earth
i
Earth
LoopIm
c
n
a
d
e
p
Impedance
Zs
Functional
Testing
RCD
time
Remarks
Other
t
M
14
M
15
y
16
ms
17
18
19
1
2
3
4
5
6
7
8
9
10
11
12
Page
of
r.c.d.operation
Form 4
Form No
/4
Instruments:
.................................................................
1 Type of Supply TN-S/TN-C-S/TT
.................................................................
2 Ze at origin .......................... ohms
Signature ..................................................
.................................................................
3 PFC ..................................... kA
Method of protection against indirect contact .......................................................................................................................
Wiring
Overcurrent
Device
Short-circuit
capacity
..............kA
Inst.
Ref.
Meth.
4
type
Test Results
Conductors
conductors
Insulation
Resistance
live cpc
Rating
In
live
cpc
mm 2
mm 2
Continuity
continuity
10
R1 + R2
R2
R1+R2
R2
11
12
Rin
g
i
n
g
13
Live/L
ive
Live
Po
rity
la
o
l
a
Live/E
rth
a
r
Earth
i
Earth
LoopIm
c
n
a
d
e
p
Impedance
Zs
Functional
Testing
RCD
time
Remarks
Other
t
M
14
M
15
y
16
ms
17
18
19
1
2
3
4
5
6
7
8
9
10
11
12
Page
of
Form No
/4
Instruments:
.................................................................
1 Type of Supply TN-S/TN-C-S/TT
.................................................................
2 Ze at origin .......................... ohms
Signature ..................................................
.................................................................
3 PFC ..................................... kA
Method of protection against indirect contact .......................................................................................................................
Wiring
Overcurrent
Device
Short-circuit
capacity
..............kA
Inst.
Ref.
Meth.
4
type
Test Results
Conductors
conductors
Insulation
Resistance
live cpc
Rating
In
live
cpc
mm 2
mm 2
Continuity
continuity
10
R1 + R2
R2
R1+R2
R2
11
12
Rin
g
i
n
g
13
Live/L
ive
Live
Po
rity
la
o
l
a
Live/E
rth
a
r
Earth
i
Earth
LoopIm
c
n
a
d
e
p
Impedance
Zs
Functional
Testing
RCD
time
Remarks
Other
t
M
14
M
15
y
16
ms
17
18
19
1
2
3
4
5
6
7
8
9
10
11
12
Deviations from Wiring Regulations and special notes:
Page
of