Sei sulla pagina 1di 17

Submittal

Trane A Division of American Standard Inc.

Prepared For: Seminole County Government

Date: February 02, 2006

Job Name: Seminole County Services Air Cooled Chillers

Trane is pleased to provide the enclosed submittal for your review and approval. Product Summary Qty Product 6 Air-Cooled Water Chillers

The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval.

Trane 1151 Keller Road Orlando, FL 32810-5924 Phone: (407)660-1111 Fax: (407)660-0303

J:\JOBS\43\41802\2\Seminole County Services Air Cooled Chillers submittal.doc

Table Of Contents Product Summary.............................................................................. Error! Bookmark not defined. Air-Cooled Water Chillers (Large Tonnage) (Items A1 - A3)
Tag Data ...................................................................................................Error! Bookmark not defined. Product Data .............................................................................................Error! Bookmark not defined. Performance Data .....................................................................................Error! Bookmark not defined. Mechanical Specifications .........................................................................Error! Bookmark not defined. Unit Dimensions ........................................................................................Error! Bookmark not defined. Weight, Clearance & Rigging Diagram......................................................Error! Bookmark not defined. Field Wiring ...............................................................................................Error! Bookmark not defined.

Field Installed Options - Part/Order Number Summary


Air-Cooled Water Chillers (Large Tonnage) ..............................................Error! Bookmark not defined.

Seminole County Services Air Cooled Chillers

February 02, 2006

Tag Data - Air-Cooled Water Chillers (Qty: 6) Item Tag(s) Qty Description A1 CGAF-C25 1 25 Ton Packaged Air-Cooled Chiller A2 CGAF-C50 2 50 Ton Packaged Air-Cooled Chiller A3 CGAF-C60 3 60 Ton Packaged Air-Cooled Chiller Product Data - Air-Cooled Water Chillers All Units 200 Volt 60 Hertz 3 Phase 40 to 50 degree F Water Setpoint UL/ CSA Approval Unit Spring Isolators (Fld) Unit Mounted Terminal Block Trane Communications Interface Module (TCI) R-407C

Model Number CGAFC25E CGAFC50E CGAFC60E

Notes: Disconnect switches not included.

FLD = Furnished by Trane / Installed by Others

Trane Equipment Submittal

Page 3 of 17

Seminole County Services Air Cooled Chillers

February 02, 2006

Performance Data - Air-Cooled Water Chillers Tags CGAF-C25 Total cooling capacity (tons) 23.32 Ent evaporator temp (F) 54.00 Lvg evaporator temp (F) 44.00 Ambient temperature (F) 95.00 Evaporator fouling factor (hr-sq ft-deg F/Btu) 0.00001 Evaporator flow rate (gpm) 55.79 Saturated suction temp (F) 37.23 Cooling fluid PD (ft H2O) 6.15 Compressor power (kW) 25.92 Fan power (kW) 2.70 System power (kW) 28.62 EER @ ARI (EER) 9.8 COP @ ARI (COP) 2.80 IPLV @ ARI (IPLV) 14.6 Min circuit ampacity (A) 124.00 Max fuse size (A) 175.00 Recommended dual element (A) 150.00 Circuit 1 compressor 1 LRA (A) 269.00 Circuit 1 compressor 1 RLA (A) 39.30 Circuit 1 compressor 2 LRA (A) 409.00 Circuit 1 compressor 2 RLA (A) 56.90 Circuit 2 compressor 1 LRA (A) 0.00 Circuit 2 compressor 1 RLA (A) 0.00 Circuit 2 compressor 2 LRA (A) 0.00 Circuit 2 compressor 2 RLA (A) 0.00 Fan quantity (Each) 3.00 FLA per fan (A) 4.10 Part load step 1 (%) 40.00 Ambient at step 1 (F) 59.00 Capacity at step 1 (tons) 12.22 Unit power at step 1 (kW) 8.26 EER @ ARI at step 1 (EER) 15.3 Part load step 2 (%) 60.00 Ambient at step 2 (F) 71.00 Capacity at step 2 (tons) 16.89 Unit power at step 2 (kW) 13.48 EER @ ARI at step 2 (EER) 13.8 Part load step 3 (%) Ambient at step 3 (F) Capacity at step 3 (tons) Unit power at step 3 (kW) EER @ ARI at step 3 (EER) Outdoor - 63 Hz (dB) 96 Outdoor - 125 Hz (dB) 91 Outdoor - 250 Hz (dB) 92 Outdoor - 500 Hz (dB) 91 Outdoor - 1 kHz (dB) 88 Outdoor - 2 kHz (dB) 87 Outdoor - 4 kHz (dB) 84 Outdoor - 8 kHz (dB) 82 A weighted sound power (dBA) 94 A weighted sound pressure (dBA) 67 Min operating weight (lb) 2085.0 Max operating weight (lb) 2370.0

CGAF-C50 42.77 54.00 44.00 95.00 0.00001 102.32 37.69 7.42 46.98 5.40 52.38 9.7 2.80 14.5 224.00 250.00 250.00 409.00 55.50 269.00 35.50 409.00 55.50 269.00 35.50 6.00 4.10 30.00 55.00 14.57 10.70 17.0 60.00 71.00 31.17 24.87 13.5 80.00 83.00 37.73 37.42 11.3 97 92 92 93 89 89 87 85 96 69 3900.0 4435.0

CGAF-C60 54.65 54.00 44.00 95.00 0.00001 130.75 38.24 6.00 62.22 5.40 67.62 9.7 2.80 15.0 270.00 300.00 300.00 409.00 56.90 409.00 56.90 409.00 56.90 409.00 56.90 6.00 4.10 25.00 55.00 15.93 11.30 18.3 50.00 65.00 35.08 25.17 15.2 75.00 80.00 46.16 43.41 11.9 97 92 92 94 91 89 87 85 97 70 4885.0 5820.0

FLD = Furnished by Trane / Installed by Others

Trane Equipment Submittal

Page 4 of 17

Seminole County Services Air Cooled Chillers

February 02, 2006

Mechanical Specifications - Air-Cooled Water Chillers (Large Tonnage) Item: A1 - A3 Qty: 6 Tag(s): CGAF-C25, CGAF-C50, CGAF-C60 General All chillers are factory run-tested to confirm proper operation. Units are checked on computer based test stand at typical ambient and water conditions and control operation is monitored. Units ship with a full operating charge of refrigerant and oil. Units are constructed of 14-gauge welded galvanized steel frame with 14 and 16-gauge galvanized steel panels and access doors. Unit surface is phosphatized and finished with an air-dry paint. This air-dry paint finish is durable enough to withstand a 1000-consecutive-hour salt spray application in accordance with standard ASTM B117. A flow switch is included as ship-with item to be field installed at the outlet of the evaporator. The flow switch is required as a safety interlock to prevent operation of unit without evaporator flow. General A strainer (with installation hardware) is included as a ship-with item to be field installed at the inlet of the evaporator. The strainer is required to prevent collection of particles within the evaporator. Strainer is field installed to facilitate ease of installation. Compressor Trane 3-D Scroll compressors have simple mechanical design with only three (3) major moving parts. Scroll type compression provides inherently low vibration. 3-D compliance provides a completely enclosed compression chamber which leads to increased efficiency. Exhaustive testing on the 3D Scroll, including start up with the shell full of liquid, has proven that slugging does not fail involutes. Direct-drive, 3600 rpm, suction gas-cooled hermetic motor. Trane 3D Scroll compressor includes centrifugal oil pump, oil level sightglass and oil charging valve. Evaporator The evaporator shall be braze plate construction with a waterside working pressure of 300 PSIG and a refrigerant side of working pressure of 225. Etched foil heaters protect the evaporator to ambient of -20 degrees F. Condenser Fans Direct-drive vertical discharge condenser fans are statically and dynamically balanced. Three phase thermal overload protected with permanently lubricated ball bearings. Controls Compressor contactors and unit controls are in a weather tight enclosure with knockouts for field installed wiring. The chiller unit utilizes a DDC microprocessor control system which is suitable for comfort and process cooling applications. The control system is factory installed in the main control panel with the necessary internal controls and run tested. Terminal blocks for field power wiring connections are standard. Units provide a location for a non-fused disconnect switch with an external handle for safety. Unit mounted microprocessor controls provide compressor antishort cycle protection. The unit is equipped with a Human Interface Panel with a 16 key keypad, a 2 line by 40 character English display to provide the operator with full adjustment and display of control data function. The unit controls can be used as a stand-alone controller or as part of a building management system. The display can be read and adjusted without opening any unit panels. Decorative Grilles Decorative grilles provide protection from exterior damage to coil surface and other interior unit components. Grilles are factory mounted louvered, galvanized steel panels finished with an air dry paint. Grilles cover all air accessible ends of the unit. Refrigerant Circuits with 2-Stage Capacity Modulation for 20 - 30 Ton Units The unit has a single refrigeration circuit with two (2) compressors manifolded together utilizing a passive oil system. The refrigerant circuit includes an liquid line solenoid valve, filter drier, sight glass with moisture indicator, thermostatic expansion valve and service valves (liquid and discharge). Capacity modulation is accomplished by turning compressors on and off. The unit has two capacity stages. The standard leaving chilled water temperature range is 40 to 50 F [4.5 to 10 C]. Refrigerant Circuits with 4-Stage Capacity Modulation for 40 - 60 Ton Units The unit has dual refrigeration circuits. Each circuit has two (2) compressors manifolded together utilizing a passive oil system. Each refrigerant circuit includes an liquid line solenoid valve, filter drier, sightglass with moisture indicator,thermostatic expansion valve and service valves (liquid and discharge). Capacity modulation is accomplished by turning compressors on and off. The unit has four capacity stages. The standard leaving chilled
FLD = Furnished by Trane / Installed by Others Trane Equipment Submittal Page 5 of 17

Seminole County Services Air Cooled Chillers

February 02, 2006

water temperature range is 40 to 50 F [4.5 to 10 C]. Trane Communication Interface Module ( TCI ) The TCI provides interface to Trane's Integrated Comfort system ( ICS ), which allows control and monitoring of the unit by Tracer building management system. Spring Isolators Spring isolators are available for field installation under the unit frame. Condenser Coils with Aluminum Fins Air-cooled condenser coils have configured aluminum fins mechanically bonded to seamless copper tubing and integral subcooling circuits. Condenser coils are factory leak tested under water with 425 psig [2930.4 kPa] air pressure.

FLD = Furnished by Trane / Installed by Others

Trane Equipment Submittal

Page 6 of 17

Seminole County Services Air Cooled Chillers

February 02, 2006

Unit Dimensions - Air-Cooled Water Chillers (Large Tonnage) Item: A1 Qty: 1 Tag(s): CGAF-C25

2 3/4" 70mm 1 3/32" (4X) 30V MAX. 28mm

3 1/4" 83mm 3'-1 3/8" 949mm 3'-3 5/8" 1006mm 2'-11" 889mm 2'-9" 838mm 5 7/8" 149mm 7'-4 " 1/4 1 3/32" (1X) HEAT TAPE POWER 28mm 8" 3" CONDUIT MAIN POWER 76mm 9 3/4" 248mm 7 1/8" 181mm 3/4" 19mm DIA. X 4 MTG HOLES 203mm 6'- "1/8 1832mm 8'-0" 2438mm MINIMUM CLEARANCE 2242mm

3 5/8" 92mm

CONNECTIONS BOTTOM SEE DETAIL "A"

4'-9 1/2" 1461mm DOOR SWING 180 5'-0 1/8" 1527mm

DETAIL "A"

3'-5 3/4" 1060mm

NO OBSTRUCTIONS AIR FLOW OPTIONAL DAMPER 2 3/4" 70mm 1'-1 1/2" 343mm

3 1 1/4" 32mm

TOP VIEW

8'-0" 2438mm MINIMUM CLEARANCE

CONTROL PANEL

6 1/8 " 3'-2" 965mm 156mm 6'-1 3/8" 1864mm 5'-8" 1727mm COMP 2'-3 1/4" 692mm 4 3/8 " 111mm

3 5/8" DIA. 92mm LINE VOLTAGE 1 1/4" X 4 1/2" 32mm X 114mm CONTROL CONN. 1'-6" 457mm SLOT

2" Grooved Pipe Connection Water Inlet

LEFT SIDE VIEW

11 1/2" 292mm

2" Grooved Pipe Connection Water Outlet

2' 6" 762mm

5 1/8" 130mm

6'-6" 1981mm

2 1/2" 64mm

DIA. HOLES (4) LIFTING LOCATIONS

FRONT VIEW
9" 229mm

1' 3" 381mm

Front View Access Hole Locations

FLD = Furnished by Trane / Installed by Others

Trane Equipment Submittal

Page 7 of 17

Seminole County Services Air Cooled Chillers

February 02, 2006

Unit Dimensions - Air-Cooled Water Chillers (Large Tonnage) Item: A2 Qty: 2 Tag(s): CGAF-C50

2 3/4" 70mm 1 3/32" (4X) 30V MAX. 28mm

3 1/4" 83mm 3'-1 3/8" 949mm 3'-3 5/8" 1006mm 2'-11" 889mm 2'-9" 838mm 5 7/8" 149mm 1 3/32" (1X) HEAT TAPE POWER 28mm 3" CONDUIT MAIN POWER 76mm 9 3/4" 248mm 7 1/8" 181mm CONNECTIONS BOTTOM SEE DETAIL "A" 2 8 1/8" 206mm 4'-0 7/8" 1241mm

9'-5 7/8" 2892mm 4'-0 7/8" 1241mm

8'-0" 2438mm MINIMUM CLEARANCE

7'-4 3/8" 2245mm

3 5/8" 92mm

7'-1 5/8" 2175mm

DETAIL "A"

3'-5 3/4" 1060mm

DOOR SWING 180

NO OBSTRUCTIONS AIR FLOW

OPTIONAL DAMPER

1 2 3/4" 70mm 1'-1 1/2" 343mm

5 1 1/4" 32mm 8'-0" 2438mm MINIMUM CLEARANCE

3/4" DIA. X 6 MTG HOLES 19mm

TOP VIEW

CONTROL PANEL 3" Grooved Pipe Connection Water Inlet COMP

4'-6" 1371mm 6'-6 3/8" 1991mm 6'-1" 1854mm 5 1/4" 133mm

3" Grooved Pipe Connection Water Outlet

1'-4 1/4" 413mm 3 5/8" DIA 92mm LINE VOLTAGE

LEFT SIDE VIEW


1 1/4" X 5 1/4" SLOT 32mm X 133mm CONTROL CONN. 1'-2" 356mm 7" 178mm

2 1/2" 64mm DIA HOLES (4) LIFTING LOCATIONS

5" 127mm

8'-7 1/2" 2629mm

FRONT VIEW

2' 6" 756mm

9-1/2" 241mm

5' 1528mm
1' 1" 336mm

Rear View Access Hole Locations

FLD = Furnished by Trane / Installed by Others

Trane Equipment Submittal

Page 8 of 17

Seminole County Services Air Cooled Chillers

February 02, 2006

Unit Dimensions - Air-Cooled Water Chillers (Large Tonnage) Item: A3 Qty: 3 Tag(s): CGAF-C60

2 3/4" 70mm 1 3/32" (4X) 30V MAX. 28mm

3 1/4" 83mm 3'-1 3/8" 949mm 3'-3 5/8" 1006mm 2'-11" 889mm 2'-9" 838mm 5 7/8" 149mm 1 3/32" (1X) HEAT TAPE POWER 28mm 3" CONDUIT MAIN POWER 76mm 9 3/4" 248mm 7 1/8" 181mm CONNECTIONS BOTTOM SEE DETAIL "A" 2 8 1/8" 206mm 4'-0 7/8" 1241mm 9'-5 7/8" 2892mm 4'-0 7/8" 1241mm

8'-0" 2438mm MINIMUM CLEARANCE

7'-4 3/8" 2245mm

3 5/8" 92mm 7'-1 5/8" 2175mm

DETAIL "A"
3'-5 3/4" 1060mm NO OBSTRUCTIONS AIR FLOW DOOR SWING 180

OPTIONAL DAMPER 1 2 3/4" 70mm 3 5 1 1/4" 32mm 8'-0" 2438mm MINIMUM CLEARANCE

1'-1 1/2" 343mm

3/4" DIA. X 6 MTG HOLES 19mm

TOP VIEW
CONTROL PANEL 4'-6" 1371mm 6'-6 3/8" 1991mm 6'-1" 1854mm 3 5/8" DIA 92mm LINE VOLTAGE

5 1/4" 133mm

3" Grooved Pipe Connection Water Inlet COMP 3" Grooved Pipe Connection Water Outlet

1'-4 1/4" 413mm

2 1/2" 64mm DIA HOLES (4) LIFTING LOCATIONS

LEFT SIDE VIEW

1 1/4" X 5 1/4" SLOT 32mm X 114mm CONTROL CONN. 1'-2" 356mm

7" 178mm

5" 127mm

8'-7 1/2" 2629mm

FRONT VIEW

2' 6" 756mm

9-1/2" 241mm

5' 1528mm
1' 1" 336mm

Rear View Access Hole Locations

FLD = Furnished by Trane / Installed by Others

Trane Equipment Submittal

Page 9 of 17

Seminole County Services Air Cooled Chillers

February 02, 2006

Weight, Clearance & Rigging Diagram - Air-Cooled Water Chillers (Large Tonnage) Item: A1 Qty: 1 Tag(s): CGAF-C25

84" TO TOP OF UNIT

WARNING!!!
TO PREVENT INJURY OR DEATH AND POSSIBLE EQUIPMENT DAMAGE, DO NOT USE CHAIN (CABLES) OR SLINGS EXCEPT AS SHOWN AND USE CABLES STRONG ENOUGH TO SUPPORT UNIT WEIGHT. TEST LIFT UNIT TO ENSURE PROPER BALANCE AND RIGGING.

96" FIELD SUPPLIED SPREADER BAR

NO OBSTRUCTION AIR FLOW

CLEARANCE 48" CLEARANCE 96"

CONTROL PANEL 2 1/2"X4 LIFTING HOLES

UNIT RIGGING

8 1/16"
2

72 1/4"
3

CLEARANCE 96" CLEARANCE 96" CONTROL PANEL DOOR SWING 180

57 1/2"

UNIT CLEARANCE
49 1/16"

FRONT OF UNIT

1 1/4"

UNIT MOUNTING POINT


29"
CONTROL PANEL

UNIT WEIGHT SHIPPING WEIGHT 2085.0 lb 1

UNIT MOUNTING POINTS 2 470.0 lb 3 490.0 lb 4 425.0 lb

CENTER OF GRAVITY AND UNIT WEIGHT

OPERATING WEIGHT 2085.0 lb 700.0 lb

NOTES:
1. OPERATING WEIGHT INCLUDES REFRIGERANT, OIL AND WATER. 2. SHIPPING WEIGHT INCLUDES REFRIGERANT AND OIL CHARGES. 3. IF THE UNIT IS INSTALLED IN A WELL, THE DEPTH OF THE WELL MUST NOT EXCEED THE HEIGHT OF THE UNIT. THE TOP OF THE UNIT MUST HAVE UNRESTRICTED AIRFLOW.

FLD = Furnished by Trane / Installed by Others

Trane Equipment Submittal

Page 10 of 17

Seminole County Services Air Cooled Chillers

February 02, 2006

Weight, Clearance & Rigging Diagram - Air-Cooled Water Chillers (Large Tonnage) Item: A2 Qty: 2 Tag(s): CGAF-C50

84" TO TOP OF UNIT

WARNING!!!
TO PREVENT INJURY OR DEATH AND POSSIBLE EQUIPMENT DAMAGE, DO NOT USE CHAIN (CABLES) OR SLINGS EXCEPT AS SHOWN AND USE CABLES STRONG ENOUGH TO SUPPORT UNIT WEIGHT. TEST LIFT UNIT TO ENSURE PROPER BALANCE AND RIGGING.

96" FIELD SUPPLIED SPREADER BAR NO OBSTRUCTION AIR FLOW

CLEARANCE 48" CLEARANCE 96"

CONTROL PANEL

2 1/2"X4 LIFTING HOLES

UNIT RIGGING

8 3/16" 48 7/8" 48 7/8"

6 CLEARANCE 96" CONTROL PANEL DOOR SWING 180

CLEARANCE 96"

UNIT CLEARANCE

85 5/8"

58"

FRONT OF UNIT

5
1 5/16" 46"

UNIT MOUNTING POINTS


CONTROL PANEL UNIT WEIGHT SHIPPING WEIGHT 3900.0 lb 1 2 715.0 lb UNIT MOUNTING POINTS 3 720.0 lb 4 750.0 lb 5 505.0 lb 6 525.0 lb

CENTER OF GRAVITY AND UNIT WEIGHT

OPERATING WEIGHT 3900.0 lb 685.0 lb

NOTES:
1. OPERATING WEIGHT INCLUDES REFRIGERANT, OIL AND WATER. 2. SHIPPING WEIGHT INCLUDES REFRIGERANT AND OIL CHARGES. 3. IF THE UNIT IS INSTALLED IN A WELL, THE DEPTH OF THE WELL MUST NOT EXCEED THE HEIGHT OF THE UNIT. THE TOP OF THE UNIT MUST HAVE UNRESTRICTED AIRFLOW.

FLD = Furnished by Trane / Installed by Others

Trane Equipment Submittal

Page 11 of 17

Seminole County Services Air Cooled Chillers

February 02, 2006

Weight, Clearance & Rigging Diagram - Air-Cooled Water Chillers (Large Tonnage) Item: A3 Qty: 3 Tag(s): CGAF-C60

84" TO TOP OF UNIT

WARNING!!!
TO PREVENT INJURY OR DEATH AND POSSIBLE EQUIPMENT DAMAGE, DO NOT USE CHAIN (CABLES) OR SLINGS EXCEPT AS SHOWN AND USE CABLES STRONG ENOUGH TO SUPPORT UNIT WEIGHT. TEST LIFT UNIT TO ENSURE PROPER BALANCE AND RIGGING.

96" FIELD SUPPLIED SPREADER BAR NO OBSTRUCTION AIR FLOW

CLEARANCE 96" CLEARANCE 96"

CONTROL PANEL

2 1/2"X4 LIFTING HOLES

UNIT RIGGING

8 3/16" 48 7/8" 48 7/8"

6 CLEARANCE 96" CONTROL PANEL DOOR SWING 180

CLEARANCE 96"

UNIT CLEARANCE

85 5/8"

58"

FRONT OF UNIT

5
1 5/16" 47"

UNIT MOUNTING POINTS


CONTROL PANEL UNIT WEIGHT SHIPPING WEIGHT 4865 in3 1 2 820.0 lb UNIT MOUNTING POINTS 3 855.0 lb 4 985.0 lb 5 985.0 lb 6 720.0 lb

CENTER OF GRAVITY AND UNIT WEIGHT

OPERATING WEIGHT 4885.0 lb 885.0 lb

NOTES:
1. OPERATING WEIGHT INCLUDES REFRIGERANT, OIL AND WATER. 2. SHIPPING WEIGHT INCLUDES REFRIGERANT AND OIL CHARGES. 3. IF THE UNIT IS INSTALLED IN A WELL, THE DEPTH OF THE WELL MUST NOT EXCEED THE HEIGHT OF THE UNIT. THE TOP OF THE UNIT MUST HAVE UNRESTRICTED AIRFLOW.

FLD = Furnished by Trane / Installed by Others

Trane Equipment Submittal

Page 12 of 17

Seminole County Services Air Cooled Chillers

February 02, 2006

Field Wiring - Air-Cooled Water Chillers (Large Tonnage) Item: A1 - A3 Qty: 6 Tag(s): CGAF-C25, CGAF-C50, CGAF-C60

WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING.
FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.

AVERTISSEMENT
VOLTAGE HASARDEUX!
DECONNECTEZ TOUTES LES SOURCES ELECTRIQUES INCLUANT LES DISJONCTEURS SITUES A DISTANCE AVANT D'EFFECTUER L'ENTRETIEN.
FAUTE DE DECONNECTER LA SOURCE ELECTRIQUE AVANT D'EFFECTUER L'ENTRETIEN PEUT ENTRAINER DES BLESSURES CORPORELLES SEVERES OU LA MORT.

CAUTION
USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT.

DEVICE PREFIX LOCATION CODE AREA


1 2 3 4 5 6

Notes:

LOCATION
CONTROL PANEL FAN SECTION COMPRESSOR SECTION EXTERNAL FACTORY MTD DEVICE CUSTOMER OR FIELD PROVIDED SHIP W/FIELD INSTALLED DEVICE IMPORTANT! DO NOT ENERGIZE UNIT UNTIL CHECK-OUT AND START-UP PROCEDURE HAS BEEN COMPLETED

2. Phantom lines indicate alternate circuitry or available sales options.

Connect to 24VAC Connect to 24VAC class 2 circuits only. class 2 circuits only.

ALARM OUTPUT

ICE MAKING OUTPUT

NC

COM

NO

NC

COM

NO

450

449

448

447

446

445

1TB5
1 2 3 4 5 6 7 8 9 10 11 445 446 447 448 449 450 495 496 497 498 499 500 12 501 13 502 14 503 15 533 16 534 17 537 18 538 19 20 21 22

FLD = Furnished by Trane / Installed by Others

Trane Equipment Submittal

Page 13 of 17

Seminole County Services Air Cooled Chillers

February 02, 2006

Field Wiring - Air-Cooled Water Chillers (Large Tonnage) Item: A1 - A3 Qty: 6 Tag(s): CGAF-C25, CGAF-C50, CGAF-C60

WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING.
FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.

AVERTISSEMENT
VOLTAGE HASARDEUX!
DECONNECTEZ TOUTES LES SOURCES ELECTRIQUES INCLUANT LES DISJONCTEURS SITUES A DISTANCE AVANT D'EFFECTUER L'ENTRETIEN.
FAUTE DE DECONNECTER LA SOURCE ELECTRIQUE AVANT D'EFFECTUER L'ENTRETIEN PEUT ENTRAINER DES BLESSURES CORPORELLES SEVERES OU LA MORT.

CAUTION
USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT.

DEVICE PREFIX LOCATION CODE AREA


1 2 3 4 5 6

LOCATION
CONTROL PANEL FAN SECTION COMPRESSOR SECTION EXTERNAL FACTORY MTD DEVICE CUSTOMER OR FIELD PROVIDED SHIP W/FIELD INSTALLED DEVICE

Use BAYSENS016, BAYSENS017 or equivalent.

IMPORTANT! DO NOT ENERGIZE UNIT UNTIL CHECK-OUT AND START-UP PROCEDURE HAS BEEN COMPLETED

5RT19 ICS DEFINED TEMP

424

425

1TB4
1 410 424 425 12 13 2 411 3 4 5 ICS CONTROLLED (CONNECT TO 24 VOLT CLASS 2 CIRCUIT ONLY) 414

436 14 403 15 435 16 431 17 434 18 438 19 437 20 21 22

6 415 NO COM NC 414 415 416 7 416 8 417

9 418 10 421 11 422

437

438

Contacts rated 12mA @ 24VDC minimum.

5K86 ICE BUILDING INITIATE

438

434

431

435

Remove jumper between 1tb4-16 & 17 when required, Contacts rated 12mA @ 24VDC minimum. Remove jumper between 1tb4-18 & 19 when required, Contacts rated 12mA @ 24VDC minimum.
5S67 EXTERNAL AUTO/STOP SWITCH 5S71 EMERGENCY STOP SWITCH

Notes:
2. Phantom lines indicate alternate circuitry or available sales options.

FLD = Furnished by Trane / Installed by Others

Trane Equipment Submittal

Page 14 of 17

Seminole County Services Air Cooled Chillers

February 02, 2006

Field Wiring - Air-Cooled Water Chillers (Large Tonnage) Item: A1 - A3 Qty: 6 Tag(s): CGAF-C25, CGAF-C50, CGAF-C60

WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING.
FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.

AVERTISSEMENT
VOLTAGE HASARDEUX!
DECONNECTEZ TOUTES LES SOURCES ELECTRIQUES INCLUANT LES DISJONCTEURS SITUES A DISTANCE AVANT D'EFFECTUER L'ENTRETIEN.
FAUTE DE DECONNECTER LA SOURCE ELECTRIQUE AVANT D'EFFECTUER L'ENTRETIEN PEUT ENTRAINER DES BLESSURES CORPORELLES SEVERES OU LA MORT. CUSTOMER CONNECTION WIRE RANGE

CAUTION
USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT.

NOTES
A. BLOCK SIZE & DISCONNECT SIZE ARE CALCULATED BY SELECTING THE SIZE GREATER THAN OR EQUAL TO 1.15 X (SUM OF UNIT LOADS). SEE UNIT LITERATURE FOR UNIT LOAD VALUES.

UNITS WITH MAIN POWER TERMINAL BLOCK (ALL VOLTAGES) BLOCK SIZE 335 AMP WIRE QTY. 1 CONNECTOR WIRE RANGE (1) #6 - 350 MCM

IMPORTANT! DO NOT ENERGIZE UNIT UNTIL CHECK-OUT AND START-UP PROCEDURE HAS BEEN COMPLETED

DEVICE PREFIX LOCATION CODE


SEE UNIT NAMEPLATE FOR LINE VOLTAGE L1 L2 L3 2 5K1 3 4 5 5B1 6 SHIP W/FIELD INSTALLED DEVICE FAN SECTION COMPRESSOR SECTION EXTERNAL FACTORY MTD DEVICE CUSTOMER OR FIELD PROVIDED

AREA
1

LOCATION
CONTROL PANEL

1TB6 1 5T1 5S1 2 5K1 5K1-OL 39 3 4 5 38 38 39 6 7 8 9 10 EQUIPMENT GROUND 1TB1 4HR1 - HEAT TAPE POWER WIRING 11 12

201

L2 115VAC/60HZ 15A MAX

DEVICE DESIGNATION
5B1 5K1 5K86 5K89 5RT19 5S1 5S67 5S71 5T1 CHILLER PUMP MOTOR CHILLED SOL PUMP STARTER ICE BUILDING INITIATE DEMAND LIMIT RELAY ICE DEFINED TEMP. SENSOR FUSED DISCONNECT EXTERNAL AUTO STOP SWITCH EMERGENCY STOP CONTROL TRANSFORMER TO 4HR1 HEAT TAPE 200 L1

1TB12

Notes:

2. Phantom lines indicate alternate circuitry or available sales options.

FLD = Furnished by Trane / Installed by Others

Trane Equipment Submittal

Page 15 of 17

Seminole County Services Air Cooled Chillers

February 02, 2006

Field Wiring - Air-Cooled Water Chillers (Large Tonnage) Item: A1 - A3 Qty: 6 Tag(s): CGAF-C25, CGAF-C50, CGAF-C60

WARNING
HAZARDOUS VOLTAGE!
DISCONNECT ALL ELECTRIC POWER INCLUDING REMOTE DISCONNECTS BEFORE SERVICING.
FAILURE TO DISCONNECT POWER BEFORE SERVICING CAN CAUSE SEVERE PERSONAL INJURY OR DEATH.

AVERTISSEMENT
VOLTAGE HASARDEUX!
DECONNECTEZ TOUTES LES SOURCES ELECTRIQUES INCLUANT LES DISJONCTEURS SITUES A DISTANCE AVANT D'EFFECTUER L'ENTRETIEN.
FAUTE DE DECONNECTER LA SOURCE ELECTRIQUE AVANT D'EFFECTUER L'ENTRETIEN PEUT ENTRAINER DES BLESSURES CORPORELLES SEVERES OU LA MORT.

CAUTION
USE COPPER CONDUCTORS ONLY! UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT OTHER TYPES OF CONDUCTORS. FAILURE TO DO SO MAY CAUSE DAMAGE TO THE EQUIPMENT.

DEVICE PREFIX LOCATION CODE AREA


1 2 3 4 5 6

Notes:

LOCATION
CONTROL PANEL FAN SECTION COMPRESSOR SECTION EXTERNAL FACTORY MTD DEVICE CUSTOMER OR FIELD PROVIDED SHIP W/FIELD INSTALLED DEVICE IMPORTANT! DO NOT ENERGIZE UNIT UNTIL CHECK-OUT AND START-UP PROCEDURE HAS BEEN COMPLETED

2. Phantom lines indicate alternate circuitry or available sales options.

Connect to 24VAC Connect to 24VAC class 2 circuits only. class 2 circuits only.

ALARM OUTPUT

ICE MAKING OUTPUT

NC

COM

NO

NC

COM

NO

450

449

448

447

446

445

1TB5
1 2 3 4 5 6 7 8 9 10 11 445 446 447 448 449 450 495 496 497 498 499 500 12 501 13 502 14 503 15 533 16 534 17 537 18 538 19 20 21 22

Wires are shielded twisted pair.

534

533

(-)

(+)

TRACER COMM (1U54)

FLD = Furnished by Trane / Installed by Others

Trane Equipment Submittal

Page 16 of 17

Seminole County Services Air Cooled Chillers

February 02, 2006

Field Installed Options - Part/Order Number Summary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job. Product Family - Air-Cooled Water Chillers (Large Tonnage) Item Tag(s) Qty Description A1 CGAF-C25 1 25 Ton Packaged Air-Cooled Chiller A2 CGAF-C50 2 50 Ton Packaged Air-Cooled Chiller A3 CGAF-C60 3 60 Ton Packaged Air-Cooled Chiller Field Installed Option Description Unit Spring Isolators

Model Number CGAFC25E CGAFC50E CGAFC60E Part/Ordering Number

FLD = Furnished by Trane / Installed by Others

Trane Equipment Submittal

Page 17 of 17