PSC9717

European Refrigeration Controls Catalogue Catalog Section 2 Product Bulletin W27 Issue 0102

Modular Electronic Humidity Control System

System 27 NOVA

Introduction
System 27 NOVA is a family of modular electronic modules designed for a wide variety of control configurations in refrigeration, heating, ventilation, air-conditioning and other related fields. The humidity control modules can be used as a stand alone device or in conjunction with other modules such as display modules, signal converter modules etc. to achieve a wide variety of single or multiple stage applications. Typical applications are: - computer rooms; - clean rooms; - fruit storage/ripening; - food processing; - industrial processes. System 27 NOVA Modular Humidity Controls

Description
The modular concept was specially designed to make control configuration easier and still offer the flexibility necessary to answer the many individual control requirements encountered today.

Feature and Benefits


q Modular design Provides the flexibility to realise the required control set up without redundancy and makes future expansion easy. Eliminates wiring between modules and reduces installation cost. Provides flexibility to match any combination of heating or cooling applications. Matches various applications.

q Plug-in quick connector wiring system q Adjustable differential and humidification/dehumidification setting q Interchangeable humidity transmitters with different housings q Attractive DIN-rail mount housing q Setpoint shift output function

Easy and quick to install. Modules can be used for multiple setpoint applications.

2001 Johnson Controls Inc. Order No. PD-W27-E

Catalogue Section 2

W27 Issue 0102

The System 27 NOVA family includes the following modules: W27 Humidity Control Modules These one- or two-stage humidity control modules can be used as a low cost control for stand alone applications or, when connected in parallel, for multistage applications. The control output(s)is a single-pole, double-throw (SPDT) relay with LED indication. It features humidification and dehumidification modes of operation and an adjustable differential. Sensors are available for room, duct or build-in applications. Please refer to the HT-9000 humidity sensor bulletin. HT-9000 Humidity Sensor

D27W Humidity Display Modules A display connected to a humidity control module gives a digital indication of the measured humidity or setpoint. It is also possible to connect a sensor directly to the D27W (the sensor is powered by the D27W). The display can be connected to a humidity control module very easy by using the quick connector system.

Note
The System 27 modules are intended to control equipment under normal operating conditions. Where failure or malfunction of the modules could lead to an abnormal operating condition that could cause personal injury or damage to the equipment or other property,other devices (limit or safety controls) or systems (alarm or supervisory systems) intended to warn of or protect against failure or malfunction of the modules must be incorporated into and maintained as part of the control system.

Y27M Signal Converter This module converts a voltage input signal to a standardised output signal of 0 to 10 Vdc or 4 to 20 mA. The input signal can either be obtained from a humidity sensor or a humidity control module. The signal converter can be used for those applications where an analogue output is required. Such as; to a motor, motor actuated valve, recorder etc.

Application examples
At page 6 you will find some applications examples. For more detailed information about wiring and adjustment reference should be made to the installation sheets.

Repair and Replacement

Repair is not possible. In case of an improperly functioning control, please check with your nearest supplier. When contacting the supplier for a replacement you should state the type-model number of the control. This number can be found on the dataplate.

Catalogue Section 2

2001 Johnson Controls Inc. Order No. PD-W27-E

W27 Issue 0102

Accessories dim. in mm

30

Fig. 1 WRE027N600 Quick Connector for connecting System 27 NOVA modules.

Dimensions (mm)

118

45 12 43 53 5

83 27 20 70

Fig. 2 System 27 NOVA Modules

2001 Johnson Controls Inc. Order No. PD-W27-E

Catalogue Section 2

W27 Issue 0102

Type Number Selection Table


W27 Humidity Control Modules
One Stage Humidistat Order number W27N11 W27N21 Power supply 24 V ac/dc 230 V ac Setpoint range 10 to 100% R.H. Additional * Mode: field adjustable * Differential: 2 to 10% R.H. * SPDT contact 10(5)A 250 V ac * Setpoint shift: 0 to 20% R.H.

Two Stage Humidistat Order number W27N12 W27N22 Power supply 24 V ac/dc 230 V ac Setpoint range 10 to 100% R.H. Additional features * Mode: field adjustable * Differential: 2 to 10% R.H. * 2x SPDT contact 10(5)A 250V ac * Setpoint shift: 0 to 20% R.H.

Humidity Display Modules Order number D27W1N4 D27W2N4 Power supply 24 V ac 230 V ac Additional features * Can be used as stand alone or in conjunction with a humidity control module * Display range: 0 to 100% R.H

Y27M Signal Converter Order number Y27M1 Y27M2 Power supply 24 V ac 230 V ac Setpoint range (V) 0 to 10 0 to 10 Span range (V) 0 to 10 0 to 10

Catalogue Section 2

2001 Johnson Controls Inc. Order No. PD-W27-E

W27 Issue 0102

Wiring & Adjustments


One-stage Humidistat W27Nx1 Two-stage Humidistat W27Nx2

A B C S
Mode selector Mode selector on on Diff . Diff. Setp.

Mode selector on Diff.


Diff.
A B C S R Setpoint

off off Diff. on 1 stage 2

Setpoint
A B C S R

off Diff.

off

on

off Setpoint off Setp. 1 2 stage

on

6 7

3 4

Humidity/Display module D27WxN4

Signal Converter Module Y27Mx

Com mon Volt age out put Curren t out put

A B C MN

Span ad j. Outp ut 4 mA/0V

Reading out a humidistat


A B C S

DA RA

20 mA/10 V

B C M N

Input

Reading out a sensor (stand alone)


Reve rse acting 2 0 m A/10V
1 2

20 mA /10V Output 4 mA/0V

4 mA/0V

Set point I nput adj. Direct acting

2001 Johnson Controls Inc. Order No. PD-W27-E

Catalogue Section 2

W27 Issue 0102

Applications
Two stage humidity control with readout Three stage humidity control

A B C S R

A B C S R

A B C S R

A B C S

4 5

1 2

7 8

3 4 5

1 2

4 5

1 2

7 8

~ ~ 0 Stage 1 Stage 2 0 St age 1 Stage 2 Stage 3

One stage humidity control with read-out and analogue out-put

0 to 10V analogue output

A B C S R

A B C S

M N

3 4

1 2

~ 0 Humidification or Dehumidification

Catalogue Section 2

2001 Johnson Controls Inc. Order No. PD-W27-E

W27 Issue 0102

Notes

2001 Johnson Controls Inc. Order No. PD-W27-E

Catalogue Section 2

W27 Issue 0102

Specifications
General System 27 NOVA
Outtput relay rating Operating ambient temperature Storage temperature Operating (storage) R.H. Terminals Power supply SPDT 10(5)A 250 V ac 10 A 30 V dc -10 to +50 C -40 to +70 C 10 to 90 % R.H. (non condensing) screw type max. wire thickness 2,5 mm2 230 V ac +10% / -15% ; 50/60 Hz 24 V ac/dc +10% / -15% ; 50/60 Hz

Additional specification for display modules


Power supply Resolution Accuracy 230 V ac +10% / -15% ; 50/60 Hz 24 V ac +10% / -15% ; 50/60 Hz 1% R.H. 2% R.H.

Signal converter
Power supply Output load 230 V ac +10% / -15% ; 50/60 Hz 24 V ac +10% / -15% ; 50/60 Hz voltage output Rmin = 1 k current output Rmax = 500

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office or representative. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products.

Johnson Controls International, Inc.


Headquarters: European Headquarters: European Factories: Branch Offices: Milwaukee, WI, USA Westendhof 8, 45143 Essen, Germany Lomagna (Italy), Leeuwarden (The Netherlands) and Essen (Germany) Principal European Cities.
Printed in Europe

This document is subject to change

Catalogue Section 2

2001 Johnson Controls Inc. Order No. PD-W27-E