Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Short circuits
Supply bypasses the load Very dangerous
Lead to high fault currents Disastrous effects on equipment
Thermal heating Electromechanical effects Fires
Therefore fault current must be accurately predicted for a fault in any location
Impedance characteristics of all electrical items in the system must be known Fault impedance itself may be non-zero and difficult to estimate There may be substantial fault current contribution from rotating machines Initial cycles of fault current may be asymmetric with substantial dc offset Earth impedance in earth faults can be difficult to estimate
Line-to-line shortcircuit
Line-to-earth short-circuit
Magnitude
(E/Z) x multiplier 0.87 x 3-phase fault Depends on system grounding
Use of pu system
For balanced symmetrical 3-phase faults
Fault calculation must be done on single phase basis Use the pu phase impedance of one-line diagram
Care must be taken to ensure the proper phase kVA and voltage levels are used in the calculation IB = (SB/3)/(VB/3) = SB/ (3 VB) ZB = [(VB/3)2]/(SB/3) = VB2/SB Where VB is the line voltage And SB is the three phase kVA value
Change of base
Fault calculations must include all significant components of impedance
Must be expressed in pu terms using the appropriate base value Sometimes may need to be changed if they are expressed using different bases, e.g transformer impedances Zpu = Z/ZB = Z(SB/VB2) For change of kVA base (SB): Zpu(new) = Zpu(old)[SB(new)/SB(old)] Change of voltage base (VB): Zpu(new) = Zpu(old)[VB2(old)/VB2(new)] Change of both kVA and voltage bases at the same time: Zpu(new) = Zpu(old)[SB(new)/SB(old)][VB2(old)/VB2(new)] Impedances of transformers, motors, etc will be given in pu terms based on their rated voltage and power levels Impedances of cables, overhead lines, etc will be given in ohms and must be converted to pu with the appropriate base
Capacitors and battery operated UPS are lowlevel sources of fault current Supply utility and in-house generation provides constant fault current (stiff source) Motors will provide decaying fault current as their magnetic excitation fields collapse
Synchronous reactance is generally not used since protection will operate before it comes into effect
For synchronous motors, only the sub-transient and transient reactance are normally used For induction motors, only the sub-transient reactance is used
DC Offset
Must be included in fault calculations, especially LV systems
DC offset can increase initial current levels substantially
Generator
Symmetrical short-circuit current from 3 sources (utility, motors and generator combined into a total)
Fault is balanced 3-phase symmetrical Pu impedances are pure reactances for MV systems, any resistance is neglected For LV systems where resistance is important, impedance is [Z] = (R2 + X2)1/2 All significant component impedances are included The fault itself has zero impedance (i.e. bolted short circuit)
Rated voltage is used as the voltage base X/R for all equipment
used to calculate level of DC offset multiplier
after symmetrical fault current has been calculated
10
11
12
13