Sei sulla pagina 1di 94

They trust us

VTS worldwide

made of expectations

VTS HQ Sp. z o.o.


6b uycka Str.
81-537 Gdynia, Poland
tel. + 48 58 628 13 54
fax + 48 58 628 13 22
vtsgroup@vtsgroup.com

www.vtsgroup.com

EN

Catalogue
Air Handling Units

Climate parameters
Country

VTS Polska
Al. Sikorskiego 11
02-758 Warszawa
Tel.: +48 22 4313700
Fax: +48 22 4313714
warszawa@vtsgroup.com

VTS Czech Republic


Tel.: +420 241 443 839
Fax: +420 241 444 118
VTS Slovakia
Tel.: +421 02 43 33 96 84
Fax: +421 02 44 63 06 39
VTS Hungary
Hungria krt. 162., Hermina Business Tower B
1146 Budapest
Tel.: +36 1 436 0100
Fax: +36 1 439 1636
E-mail: budapest@vtsgroup.com

VTS Ukraine
Sholudenko 3 ofce 373
04116 Kiev
Tel.: +38 044 230-4760
Fax: +380 44 230-4760
E-mail: kiev@vtsgroup.com

VTS Lithuania
Perknkiemio g. 4A
12128 Vilnius
Tel: +370 5 2636152
Fax: +370 5 2636156
e-mail: vilnius@vtsgroup.com

VTS India
VTS TF Air Systems Pvt Ltd
855, 3rd Cross, 11th Main
HAL 2nd Stage Indiranagar
Bangalore 560 008
Tel : +080 25213418 / 19
Fax : +080 25272423
E-mail: india@vtsgroup.com

VTS China
21st oor World Plaza, No. 855 South Pudong
Road
200120 Shanghai
Tel.: +86 21 5119 6890
Fax: +86 21 5119 6891
E-mail: shanghai@vtsgroup.com

VTS Latvia
Ganibu dambis 24a
LV 1005 Riga
Tel.: +371 7382530
Fax: +371 7395241
E-mail: riga@vtsgroup.com

VTS Kazakhstan
32A Manas Street, Ofce 502 B
050008 Almaty
Tel: +7 3272 378488
Fax: +7 3272 378487
E-mail: almaty@vtsgroup.com

VTS Russia
13 Rusakovskaya str.
Borodino Plaza
107140 Moscow Russia
Tel: +7 495 981 95 52
Fax: +7 495 981 95 53
moscow@vtsgroup.com

VTS UAE
Al Garhoud, Al Sayegh Building, Ofce 105
P BOX #76849.O.
Dubai
Tel.: +971 (4) 2869560
Fax: +971 (4) 2869561
E-mail: dubai@vtsgroup.com

www.vtsgroup.com

Above sea

Pressure

level [m]

[kPa]

55
7

100.67
101.24

366
246
256

97
98.4
98.29

Summer
Temperature

Enthalpy

Optional functions and accessories

Winter
Relative
Temperature Enthalpy
humidity [%]*
[kJ/kg]
[C]

Relative
humidity [%]*

[C]

[kJ/kg]

34.2
34.4

64
87.3

34
59

-10.4
-3.7

90
90

30
29
29

54.1
56.2
53.2

34
37
37

-12
-12
-15

95
95
95

23.5

51.1

59

-22

-20.7

100

91.56
97.33

31.2
31

54.4
51.1

30
26

-25
-35

-24.4
-35.2

100
100

156
10

99.46
101.2

26.1
23.8

53.2
52.2

48
60

-23
-20

-21.9
-18.2

100
100

VS

LH
[mm]

mH
[kg]

VS

LE
[mm]

LS
[mm]

mS
[kg]

24.3

51.1

56

-20

-18.8

100

h2 x w2
[mm]

VS

101.29

hxw
[mm]

mE
[kg]

10

731

31

10

731

220x500

22

10

731

26

49
113
16
529

100.74
99.97
101.13
95.13

32
33
31
32

62.9
65.8
60.4
64.5

40
40
40
40

-14
-12
-12
-16

90
90
90
90

15

731

37

15

731

250x660

25

15

731

21

731

44

21

731

313x821

220x500

33

21

1097

30

731

49

30

731

440x821

220x500

36

30

1097

40

731

56

40

731

440x1028

250x660

40

40

1097

79

55

731

67

55

731

575x1199

440x821

47

55

1097

101

75

731

75

75

731

695x1340 440x1028

54

75

1097

116

100

731

86

100

731

795x1520 575x1199

60

100

1097

141

120

731

94

120

731

832x1751 575x1199

150

731

105

150*

731/1097

933x1945 795x1520

180

731

121

180*

731/1097 1137x1945 795x1520

230

731

133

230*

731/1097 1137x2353 933x1945

300

731

149

300*

731/1097 1436x2445 933x1945

400

731

182

400*

731/1097 1669x2945 933x2650

500

500*

650

650*

Peking
Shanghai

CZECH
REPUBLIC

Prague
Brno
Ostrava

ESTONIA

Tallin

KAZAKHSTAN

Alma-ata
Astana

847
348

LITHUANIA

Vilnius
Klaipeda

LATVIA

Riga

GERMANY

Berlin
Frankfurt
Hamburg
Munich

44

100.8

Warsaw
Gdansk
Krakow
Przemysl
Suwalki

107
38
237
280
186

100.05
99.68
98.51
98.01
99.11

30
28
30
30
30

60
59.9
60
60
60

45
52
45
45
45

-20
-16
-20
-20
-24

-18.4
-13.4
-18.4
-18.4
-22.6

100
100
100
100
100

Moscow
St. Petersburg
Samara
Kazan
Jekaterynburg
Krasnodar
Rostov
Nizni Novogrod
Krasnoiarsk
Irkutsk
Vladivostok
Omsk
Perm
Novosybirsk
Murmansk

156
4
44
116
237
33
77
82
277
513
184
123
172
177
51

99.46
101.28
100.8
99.94
97
100.93
100.4
100.34
98.04
95.31
99.13
99.86
99.28
99.22
100.71

28.5
24.8
29.7
27.3
28.7
30.8
31.9
26.8
25.9
26.9
23.4
27.7
26.3
28.4
22

54
51.5
55.3
54.8
51.1
63.6
60.7
54.9
51.9
53.6
61.5
53.6
53.2
54.8
42.7

40
52
38
46
34
46
38
49
46
45
81
42
48
41
49

-26
-26
-30
-32
-35
-19
-32
-30
-40
-37
-24
-37
-35
-39
-27

-25.3
-25.3
-29
-31.7
-34.6
-17.6
-20.9
29.7
-40.2
-37.1
25.3
-36.8
-34.9
-38.9
-26.6

100
100
100
100
100
100
100
100
100
100
100
100
100
100
100

SLOVAKIA

Bratislava
Kosice

130
232

99.7
98.57

UKRAINE

Kiev
Doneck
Odessa
Dnepropietrovsk
Lvov

168
226
35
142
366

99.32
98.64
100.91
99.63
97

POLAND

RUSSIA
VTS Romania
Strada George Baritiu, nr 33, sector 1
011295 Bucuresti
Tel: +40 31 425 44 55
Fax: +40 31 425 44 56
E-mail: romania@vtsgroup.com

Town

CHINA

NElectric
pre-heater

E
empty section

S
silencer

LH

31
60
68

65

120

1097

159

72/116

150

1097

178

81/132

180

1097

205

89/148

230

1097

243

100/171

300

1463

345

125/217

400

1463

510

731/1097 1669x3445 933x3150

136/241

500

1463

580

731/1097 2146x3557 933x3250

150/280

650

1463

702

* Data regarding length and weight refers to the empty section with a horizontal or a top/bottom inlet/outlet respectively.

F
secondary
lter

M
mixing box

32
31

58.2
59.8

34
39

-12
-12

95
95

VS

LM
[mm]

h2 x w2
[mm]

h3 x w3
[mm]

mM
[kg]

VS

LF
[mm]

10

10

28.7
31.8
28.6
31
26.4

56.1
58.6
62
57.4
57.4

43
34
53
36
54

-22
-25
-18
-23
-19

-20.7
-24.3
-18.3
-22
-17.6

100
100
100
100
100

15

15

21

731

220x500

213x380

40

21

731

39

30

731

220x500

313x380

43

30

731

43

40

731

250x660

313x380

49

40

731

47

55

731

440x821

413x380

62

55

731

57

731

73

69

HUNGARY

Budapest

185

99.12

32

63.9

40

-15

90

UNITED
ARAB
EMIRATES

Abu-Dhabi
Dubai

27
5

101
101.26

46
46

96.6
96.6

30
30

12
13

27
27

70
70

EUROPE

Optional functions

Bucharest
Paris
Amsterdam
Minsk
Vienna
London

91
109
-2
234
200
24

100.24
100.02
101.35
98.55
98.95
101.04

33
29.8
28
25.9
32
27.4

64.5
60.4
58.5
53.6
63.6
53.4

Amman
Riyadh
Muscat
Kuwait
Bombay
Delhi
Washington
Montreal
Doha

773
612
15
55
14
216
20
82
42

92.38
94.19
101.14
100.67
101.16
98.75
101.08
100.34
101.26

42
47
54
47
35
41.7
34.8
28.8
46

97.7
80.7
130.8
100.6
67.7
65
75.2
62.6
96.6

40
18
30
30
35
17
44
52
30

2
8
17
5
19
8
-9.3
-26.9
13

70
50
30
30
70
63
90
90
70

mF
[kg]
-

440x1028

413x380

75

731

731

575x1199

613x380

85

100

731

120

731

575x1199

613x380

91

120

731

150

1097

795x1520

713x740

126

150

731

94

180

1097

795x1520

913x740

155

180

731

106

230

1097

933x1945

913x740

188

230

731

117

300

1097

202

300

731

140

400

1097

252

400

731

181

500

1097

282

500

731

200

650

1097

304

650

731

230

75
100

933x2650 1513x740
933x3250 1913x740

Accessories

AD - air damper

78
83

Index
VTS

VENTUS Air Handling Units

A corporation with European tradition ............................... 2

General description ........................................................... 12

A trustworthy brand ........................................................... 3

How to select an AHU? ...................................................... 13

VENTUS made of expectations ........................................... 4

Symbols and labels ............................................................. 14

Wide scope of possibilities ................................................ 5

Base AHUs and optional functions ...................................... 15

We design for you .............................................................. 6

Quick selection ................................................................... 16

ClimaCAD On-Line ............................................................. 7

Navigation .......................................................................... 20

Guarantee of quality ........................................................... 8

Base VENTUS AHUs ........................................................... 21

Feel the difference .............................................................. 9

Supply AHUs ...................................................................... 21


Exhaust AHUs ..................................................................... 25
Supply-exhaust AHUs ......................................................... 27
Optional functions .............................................................. 53
Components ...................................................................... 54
Casing ................................................................................. 54
Filters .................................................................................. 56
Heaters ............................................................................... 58
Coolers ............................................................................... 60
Energy Recovery ................................................................. 62
Fan sets ............................................................................... 64
Mixing box, Silencers .......................................................... 66
Accessories ......................................................................... 68

Automation
Control elements ................................................................ 72
Control applications ............................................................ 78

Psychrometric chart ............................................................ 92


Optional functions, accessories .. bookmark

VTS
Latvia
VTS
VTS
Lithuania Estonia
VTS
Belarus
VTS
VTS
Poland
Ukraine

VTS
Kazakhstan

VTS
Russia

VTS
Czech
Republic

VTS
Slovakia

VTS
Romania

VTS
Hungary
VTS
China

VTS
United
Arab Emirates
VTS
India

A corporation with European tradition


VTS Group is a leading supplier in the ventilation and air conditioning trade. We create and implement innovative
and technologically advanced solutions for all types of industrial facilities, commercial institutions and hotels.
We have been providing people in 19 countries with perfect atmosphere for 20 years now. We are an international company
with European roots and tradition of reliable quality.

We monitor the market in detail and react to its changes immediately. Hence we are able to provide our clients with the best
solutions that are perfectly tailored to their needs.

Latitude or climate are not important. Our ventilation and air handling units guarantee comfort regardless
of a facilitys location. We are real experts in good climate

A trustworthy brand

The quality and parameters of VTS devices are conrmed by international Eurovent and TV certicates. We comply with
all requirements stemming from European (CE) product safety standards as well as the integrated quality and environment
protection system ISO 9001/ISO 14001.

Eurovent

ISO 9001, ISO 14001

It conrms the conformity of


parameters of selected devices,
calculated with the use of the Clima
CAD On-Line (CCOL) application,
with real operating parameters.

ISO 9001 guarantees complete


repeatability of all VTS devices.
ISO 14001 conrms an efcient
environment management
system.

EN 1886, EN 13053

CE

Two major European standards


describing the performance and
mechanical characteristics of Air
Handling Units.

VTS devices comply with the


safety standards in accordance
with the European Unions
guidelines.

VENTUS made of expectations


VENTUS is a type-line of ventilation and air conditioning units offered by VTS Group. The functionality and application of
the product reect market demand and are the effect of intensive work of some experienced specialists in the trade. The
AHU was designed with the use of state-of-the-art technologies, advanced material engineering and completely innovative
constructional solutions. Due to that the AHU is reliable, energy-saving and fully adjusted to the expectations of the market.

We look at our AHUs from the angle of our Clients needs. They can be applied regardless of weather conditions or
geographical zones. Designing devices is incredibly simple thanks to our technical and commercial advisers as well
as the ClimaCAD tool that makes it possible to prepare an AHU specication in just 4 steps. We have optimized
the process of delivering AHUs to the construction site and created a team of qualied specialists to assemble them.
We want the operation of devices to produce some notable benets. Hence our special attention to energy recovery of
our devices reaching up to 85%!
That is why VENTUS type-line is made of expectations.

Wide scope of possibilities


Wide performance range
As many as 16 sizes!
Adjusting an AHU size to the
cubic capacity of a particular
building

Frameless casing
Operation in different climatic
zones (-40 to +70C)
Lack of thermal bridges
elimination of moist condensation
Durability for years sandwich
type panels with polyurethane foam

Small dimensions of
a device
Low AHUs minimum height
is only 36cm!

Air treatment function


Adjustment of air treatment
functions to a required
microclimate

Adaptation to technical and utility


rooms, ventilation ducts

We design for you

Technical and commercial adviser


Top class specialists in the trade are ready to design an AHU adapted to your design.
Extensive network of commercial ofces makes us more accessible.
We provide advice and assistance during the whole process of selecting and purchasing a particular device.

ClimaCAD On-Line
Our Clients can design an AHU themselves using a tool available at www.vtsgroup.com
Designing an AHU involves 4 steps of selection and 10 seconds of calculation
Calculations in the analytical module with alternative results + indicating an optimum solution

ClimaCAD On-Line

Step 1 selection of a base AHU

Step 2 selection of optional functions and parameters

Step 3 selection of an AHU from among several


alternative options

Step 4 a ready AHU with a complete set of technical data

www.vtsgroup.com

Guarantee of quality

We care for quality on all stages of work with the product starting from AHU design through production to service
assistance. VENTUS is always delivered by professional forwarders fully responsible for the quality of transport.
We make sure that our ventilation and air conditioning units are always assembled by highly qualied services.
Assembly is included as standard and we are responsible for performing services of the highest quality possible.

VTS Group has prepared a network of authorized service centers to work with the product.
Their assistance is available 24 hours a day they are always at our Clients disposal.

We guarantee appropriate operation of our VENTUS


ventilation and air conditioning AHUs.

Feel the difference

Silent operation of AHUs


The PLUG fan set with
frequency converter
Different fan sizes for one
AHU size
Improved shape of fan blades

Simple control
HMI (Human Machine Interface)
Simple and clear interface
Reading out and setting up
operation parameters from any
location in a building
Communication with
any number of AHUs

Energy recovery
Different types of energy recovery
Efciency up to 85%
Separation of the exhaust air
stream from the supply air stream
Sensible and latent heat
recovery

BMS
(Building Management System)
Automation open for overriding
control system
Monitoring of devices
performance from any place

Air Handling Units

10

VENTUS Air Handling Units


General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
How to select an AHU? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Symbols and labels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Base AHUs and optional functions . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Quick selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Supply AHUs
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Heating, Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Heating, Cooling, Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Exhaust AHUs
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Filtration, Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Supply-exhaust AHUs: cross-ow exchanger
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Heating, Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Heating, Cooling, Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Supply-exhaust AHUs: rotary exchanger
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Heating, Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Heating, Cooling, Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Supply-exhaust AHUs: glycol system
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Heating, Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Optional functions and accessories . . . . . . . . . . . . . . . . . . . . . . . . 53
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Control elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Control applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

Due to continuous improvement of the product VTS reserves its rights to implement
modications.
Some technical specication as well as descriptions may differ from the actual state.
Before placing an order technical specication and operation parameters of particular devices
should be conrmed with a VTS representative.

VS 21650

VS 1015

Capacity:

400 100 000 [m3 /h]


Functions:
A

Sizes:

10

180

12

230

15

300

21

30

40

400

55

75

100

500

120

150

650

How to select an AHU?


1
Start with the Quick selection page (p. 16-19):
choose a type and a size of an AHU;
check which AHUs provide a capacity you are
interested in;
choose the optimal one on the basis of air
ow speed through the units window, taking
the most important function into
consideration;
read the size of the unit , e.g. VS 21.

Airow [m3/h]

Dimensions

VS unit 's size

2000

H Hs Hf W H2 H2s H2f W2 Hi Wi Ai Hf Hs

4000

6000

[mm] [mm] [mm] [mm] [mm] [mm] [m2] [mm] [mm] [mm] [m2] [mm] [mm]
2

0,7 1
10

360

660

1330 280

580 0,16

3 3,4 [m/s]

-1960 [m3/h]

400
0,7 1
15

390

800

1610 310

720 0,22

3,6 [m/s]

-2900 [m3/h]

600

1
21

488 544* 961

544 936 992

368 881 0,32 40

3 3,1 [m/s]

96
3658 [m3/h]

1167

3 3,2 [m/s]

2
On the Navigation page (p. 20):

FUNCTION

PAGE NUMBER

AHU TYPE

nd a base unit which is equipped with


functions you are interested in and the
corresponding automatics;
move to an appropriate page.

AHUs

AUTOMATICS

VS 1015 VS 21650 VS 1015 VS 21650

SUPPLY AHUs
Heating

21

Cooling

23

Heating, Cooling
Heating, Cooling, Heating

21

78

22

79

23

80

24

EXHAUST AHUs
25

25

81

26

26

81

27

27

Ventilation

SUPPLY EXHAUST AHUs


82

84

3
VS 21650 sizes

On the page with a description of an AHU:


choose the access side;
choose optional functions and accessories;
read the parameters for the chosen size of
a base AHU as well as optional functions
(tables for optional functions are presented
on page 53 and on the bookmark).

HxW

HxW

Hf

Hf

VS -

VS -

- R - HC

L
[mm]

HH f*
(H(s) / (H(f)) (H(s) / (H(f))
[mm][mm]

L*
[mm]

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax
[m3/h]

Vmax
[CFM]

10

436

257

1160

683

1124 / 1490*

15

648

381

1740

1024

1490

21

1167

687

2200

1295

1856

2221

30

1586

933

3100

1825

1856

2221

620 / 676 Hf*

40 / 96Hf*

961

40

1958

1152

4100

2413

1856

2221

620 / 676 Hf*

40 / 96Hf*

1168

55

2878

1694

6054

3563

2221

2587

755 / 811Hf*

40 / 96Hf*

1339

575x1199

360

W
[mm]

- R - CH

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

660

220x500

220x500

390

800

250x660

250x660

488 / 544Hf*

40 / 96Hf*

961

313x821

313x821

250x660

440x821

440x821

380x613

440x1028

440x1028

440x821

575x1199

440x1028

4
Write down the code of an AHU down and check
the information concerning a recommended
control application.

VS -

21

size of an AHU

access side
R - right
L - left

SE
optional
functions
before a base
AHU

HC
code of a base
AHU

EF
optional
functions
behind a base
AHU

A
80

Detailed technical specication is available in ClimaCAD On-Line application at www.vtsgroup.com.


If you want to order a selected unit, get in touch with our Sales and technical adviser.

13

Symbols and labels


Basic functions of a base AHU

Optional functions

V - Ventilator

N - Electric pre-heater

F - pre-Filter

E - Empty section

H - Heater: water, electric

S - Silencer

C - Cooler: water, with direct expansion

F - Secondary Filter

P - Plate cross-ow recuperator

M - Mixing box

Accessories
FC - Flexible Connection
R - Rotary regenerator

AD - Air Damper

Miscellaneous
G - Glycol system (Run-around coil)

CCOL - ClimaCAD On-Line


order of exchangers in a unit
(heater, cooler)

View of an AHU

order of exchangers in a unit


(cooler, heater)

from a side: VS 10650


from the top: VS 1015
from a side: VS 21650
(a dominating function in a lower module)

14

80

page symbol

Automatics

units inlet

units outlet

Base AHUs and optional functions


Base AHU

Optional functions

Cross-ow exchanger

Rotary exchanger

Glycol system

N
p. 62

p. 62

p. 58

p. 62

E
Fan

Pre-lter

p. 64

p. 56

p. 66

F
p. 56

M
p. 66

VS -

- R - RHC

Accessories
Water cooler
Water heater
p. 60
p. 58

FC

AD

p. 68

p. 68

Direct expansion coil

Electric heater

Automation
p. 60

p. 58

p. 78

Coding system

VS -

75

size of an AHU

access side
R - right
L - left

SE
optional
functions placed
before a base unit

RHC
code of a base
AHU

EF
optional
functions placed
behind a base
unit

T the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

15

Quick selection
Airow [m3/h]

Dimensions

VS unit 's
size

H*H2*Hs *
W HW2 Hi Wi Ai HH(min)/H(max) [mm] 2(min)/H2(max) [mm] [mm] [mm]
[m2] s(min)
[mm] /Hs(max)
[mm]
[mm]

2000

10

360

660

1330 280

580 0,16

1960 [m3/h]

400

0,7 1

15

390

800

1610 310

3,6 [m/s]

720 0,22

2900 [m3/h]

600

21

528 / 544

961

976 / 992

368

881 0,32

3 3,1 [m/s]

80 / 96
3658 [m3/h]

1167

30

660 / 676

961

1240 / 1256

500

881 0,44

3 3,2 [m/s]

80 / 96
5118 [m3/h]

1586

40

660 / 676

1161

1240 / 1256

6000

3 3,4 [m/s]

0,7 1

4000

500 1088 0,54

80 / 96
6700 [m3/h]

1958

55

795 / 811

1339

1510 / 1526

635 1259 0,80

80 / 96

75

915 / 931

1480

1750 / 1766

755 1400 1,06

80 / 96

100

1015 / 1031

1660

1950 / 1966

855 1580 1,35

80 / 96

* - heights options details on page 54


Construction of a unit
H, H(min) / H(max) height of a unit,
minimal / maximal
VS 1015
W - width of a unit
H2, H2(min) / H2(max) - height of an integrated
Legend:
unit, minimal / maximal
Hi - height of a units cross section
H H
Wi - width of a units cross section
Ai - cross section of the window inside a unit
W
Hs, Hs(min) / Hs(max) - height of an units support, W
minimal / maximal

VS 21650

Hs

16

3,4 [m/s]

Wi

VS 1015

Hi H

VS 21650

H2

W2

Hs

W
W

Airow [m3/h]
4000

6000

8000

VS unit 's
size

10 000

12 000

14 000

16 000

18 000

10

v - air velocity in cross section of a unit Ai

[m/s]

cooler's operation range


water heater's operation range
lter's operation range

Vmax

Vmin

15

[m3/h]

V - unit's airow

21

optimum air velocity in a unit's cross section


= 2.6m/s in exchanger's cross section
30

40

3,4 [m/s]

55
9720 [m3/h]

2878

3,5 [m/s]

75
13 470 [m3/h]

3805

3,6 [m/s]

100
17 620 [m3/h]

4863

Maximum air velocity vmax [m/s]


functions

velocity in a units cross section

3,6

3,0

3,5

3,6

2,3

2,3

3,6

3,6

velocity in a component's cross


section

4,3

3,5

4,4

4,5

2,8

2,8

4,5

5,2

17

Airow [m3/h]

Dimensions

VS unit 's
size

H*H2*Hs *
5000
W HW2 Hi Wi Ai HH(min)/H(max) [mm] 2(min)/H2(max) [mm] [mm] [mm]
[m2] s(min)
[mm] /Hs(max)
[mm]
[mm]

10 000

120

1052 / 1068

1891

2024 / 2040

892 1811 1,62

15 000

20 000

2085

2226 / 2242

2085

2714

3,7[m/s]

26 558 [m3/h]

1197 2005 2,40

32 246 [m3/h]

1
1357

2493

2714

3,7 [m/s]

80
8640

230

1197 2413 2,89

3,8[m/s]

80
39 630 [m3/h]

10 398

300

1656

2585

3312

1496 2505 3,75

80

400

1889

3085

3778

1729 3005 5,20

80

500

1889

3585

3778

1729 3505 6,06

80

650

2366

3697

4732

2206 3617 7,98

80

* - heights options details on page 54


Construction of a unit
H, H(min) / H(max) height of a unit,
minimal / maximal
VS 1015
W - width of a unit
H2, H2(min) / H2(max) - height of an integrated
Legend:
unit, minimal / maximal
Hi - height of a units cross section
H H
Wi - width of a units cross section
Ai - cross section of the window inside a unit
W
Hs, Hs(min) / Hs(max) - height of an units support, W
minimal / maximal

VS 21650

Hs

18

45 000

80 / 96

993 2005 1,99

1357

40 000

21 410[m3/h]

7167

180

35 000

80 / 96

1153 / 1169

30 000

3,7[m/s]

5815

150

25 000

Wi

VS 1015

Hi H

VS 21650

H2

W2

Hs

W
W

Airow [m3/h]
10 000

20 000

30 000

40 000

50 000

VS unit 's
size

60 000

70 000

80 000

90 000

100 000

120

v - air velocity in cross section of a unit Ai

[m/s]

cooler's operation range


water heater's operation range
lter's operation range

Vmax

Vmin

150

[m3/h]

V - unit's airow

180

optimum air velocity in a unit's cross section


= 2.6m/s in exchanger's cross section
230

3,9 [m/s]

300
53 010 [m3/h]

13 491

3,3 [m/s]

400
62646 [m3/h]

18 704

3,6 [m/s]

500
79 350 [m3/h]

21 817

3,5 [m/s]

650
100 000 [m3/h]

28 725

Maximum air velocity vmax [m/s]


functions

velocity in a units cross section

3,6

3,0

3,5

3,6

2,3

2,3

3,6

3,6

velocity in a component's cross


section

4,3

3,5

4,4

4,5

2,8

2,8

4,5

5,2

19

Navigation
FUNCTION

PAGE NUMBER

AHU TYPE

AHUs

AUTOMATICS

VS 1015 VS 21650 VS 1015 VS 21650

SUPPLY AHUs
21

Heating
Cooling

23

Heating, Cooling

21

79

22

80

23

81

24

Heating, Cooling, Heating

EXHAUST AHUs
25

25

82

26

26

82

27

27

Ventilation

SUPPLY EXHAUST AHUs

Ventilation

29, 31
Heating

84

86

41

89

52

91

29, 30, 31

84

86

42, 43

89

50

91

32, 33, 34

85

87

Cooling

90

44, 45
35, 37

35, 36, 37

85

46, 47

Heating, Cooling

51
38, 39, 40
Heating, Cooling, Heating

48, 49

OPTIONAL FUNCTIONS:
* VS 1015 AHUs are available as indoor units only.
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.

V MAX parameters are specified for the following:


VS 10 equipped with the fan set and a motor with the following parameters n= 2790 rpm, P=0,55 kW,
VS 15 equipped with the fan set and a motor with the following parameters n=2850 rpm, P=0,75 kW,
VS 21VS 150 equipped with fan sets with direct drive,
VS 180VS 300 equipped with double fan sets (direct driven),
VS 400VS 500 equipped with triple fan sets (direct driven),
VS 650 - equipped with fourfold fan sets (direct driven).
VTS reserves the right to make a changes in product.

20

Detailed specication is available in the CLIMA-CAD on-line selection application at www.vtsgroup.com

87
90

Supply AHUs
Heating

Base AHU

79

VS 1015 sizes (suspended)*

HxW

VS -

- R -H- T

VS 21650 sizes

HxW

Hs
L

VS -

- R -H

VS 21150 sizes COMPACT

HxW

Hs

Lf

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax*
[m3/h]

10

436

257

15

648

381

21

1167

687

30

1586

40

1958

55

2878

H*Hs*
(H(min) / (H(max)) (Hs(min) / (Hs(max))
[mm][mm]

VS

L
[mm]

L2R
[mm]

Lf
[mm]

21

1124

1124

92

30

1124

1124

92

40

1124

1124

92

55

1490

1124

92

75

1490

1490

92

100

1856

1490

92

120

1856

1490

92

150

1856

1490

92

Vmax*
[CFM]

L
[mm]

W
[mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

1655

974

758 / 1124*

360

2462

1449

758 / 1124*

390

660

220x500

220x500

800

250x660

250x660

3080

1813

1490

528 / 544

80 / 96

961

313x821

313x821

250x660

933

4322

2544

1490

660 / 676

80 / 96

961

1152

5661

3332

1490

660 / 676

80 / 96

1168

440x821

440x821

380x613

440x1028

440x1028

1694

8216

4836

1856

795 / 811

80 / 96

1339

440x821

575x1199

575x1199

440x1028

75

3805

2240

11379

6697

1856

915 / 931

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

13550

7975

2221

1015 / 1031

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

18079

10641

2221

1052 / 1068

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

22420

13196

2221

1153 / 1169

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

27220

16021

2221

1357

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

33460

19694

2221

1357

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

44760

26345

2587

1656

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

60501

35610

2587

1889

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

74350

43761

2587

1889

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

98500

57975

2587

2366

80

3697

2146x3557

2146x3557

1520x3250

758/1124* - for VS- 10 and VS-15 with water heater is 758mm, with electric heater is 1124mmVmax - Parametres description on page 20
H*, Hs* - heights options details on page 54Optional functions are presented on the bookmark (in the back cover).
L2R - length of AHU equipped with two-rows exchanger
- VS 15 lenght for optional fan (low pressure) as well as the location of the water heater

VS -

15

size of an AHU

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

21

Supply AHUs
Cooling

Base AHU

80

VS 21650 sizes

HxW

Hs
L

VS -

- R -C

VS 21150 sizes COMPACT

HxW

Hs

Lf

VS

L
[mm]

L*
[mm]

Lf
[mm]

21

1124

1490

92

30

1124

1490

92

40

1124

1490

92

55

1490

1856

92

75

1490

1856

92

100

1856

2221

92

120

1856

2221

92

150

1856

2221

92

Hs*H*
(H(min) / (H(max)) (Hs(min) / (Hs(max))
[mm][mm]

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax*
[m3/h]

Vmax*
[CFM]

L
[mm]

L*
[mm]

W
[mm]

hxw
[mm]

hxw
[mm]

h1 x w 1
[mm]

21

1167

687

2200

1295

1490

1856

528 / 544

30

1586

933

3100

1825

1490

1856

660 / 676

80 / 96

961

313x821

313x821

250x660

80 / 96

961

440x821

440x821

40

1958

1152

4100

2413

1490

1856

380x613

660 / 676

80 / 96

1168

440x1028

440x1028

55

2878

1694

6054

3563

1856

2221

440x821

795 / 811

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

8150

4797

1856

2221

915 / 931

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

10700

6298

2221

2587

1015/1031

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

13300

7828

2221

2587

1052 / 1068

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

16400

9653

2221

2587

1153 / 1169

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

19900

11713

2221

2221

1357

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

24600

14479

2221

2221

1357

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

32900

19364

2587

2587

1656

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

44500

26192

2587

2587

1889

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

54000

31783

2587

2587

1889

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

71400

42025

2587

2587

2366

80

3697

2146x3557

2146x3557

1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
H*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).
* VS 1015 AHUs are available as indoor units only.
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.
Change of interrelated settings of a heater and a cooler results in changing the code of a specific AHU.

22

Supply AHUs
Heating, Cooling

Base AHU

81

VS 1015 sizes (suspended)*

HxW

VS -

- R - HC - T

VS 21650 sizes

HxW

HxW

Hs
L

Hs
VS -

- R - CH

VS -

- R - HC
VS

L
[mm]

L*
[mm]

Lf
[mm]

21

1490

1856

92

30

1490

1856

92

40

1490

1856

92

55

1856

2221

92

75

1856

2221

92

100

2221

2587

92

120

2221

2587

92

150

2221

2587

92

VS 21150 sizes COMPACT

HxW

HxW
Hs

Hs
Lf

Lf

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax*
[m3/h]

10

436

257

15

648

381

21

1167

30
40

Hs*H*
(H(min) / (H(max)) (Hs(min) / (Hs(max))
[mm][mm]

Vmax*
[CFM]

L
[mm]

L*
[mm]

W
[mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

1160

683

1124 / 1490*

360

1740

1024

1124 / 1490*

390

660

220x500

220x500

800

250x660

250x660

687

2200

1295

1856

2221

528 / 544

80 / 96

961

313x821

313x821

250x660

1586

933

3100

1825

1856

1958

1152

4100

2413

1856

2221

660 / 676

80 / 96

961

440x821

440x821

380x613

2221

660 / 676

80 / 96

1168

440x1028

440x1028

55

2878

1694

6054

3563

440x821

2221

2587

795 / 811

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

8150

4797

2221

2587

915 / 931

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

10700

6298

2587

2953

1015/1031

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

13300

7828

2587

2953

1052 / 1068

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

16400

9653

2587

2953

1153 / 1169

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

19900

11713

2587

2587

1357

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

24600

14479

2587

2587

1357

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

32900

19364

2953

2953

1656

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

44500

26192

2953

2953

1889

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

54000

31783

2953

2953

1889

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

71400

42025

2953

2953

2366

80

3697

2146x3557

2146x3557

1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
1124/1490* - L for VS-10 and VS-15 with water heater = 1124 mm, with electric heater = 1490 mm
H*, Hs* - heights options details on page 54

VS -

15

size of an AHU

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

Vmax - Parametres description on page 20


Optional functions are presented on the bookmark (in the back cover).

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

23

Supply AHUs
Heating, Cooling, Heating

Base AHU

VS 21650 sizes

HxW

Hs
L

VS -

- R - HCH

Hs*H*
(H(min) / (H(max)) (Hs(min) / (Hs(max))
[mm][mm]

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax*
[m3/h]

Vmax*
[CFM]

L
[mm]

L*
[mm]

W
[mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1167

687

2200

1295

2221

2587

528 / 544

30

1586

933

3100

1825

2221

2587

660 / 676

80 / 96

961

313x821

313x821

250x660

80 / 96

961

440x821

440x821

40

1958

1152

4100

2413

2221

2587

380x613

660 / 676

80 / 96

1168

440x1028

440x1028

55

2878

1694

6054

3563

2587

2953

440x821

795 / 811

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

8150

4797

2587

2953

915 / 931

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

10700

6298

2953

3318

1015/1031

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

13300

7828

2953

3318

1052 / 1068

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

16400

9653

2953

3318

1153 / 1169

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

19900

11713

2953

2953

1357

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

24600

14479

2953

2953

1357

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

32900

19364

3318

3318

1656

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

44500

26192

3318

3318

1889

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

54000

31783

3318

3318

1889

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

71400

42025

3318

3318

2366

80

3697

2146x3557

2146x3557

1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
H*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).
* VS 1015 AHUs are available as indoor units only.
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.

24

Exhaust AHUs
Ventilation

Base AHU

82

VS 1015 sizes (suspended)*

HxW

VS -

- R -V- T

VS 21650 sizes

HxW

Hs
L

VS -

- R -V

H*Hs*
(H(min) / (H(max)) (Hs(min) / (Hs(max))
[mm][mm]

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax*
[m3/h]

Vmax*
[CFM]

L
[mm]

W
[mm]

hxw
[mm]

hxw
[mm]

h1 x w 1
[mm]

10

400

235

1960

1154

758

360

15

600

353

2840

1672

758

390

660

220x500

220x500

800

250x660

250x660

21

1167

687

4814

2833

758

528 / 544

80 / 96

961

313x821

313x821

250x660

30

1586

933

6580

3873

40

1958

1152

8140

4791

758

660 / 676

80 / 96

961

440x821

440x821

380x613

758

660 / 676

80 / 96

1168

440x1028

440x1028

55

2878

1694

12017

440x821

7073

1124

795 / 811

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

15884

9349

1124

915 / 931

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

20346

11975

1490

1015/1031

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

24295

14300

1490

1052 / 1068

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

30014

17666

1490

1153 / 1169

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

36231

21325

1490

1357

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

43589

25656

1490

1357

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

56764

33410

1856

1656

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

62646

37068

1856

1889

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

91861

54068

1856

1889

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

100000

58858

1856

2366

80

3697

2146x3557

2146x3557

1520x3250

H*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).

VS -

15

size of an AHU

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

25

Exhaust AHUs
Filtration, Ventilation

A
82

Base AHU
VS 1015 sizes (suspended)*

HxW

VS -

- R - FV - T

VS 21650 sizes

HxW

Hs
L

VS -

- R - FV

VS 21650 sizes COMPACT

HxW
Hs
Lf

L
Hs*H*
(H(min) / (H(max)) (Hs(min) / (Hs(max))
[mm][mm]

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax*
[m3/h]

Vmax*
[CFM]

L
[mm]

10

400

235

1960

1154

758

360

15

600

353

2840

1672

758

390

21

1167

687

3658

2153

1124

30

1586

933

5118

3012

40

1958

1152

6700

3943

55

2878

1694

9720

VS

L
[mm]

Lf
[mm]

21

758

92

30

758

92

40

758

92

55

1124

92

75

1124

92

100

1490

92

120

1490

92

150

1490

92

W
[mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

660

220x500

220x500

800

250x660

250x660

528 / 544

80 / 96

961

313x821

313x821

250x660

1124

660 / 676

80 / 96

961

440x821

440x821

380x613

1124

660 / 676

80 / 96

1168

440x1028

440x1028

440x821

5721

1490

795 / 811

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

13470

7928

1490

915 / 931

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

17620

10371

1856

1015/1031

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

21410

12601

1856

1052 / 1068

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

26558

15632

1856

1153 / 1169

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

32246

18979

1856

1357

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

39630

23325

1856

1357

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

53010

31201

2221

1656

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

62646

37068

2221

1889

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

79350

46704

2221

1889

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

100000

58858

2221

2366

80

3697

2146x3557

2146x3557

1520x3250

H*, Hs* - heights options details on page 54


- VS 15 lenght for optional fan (low pressure)
Optional functions are presented on the bookmark (in the back cover).

Vmax - Parametres description on page 20

* VS 1015 AHUs are available as indoor units only.


** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.
Applying a priority air treatment function.

26

Supply-exhaust AHUs: cross-ow exchanger


Ventilation

Base AHU

84
86

VS 1015 sizes (suspended)*


L1

VS -

- R -P- T

VS 21650 sizes
L

H
Hs
L

VS -

VS

- R -P

H*H2*Hs*
L1(H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[mm][mm][mm][mm][mm]

Vmin Vmin Vmax* Vmax*L


3/h] [CFM] [m3/h] [CFM] [mm][m

W2
[mm]

hxw
[mm]

hxw
[mm]

h 1 x w1
[mm]
0

10

436

257

1655

974

1883

1883

360

660

1330

220x500

220x500

15

648

381

2462

1449

2248

2614

390

800

1610

250x660

250x660

21

1167

687

3089

1818

2587

2587

528 / 544

976 / 992

80 / 96

961

313x821

313x821

250x660

30

1586

933

4322

2544

2587

2587

660 / 676

1240 / 1256

80 / 96

961

440x821

440x821

380x613

40

1958

1152

5661

3332

2587

2587

660 / 676

1240 / 1256

80 / 96

1168

440x1028

440x1028

440x821

55

2878

1694

8216

4836

3318

3318

795 / 811

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

11379

6697

3318

3318

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

13500

7946

3684

3684

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

18079

10641

3684

3684

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

22427

13200

4050

4050

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

27230

16027

4050

4050

1357

2714

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

33467

19698

4050

4050

1357

2714

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

44767

26349

5147

5147

1656

3312

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

60500

35609

5147

5147

1889

3778

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

67600

39788

5147

5147

1889

3778

80

3585

1669x3445

1669x3445

1199x3150

5878

2366

4732

80

3697

2146x35572146x3557 1520x3250
Vmax - Parametres description on page 20

65028725 16907 97200 572105878


H*, H2*, Hs* - heights options details on page 54

Optional functions are presented on the bookmark (in the back cover).

VS -

15

size of an AHU

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

27

Supply-exhaust AHUs: cross-ow exchanger


Ventilation

A
84
86

Base AHU

VS 21650 sizes

H
Hs
L

VS -

- R -P

Hs*H*H 2*
(H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[mm][mm][mm][mm]

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax*
[m3/h]

Vmax*
[CFM]

L
[mm]

L1
[mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1167

687

3089

1818

2587

2587

528 / 544

976 / 992

80 / 96

30

1586

933

4322

2544

2587

2587

660 / 676

1240 / 1256

80 / 96

961

313x821

313x821

250x660

961

440x821

440x821

40

1958

1152

5661

3332

2587

2587

660 / 676

1240 / 1256

380x613

80 / 96

1168

440x1028

440x1028

55

2878

1694

8216

4836

3318

3318

795 / 811

440x821

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

11379

6697

3318

3318

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

13500

7946

3684

3684

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

18079

10641

3684

3684

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

22427

13200

4050

4050

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

27230

16027

4050

4050

1357

2714

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

33467

19698

4050

4050

1357

2714

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

44767

26349

5147

5147

1656

3312

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

60500

35609

5147

5147

1889

3778

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

67600

39788

5147

5147

1889

3778

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

97200

57210

5878

5878

2366

4732

80

3697

2146x3557

2146x3557

1520x3250

H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).
* VS 1015 AHUs are available as indoor units only.
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.
Applying a priority air treatment function.

28

Supply-exhaust AHUs: cross-ow exchanger


Heating

Base AHU

84
86

VS 1015 sizes (suspended)*

VS -

- R - PH - T

VS 21650 sizes

H
Hs
L

VS -

VS

VminVmin Vmax* Vmax*


[m3/h] [CFM] [m3/h] [CFM]
974

- R - PH

H 2*Hs*H*
L1(H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) WW2
[mm][mm][mm][mm][mm] [mm]

L
[mm]

10

436

257

1655

15

648

381

2462

1449 2248/2614* 2248

1883/2248* 1883

21

1167

687

3089

1818

2953

30

1586

933

4322

2544

40

1958

1152

5661

3332

55

2878

1694

8216

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]
0

360

660

1330

220x500

220x500

390

800

1610

250x660

250x660

2587

528 / 544

976 / 992

80 / 96

961

313x821

313x821

250x660

2953

2587

660 / 676

1240 / 1256

80 / 96

961

440x821

440x821

380x613

2953

2587

660 / 676

1240 / 1256

80 / 96

1168

440x1028

440x1028

440x821

4836

3684

3318

795 / 811

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

11379

6697

3684

3318

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

13500

7946

4050

3684

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

18079

10641

4050

3684

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

22427

13200

4415

4050

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

27230

16027

4415

4050

1357

2714

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

33467

19698

4415

4050

1357

2714

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

44767

26349

5513

5147

1656

3312

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

60500

35609

5513

5147

1889

3778

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

67600

39788

5513

5147

1889

3778

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

97200

57210

6244

5878

2366

4732

80

3697

2146x3557

2146x3557

1520x3250

1883/2248* - for water heater L= 1883 mm, for electric heater L= 2248 mm
H*, H2*, Hs* - heights options details on page 54
Optional functions are presented on the bookmark (in the back cover).

VS -

15

size of an AHU

Vmax - Parametres description on page 20

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

29

Supply-exhaust AHUs: cross-ow exchanger


Mixing box, Heating
Base AHU

VS 21650 sizes

H
Hs
L

VS -

- R - PMH

H 2*Hs*H*
(H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[mm][mm][mm][mm]

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax*
[m3/h]

Vmax*
[CFM]

L
[mm]

L1
[mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1167

687

3089

1818

3684

3318

528 / 544

976 / 992

80 / 96

30

1586

933

4322

2544

3684

3318

660 / 676

1240 / 1256

80 / 96

961

313x821

313x821

250x660

961

440x821

440x821

40

1958

1152

5661

3332

3684

3318

660 / 676

1240 / 1256

380x613

80 / 96

1168

440x1028

440x1028

55

2878

1694

8216

4836

4415

4050

795 / 811

440x821

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

11379

6697

4415

4050

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

13500

7946

4781

4415

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

18079

10641

4781

4415

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

22427

13200

5513

5147

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

27230

16027

5513

5147

1357

2714

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

33467

19698

5513

5147

1357

2714

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

44767

26349

6610

6244

1656

3312

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

60500

35609

6610

6244

1889

3778

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

67600

39788

6610

6244

1889

3778

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

97200

57210

7341

6975

2366

4732

80

3697

2146x3557

2146x3557

1520x3250

H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).
* VS 1015 AHUs are available as indoor units only.
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.
Applying a priority air treatment function.

30

Supply-exhaust AHUs: cross-ow exchanger


Heating

Base AHU

84
86

VS 1015 sizes (suspended)*

VS -

- R - PH - T

VS 21650 sizes

H
Hs
L

VS -

VS

Vmin Vmin Vmax* Vmax*


[m3/h] [CFM] [m3/h] [CFM]
974

- R - PH

H 2*Hs*H*
L1(H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max))W
[mm][mm][mm][mm][mm]

L
[mm]

10

436

257

1655

15

648

381

2462

1449 2248/2614* 2248

1883/2248* 1883

21

1167

687

3089

1818

2953

30

1586

933

4322

2544

40

1958

1152

5661

3332

55

2878

1694

8216

W2
[mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]
0

360

660

1330

220x500

220x500

390

800

1610

250x660

250x660

2587

528 / 544

976 / 992

80 / 96

961

313x821

313x821

250x660

2953

2587

660 / 676

1240 / 1256

80 / 96

961

440x821

440x821

380x613

2953

2587

660 / 676

1240 / 1256

80 / 96

1168

440x1028

440x1028

440x821

4836

3684

3318

795 / 811

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028
575x1199

75

3805

2240

11379

6697

3684

3318

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

100

4863

2862

13500

7946

4050

3684

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

18079

10641

4050

3684

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

22427

13200

4415

4050

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

27230

16027

4415

4050

1357

2714

80

2085

1137x1945 1137x1945

795x1520

230

10398

6120

33467

19698

4415

4050

1357

2714

80

2493

1137x2353 1137x2353

740x1913

300

13491

7941

44767

26349

5513

5147

1656

3312

80

2585

1436x2445 1436x2445

933x1945

400

18704

11009

60500

35609

5513

5147

1889

3778

80

3085

1669x2945 1669x2945

933x2650

500

21817

12841

67600

39788

5513

5147

1889

3778

80

3585

1669x3445 1669x3445 1199x3150

650

28725

16907

97200

57210

6243

5878

2366

4732

80

3697

1883/2248* - for water heater L= 1883 mm, for electric heater L= 2248 mm
H*, H2*, Hs* - heights options details on page 54
Optional functions are presented on the bookmark (in the back cover).

VS -

15

size of an AHU

2146x3557 2146x3557 1520x3250


Vmax - Parametres description on page 20

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

31

Supply-exhaust AHUs: cross-ow exchanger


Cooling

A
85
87

Base AHU

VS 21650 sizes

H
Hs
L

VS -

- R - PC

H2*Hs*H*
Vmax*LL*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[CFM] [mm] [mm] [mm][mm][mm][mm][mm]

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax*
[m3/h]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1167

687

2200

1295

2953

3318

2587

528 / 544

976 / 992

80 / 96

30

1586

933

3100

1825

2953

3318

2587

660 / 676

1240 / 1256

80 / 96

961

313x821

313x821

250x660

961

440x821

440x821

40

1958

1152

4100

2413

2953

3318

2587

660 / 676

1240 / 1256

380x613

80 / 96

1168

440x1028

440x1028

55

2878

1694

6054

3563

3684

4050

3318

795 / 811

440x821

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

8150

4797

3684

4050

3318

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

10700

6298

4050

4415

3684

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

13300

7828

4050

4415

3684

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

16400

9653

4415

4781

4050

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

19900

11713

4415

4415

4050

1357

2714

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

24600

14479

4415

4415

4050

1357

2714

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

32900

19364

5513

5513

5147

1656

3312

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

44500

26192

5513

5513

5147

1889

3778

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

54000

31783

5513

5513

5147

1889

3778

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

71400

42025

6243

6243

5878

2366

4732

80

3697

2146x3557

2146x3557

1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).
* VS 1015 AHUs are available as indoor units only.
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.
Applying a priority air treatment function.

32

Supply-exhaust AHUs: cross-ow exchanger


Mixing box, cooling
Base AHU

VS 21650 sizes

H
Hs
L

VS -

VS

- R - PMC

H 2*Hs*H*
VminVmin Vmax* Vmax*LL*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[m3/h] [CFM] [m3/h] [CFM] [mm] [mm] [mm][mm][mm][mm][mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1167

687

2200

1295

3684

4050

3318

528 / 544

976 / 992

80 / 96

961

313x821

313x821

250x660

30

1586

933

3100

1825

3684

4050

3318

660 / 676

1240 / 1256

80 / 96

961

440x821

440x821

380x613

40

1958

1152

4100

2413

3684

4050

3318

660 / 676

1240 / 1256

80 / 96

1168

440x1028

440x1028

440x821

55

2878

1694

6054

3563

4415

4781

4050

795 / 811

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

8150

4797

4415

4781

4050

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

10700

6298

4781

5147

4415

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

13300

7828

4781

5147

4415

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

16400

9653

5513

5878

5147

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

19900

11713

5513

5513

5147

1357

2714

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

24600

14479

5513

5513

5147

1357

2714

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

32900

19364

6610

6610

6244

1656

3312

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

44500

26192

6610

6610

6244

1889

3778

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

54000

31783

6610

6610

6244

1889

3778

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

71400

42025

7340

7340

6976

2366

4732

80

3697

2146x3557

2146x3557

1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).

VS -

15

size of an AHU

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

33

Supply-exhaust AHUs: cross-ow exchanger


Cooling

A
85
87

Base AHU

VS 21650 sizes

H
Hs
L

VS -

- R - PC

H2*Hs*H*
Vmax*LL*L1(H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[CFM] [mm] [mm] [mm][mm][mm][mm][mm]

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax*
[m3/h]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1167

687

2200

1295

2953

3318

2587

528 / 544

976 / 992

80 / 96

30

1586

933

3100

1825

2953

3318

2587

660 / 676

1240 / 1256

80 / 96

961

313x821

313x821

250x660

961

440x821

440x821

40

1958

1152

4100

2413

2953

3318

2587

660 / 676

1240 / 1256

380x613

80 / 96

1168

440x1028

440x1028

55

2878

1694

6054

3563

3684

4050

3318

795 / 811

440x821

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

8150

4797

3684

4050

3318

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

10700

6298

4050

4415

3684

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

13300

7828

4050

4415

3684

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

16400

9653

4415

4781

4050

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

19900

11713

4415

4415

4050

1357

2714

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

24600

14479

4415

4415

4050

1357

2714

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

32900

19364

5513

5513

5147

1656

3312

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

44500

26192

5513

5513

5147

1889

3778

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

54000

31783

5513

5513

5147

1889

3778

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

71400

42025

6244

6244

5879

2366

4732

80

3697

2146x3557

2146x3557

1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).
* VS 1015 AHUs are available as indoor units only.
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.
Applying a priority air treatment function.
Change of interrelated settings of a heater and a cooler results in changing the code of a specific AHU.

34

Supply-exhaust AHUs: cross-ow exchanger


Heating, Cooling

Base AHU

85
87

VS 1015 sizes (suspended)*

VS -

- R - PHC - T

VS 21650 sizes

Hs

Hs

VS -

VS

Vmin Vmin Vmax* Vmax*


[m3/h] [CFM] [m3/h] [CFM]

- R - PHC
L
[mm]

VS -

H 2*Hs*H*
L*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) WW2
[mm] [mm][mm][mm][mm][mm] [mm]

- R - PCH

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]
0

10

436

257

1160

683

2248/2614*

1883

360

660

1330

220x500

220x500

15

648

381

1740

1024

2980

2614

390

800

1610

250x660

250x660

21

1167

687

2200

1295

3318

3684

2587

528 / 544

976 / 992

80 / 96

961

313x821

313x821

250x660

30

1586

933

3100

1825

3318

3684

2587

660 / 676

1240 / 1256

80 / 96

961

440x821

440x821

380x613

40

1958

1152

4100

2413

3318

3684

2587

660 / 676

1240 / 1256

80 / 96

1168

440x1028

440x1028

440x821

55

2878

1694

6054

3563

4050

4415

3318

795 / 811

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

8150

4797

4050

4415

3318

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

10700

6298

4415

4781

3684

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

13300

7828

4415

4781

3684

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

16400

9653

4781

5147

4050

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

19900

11713

4781

4781

4050

1357

2714

80

2085

1137x1945 1137x1945

795x1520

230

10398

6120

24600

14479

4781

4781

4050

1357

2714

80

2493

1137x2353 1137x2353

740x1913

300

13491

7941

32900

19364

5878

5878

5147

1656

3312

80

2585

1436x2445 1436x2445

933x1945

400

18704

11009

44500

26192

5878

5878

5147

1889

3778

80

3085

1669x2945 1669x2945

933x2650

500

21817

12841

54000

31783

5878

5878

5147

1889

3778

80

3585

1669x3445 1669x3445 1199x3150

650

28725

16907

71400

42025

6610

6610

5879

2366

4732

80

3697

2146x3557 2146x3557 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
2248/2614* - for water heater L= 2248 mm, for electric heater L= 2614 mm
H*, H2*, Hs* - heights options details on page 54

VS -

15

size of an AHU

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

Vmax - Parametres description on page 20


Optional functions are presented on the bookmark (in the back cover).

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

35

Supply-exhaust AHUs: cross-ow exchanger


Mixing box, Heating, Cooling
Base AHU
VS 21650 sizes

H
Hs
L

VS -

- R - PMHC - T

VS 21650 sizes

H
Hs
L

VS -

- R - PMCH - T

H2*Hs*H*
Vmax*LL*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[CFM] [mm] [mm] [mm][mm][mm][mm][mm]

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax*
[m3/h]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1167

687

2200

1295

4050

4415

3318

528 / 544

976 / 992

80 / 96

30

1586

933

3100

1825

4050

4415

3318

660 / 676

1240 / 1256

80 / 96

961

313x821

313x821

250x660

961

440x821

440x821

40

1958

1152

4100

2413

4050

4415

3318

660 / 676

1240 / 1256

380x613

80 / 96

1168

440x1028

440x1028

55

2878

1694

6054

3563

4781

5147

4050

795 / 811

440x821

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

8150

4797

4781

5147

4050

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

10700

6298

5147

5513

4415

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

13300

7828

5147

5513

4415

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

16400

9653

5878

6244

5147

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

19900

11713

5878

5878

5147

1357

2714

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

24600

14479

5878

5878

5147

1357

2714

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

32900

19364

6975

6975

6244

1656

3312

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

44500

26192

6975

6975

6244

1889

3778

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

54000

31783

6975

6975

6244

1889

3778

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

71400

42025

7707

7707

6976

2366

4732

80

3697

2146x3557

2146x3557

1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).
* VS 1015 AHUs are available as indoor units only.
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.
Applying a priority air treatment function.
Change of interrelated settings of a heater and a cooler results in changing the code of a specific AHU.

36

Supply-exhaust AHUs: cross-ow exchanger


Heating, Cooling

Base AHU

85
87

VS 1015 sizes (suspended)*

VS -

- R - PHC - T

VS 21650 sizes

Hs

Hs

VS -

VS

VS -

- R - PHC

H 2*Hs*H*
Vmin Vmin Vmax* Vmax*LL*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) WW2
[m3/h] [CFM] [m3/h] [CFM] [mm] [mm] [mm][mm][mm][mm][mm] [mm]

- R - PCH

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]
0

10

436

257

1160

683

2248

2248

360

660

1330

220x500

220x500

15

648

381

1740

1024

2980

2248

390

800

1610

250x660

250x660

21

1167

687

2200

1295

3318

3684

2587

528 / 544

976 / 992

80 / 96

961

313x821

313x821

250x660

30

1586

933

3100

1825

3318

3684

2587

660 / 676

1240 / 1256

80 / 96

961

440x821

440x821

380x613

40

1958

1152

4100

2413

3318

3684

2587

660 / 676

1240 / 1256

80 / 96

1168

440x1028

440x1028

440x821

55

2878

1694

6054

3563

4050

4415

3318

795 / 811

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

8150

4797

4050

4415

3318

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

10700

6298

4415

4781

3684

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

13300

7828

4415

4781

3684

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

16400

9653

4781

5147

4050

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

19900

11713

4781

4781

4050

1357

2714

80

2085

1137x1945 1137x1945

795x1520

230

10398

6120

24600

14479

4781

4781

4050

1357

2714

80

2493

1137x2353 1137x2353

740x1913

300

13491

7941

32900

19364

5878

5878

5147

1656

3312

80

2585

1436x2445 1436x2445

933x1945

400

18704

11009

44500

26192

5878

5878

5147

1889

3778

80

3085

1669x2945 1669x2945

933x2650

500

21817

12841

54000

31783

5878

5878

5147

1889

3778

80

3585

1669x3445 1669x3445

1199x3150

650

28725

16907

71400

42025

6610

6610

5879

2366

4732

80

3697

2146x3557 2146x3557

1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).

VS -

15

size of an AHU

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

37

Supply-exhaust AHUs: cross-ow exchanger


Heating, Cooling, Heating
Base AHU

VS 21650 sizes

H
Hs
L

VS -

- R - PHCH

H2*Hs*H*
Vmax*LL*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[CFM] [mm] [mm] [mm][mm][mm][mm][mm]

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax*
[m3/h]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1167

687

2200

1295

3684

4050

2587

528 / 544

976 / 992

80 / 96

30

1586

933

3100

1825

3684

4050

2587

660 / 676

1240 / 1256

80 / 96

961

313x821

313x821

250x660

961

440x821

440x821

40

1958

1152

4100

2413

3684

4050

2587

660 / 676

1240 / 1256

380x613

80 / 96

1168

440x1028

440x1028

55

2878

1694

6054

3563

4415

4781

3318

795 / 811

440x821

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

8150

4797

4415

4781

3318

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

10700

6298

4781

5147

3684

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

13300

7828

4781

5147

3684

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

16400

9653

5147

5513

4050

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

19900

11713

5147

5147

4050

1357

2714

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

24600

14479

5147

5147

4050

1357

2714

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

32900

19364

6244

6244

5147

1656

3312

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

44500

26192

6244

6244

5147

1889

3778

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

54000

31783

6244

6244

5147

1889

3778

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

71400

42025

6976

6976

5879

2366

4732

80

3697

2146x3557

2146x3557

1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).
* VS 1015 AHUs are available as indoor units only.
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.
Applying a priority air treatment function.

38

Supply-exhaust AHUs: cross-ow exchanger


Mixing box, Heating, Cooling, Heating

Base AHU

VS 21650 sizes

H
Hs
L

VS -

- R - PMHCH

H 2*Hs*H*
Vmax*LL*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[CFM] [mm] [mm] [mm][mm][mm][mm][mm]

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax*
[m3/h]

hxw
[mm]

hxw
[mm]

h 1 x w1
[mm]

21

1167

687

2200

1295

4415

4781

3318

528 / 544

976 / 992

80 / 96

30

1586

933

3100

1825

4415

4781

3318

660 / 676

1240 / 1256

80 / 96

961

313x821

313x821

250x660

961

440x821

440x821

40

1958

1152

4100

2413

4415

4781

3318

660 / 676

1240 / 1256

380x613

80 / 96

1168

440x1028

440x1028

55

2878

1694

6054

3563

5147

5513

4050

795 / 811

440x821

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

8150

4797

5147

5513

4050

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

10700

6298

5513

5878

4415

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

13300

7828

5513

5878

4415

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

16400

9653

6244

6610

5147

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

19900

11713

6244

6244

5147

1357

2714

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

24600

14479

6244

6244

5147

1357

2714

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

32900

19364

7341

7341

6244

1656

3312

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

44500

26192

7341

7341

6244

1889

3778

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

54000

31783

7341

7341

6244

1889

3778

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

71400

42025

8073

8073

6976

2366

4732

80

3697

2146x3557

2146x3557

1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).

VS -

15

size of an AHU

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

39

Supply-exhaust AHUs: cross-ow exchanger


Heating, Cooling, Heating
Base AHU

VS 21650 sizes

H
Hs
L

VS -

- R - PHCH

H2*Hs*H*
Vmax*LL*L1 (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[CFM] [mm] [mm] [mm][mm][mm][mm][mm]

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax*
[m3/h]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1167

687

2200

1295

3684

4050

2587

528 / 544

976 / 992

80 / 96

30

1586

933

3100

1825

3684

4050

2587

660 / 676

1240 / 1256

80 / 96

961

313x821

313x821

250x660

961

440x821

440x821

40

1958

1152

4100

2413

3684

4050

2587

660 / 676

1240 / 1256

380x613

80 / 96

1168

440x1028

440x1028

55

2878

1694

6054

3563

4415

4781

3318

795 / 811

440x821

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

8150

4797

4415

4781

3318

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

10700

6298

4781

5147

3684

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

13300

7828

4781

5147

3684

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

16400

9653

5147

5513

4050

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

19900

11713

5147

5147

4050

1357

2714

80

2085

1137x1945

1137x1945

795x1520

230

10398

6120

24600

14479

5147

5147

4050

1357

2714

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

32900

19364

6244

6244

5147

1656

3312

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

44500

26192

6244

6244

5147

1889

3778

80

3085

1669x2945

1669x2945

933x2650

500

21817

12841

54000

31783

6244

6244

5147

1889

3778

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

71400

42025

6976

6976

5879

2366

4732

80

3697

2146x3557

2146x3557

1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).
* VS 1015 AHUs are available as indoor units only.
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.
Applying a priority air treatment function.

40

Supply-exhaust AHUs: rotary exchanger


Ventilation

Base AHU

89

VS 21650 sizes
K

H
Hs
L

VS -

- R -R

H2*Hs*H*
Vmax*LL1K(H (min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[CFM] [mm] [mm] [mm][mm][mm][mm][mm]

VS

Vmin
[m3/h]

Vmin
[CFM]

Vmax*
[m3/h]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1193

702

3550

2089

2221

2221

528 / 544

976 / 992

80 / 96

30

1586

933

4530

2666

2221

2221

660 / 676

1240 / 1256

80 / 96

961

313x821

313x821

250x660

961

440x821

440x821

40

2099

1235

6700

3943

2221

2221

660 / 676

1240 / 1256

380x613

80 / 96

1168

440x1028

440x1028

55

2878

1694

9720

5721

2587

2587

366

795 / 811

440x821

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

12519

7368

2587

2587

366

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

13550

7975

2953

2953

731

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5985

3523

20748

12212

2953

2953

731

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7415

4364

25400

14950

2953

2953

731

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

25707

15131

2953

2953

731

1357

2714

80

2085

1137x1945 1137x1945

795x1520

230

10640

6262

36886

21710

2953

2953

731

1357

2714

80

2493

1137x2353 1137x2353

740x1913

300

13491

7941

40081

23591

3318

3318

1097

1656

3312

80

2585

1436x2445 1436x2445

933x1945

400

18704

11009

55594

32722

3318

3318

1097

1889

3778

80

3085

1669x2945 1669x2945

933x2650

500

22399

13184

77648

45702

3318

3318

1097

1889

3778

80

3585

1669x3445 1669x3445 1199x3150

650

28725

16907

83241

48994

3319

3319

1097

2366

4732

80

3697

2146x3557 2146x3557 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
K* - Distance with the sets with drop eliminator
H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).

VS -

15

size of an AHU

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

41

Supply-exhaust AHUs: rotary exchanger


Heating

A
89

Base AHU

VS 21650 sizes
K

H
Hs
L

VS -

VS

VminVmin
[m3/h] [CFM]

Vmax*
[m3/h]

- R - RH

H2*H s*H*
Vmax*LL1K(H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[CFM] [mm] [mm] [mm][mm][mm][mm][mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1193

702

3080

1813

2953

2221

731

528 / 544

976 / 992

80 / 96

961

313x821

313x821

250x660

30

1586

933

4322

2544

2953

2221

731

660 / 676

1240 / 1256

80 / 96

961

440x821

440x821

380x613

40

2099

1235

5661

3332

2953

2221

731

660 / 676

1240 / 1256

80 / 96

1168

440x1028

440x1028

440x821

55

2878

1694

8216

4836

3318

2587

1097

795 / 811

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

11379

6697

3318

2587

1097

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

13550

7975

3684

2953

1463

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5985

3523

18079

10641

3684

2953

1463

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7415

4364

22420

13196

3684

2953

1463

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

25707

15131

3684

2953

1463

1357

2714

80

2085

1137x1945

1137x1945

795x1520

230

10640

6262

33460

19694

3684

2953

1463

1357

2714

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

40081

23591

4050

3318

1829

1656

3312

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

55594

32722

4050

3318

1829

1889

3778

80

3085

1669x2945

1669x2945

933x2650

500

22399

13184

74350

43761

4050

3318

1829

1889

3778

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

83241

48994

4050

3319

1829

2366

4732

80

3697

2146x3557

2146x3557

1520x3250

H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers)..
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.
Applying a priority air treatment function.

42

Supply-exhaust AHUs: rotary exchanger


Mixing box, Heating
Base AHU

VS 21650 sizes
K

H
Hs
L

VS -

VS

VminVmin Vmax* Vmax*L


[m3/h] [CFM] [m3/h] [CFM] [mm]

- R - RMH

H 2*Hs*H*
K(H (min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[mm][mm][mm][mm][mm]

L1
[mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1193

702

3080

1813

3684

2587

366

528 / 544

976 / 992

80 / 96

961

313x821

313x821

250x660

30

1586

933

4322

2544

3684

2587

366

660 / 676

1240 / 1256

80 / 96

961

440x821

440x821

380x613

40

2099

1235

5661

3332

3684

2587

366

660 / 676

1240 / 1256

80 / 96

1168

440x1028

440x1028

440x821

55

2878

1694

8216

4836

4050

2953

366

795 / 811

1510 / 1526

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

11379

6697

4050

2953

366

915 / 931

1750 / 1766

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

13550

7975

4415

3318

366

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520

795x1520

695x1340

120

5985

3523

18079

10641

4415

3318

366

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751

832x1751

795x1520

150

7415

4364

22420

13196

4781

3684

366

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

25707

15131

4781

3684

366

1357

2714

80

2085

1137x1945

1137x1945

795x1520

230

10640

6262

33460

19694

4781

3684

366

1357

2714

80

2493

1137x2353

1137x2353

740x1913

300

13491

7941

40081

23591

5147

4050

366

1656

3312

80

2585

1436x2445

1436x2445

933x1945

400

18704

11009

55594

32722

5147

4050

366

1889

3778

80

3085

1669x2945

1669x2945

933x2650

500

22399

13184

74350

43761

5147

4050

366

1889

3778

80

3585

1669x3445

1669x3445

1199x3150

650

28725

16907

83241

48994

5147

4050

366

2366

4732

80

3697

2146x3557

2146x3557

1520x3250

H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).

VS -

15

size of an AHU

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

43

Supply-exhaust AHUs: rotary exchanger


Cooling

A
90

Base AHU

VS 21650 sizes
K

H
Hs
L

VS -

VS

- R - RC

H 2*Hs*H*
Vmin Vmin Vmax* Vmax*LL*L1KK* (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[m3/h] [CFM] [m3/h] [CFM] [mm] [mm] [mm] [mm] [mm][mm][mm][mm][mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1193

702

2200

1295

2953

3318

2221

731

1097

528 / 544

976 / 992

80 / 96

961

313x821

313x821

250x660

30

1586

933

3100

1825

2953

3318

2221

731

1097

660 / 676

1240 / 1256

80 / 96

961

440x821

440x821

380x613

40

2099

1235

4100

2413

2953

3318

2221

731

1097

660 / 676

1240 / 1256

80 / 96

1168 440x1028 440x1028

55

2878

1694

6054

3563

3318

3684

2587

1097

1463

795 / 811

1510 / 1526

80 / 96

1339 575x1199 575x1199 440x1028

75

3805

2240

8150

4797

3318

3684

2587

1097

1463

915 / 931

1750 / 1766

80 / 96

1480 695x1340 695x1340 575x1199

100

4863

2862

10700

6298

3684

4050

2953

1463

1829

1015 / 1031

1950 / 1966

80 / 96

1660 795x1520 795x1520 695x1340

120

5985

3523

13300

7828

3684

4050

2953

1463

1829

1052 / 1068

2024 / 2040

80 / 96

1891 832x1751 832x1751 795x1520

150

7415

4364

16400

9653

3684

4050

2953

1463

1829

1153 / 1169

2226 / 2242

80 / 96

2085 933x1945 933x1945 795x1520

180

8640

5085

19900 11713

3684

3684

2953

1463

1357

2714

80

2085 1137x1945 1137x1945 795x1520

230

10640

6262

24600 14479

3684

3684

2953

1463

1357

2714

80

2493 1137x2353 1137x2353 740x1913

300

13491

7941

32900 19364

4050

4050

3318

1829

1656

3312

80

2585 1436x2445 1436x2445 933x1945

400

18704 11009 44500 26192

4050

4050

3318

1829

1889

3778

80

3085 1669x2945 1669x2945 933x2650

500

22399 13184 54000 31783

4050

4050

3318

1829

1889

3778

80

3585 1669x3445 1669x3445 1199x3150

650

28725 16907 71400 42025

4050

4050

3319

1829

2366

4732

80

3697 2146x3557 2146x3557 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
K* - Distance with the sets with drop eliminator
H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.
Applying a priority air treatment function.

44

440x821

Supply-exhaust AHUs: rotary exchanger


Mixing box, Cooling
Base AHU

VS 21650 sizes
K

H
Hs
L

VS -

VS

- R - RMC

H 2*Hs*H*
Vmin Vmin Vmax* Vmax*LL*L1KK* (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[m3/h] [CFM] [m3/h] [CFM] [mm] [mm] [mm] [mm] [mm][mm][mm][mm][mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1193

702

2200

1295

3684

4050

2587

366

731

528 / 544

976 / 992

80 / 96

961

313x821

313x821

250x660

30

1586

933

3100

1825

3684

4050

2587

366

731

660 / 676

1240 / 1256

80 / 96

961

440x821

440x821

380x613

40

2099

1235

4100

2413

3684

4050

2587

366

731

660 / 676

1240 / 1256

80 / 96

1168 440x1028 440x1028

55

2878

1694

6054

3563

4050

4415

2953

366

731

795 / 811

1510 / 1526

80 / 96

1339 575x1199 575x1199 440x1028

440x821

75

3805

2240

8150

4797

4050

4415

2953

366

731

915 / 931

1750 / 1766

80 / 96

1480 695x1340 695x1340 575x1199

100

4863

2862

10700

6298

4415

4781

3318

366

731

1015 / 1031

1950 / 1966

80 / 96

1660 795x1520 795x1520 695x1340

120

5985

3523

13300

7828

4415

4781

3318

366

731

1052 / 1068

2024 / 2040

80 / 96

1891 832x1751 832x1751 795x1520

150

7415

4364

16400

9653

4781

5147

3684

366

731

1153 / 1169

2226 / 2242

80 / 96

2085 933x1945 933x1945 795x1520

180

8640

5085

19900

11713

4781

4781

3684

366

1357

2714

80

2085 1137x1945 1137x1945 795x1520

230

10640

6262

24600

14479

4781

4781

3684

366

1357

2714

80

2493 1137x2353 1137x2353 740x1913

300

13491

7941

32900

19364

5147

5147

4050

366

1656

3312

80

2585 1436x2445 1436x2445 933x1945

400

18704

11009

44500

26192

5147

5147

4050

366

1889

3778

80

3085 1669x2945 1669x2945 933x2650

500

22399

13184

54000

31783

5147

5147

4050

366

1889

3778

80

3585 1669x3445 1669x3445 1199x3150

650

28725

16907

71400

42025

5147

5147

4050

366

2366

4732

80

3697 2146x3557 2146x3557 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
K* - Distance with the sets with drop eliminator
H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).

VS -

15

size of an AHU

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

45

Supply-exhaust AHUs: rotary exchanger


Heating, Cooling

A
90

Base AHU
VS 21650 sizes
K

H
Hs
L

VS -

- R - RHC

VS 21650 sizes
K

H
Hs
L

VS -

VS

- R - RCH

H2*Hs*H*
Vmin Vmin Vmax* Vmax*LL*L1KK* (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[m3/h] [CFM] [m3/h] [CFM] [mm] [mm] [mm] [mm] [mm][mm][mm][mm][mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1193

702

2200

1295

3318

3684

2221

1097

1463

528 / 544

976 / 992

80 / 96

961

313x821

313x821

250x660

30

1586

933

3100

1825

3318

3684

2221

1097

1463

660 / 676

1240 / 1256

80 / 96

961

440x821

440x821

380x613

40

2099

1235

4100

2413

3318

3684

2221

1097

1463

660 / 676

1240 / 1256

80 / 96

1168 440x1028 440x1028

55

2878

1694

6054

3563

3684

4050

2587

1463

1829

795 / 811

1510 / 1526

80 / 96

1339 575x1199 575x1199 440x1028

75

3805

2240

8150

4797

3684

4050

2587

1463

1829

915 / 931

1750 / 1766

80 / 96

1480 695x1340 695x1340 575x1199

100

4863

2862

10700

6298

4050

4415

2953

1829

2194

1015 / 1031

1950 / 1966

80 / 96

1660 795x1520 795x1520 695x1340

120

5985

3523

13300

7828

4050

4415

2953

1829

2194

1052 / 1068

2024 / 2040

80 / 96

1891 832x1751 832x1751 795x1520

150

7415

4364

16400

9653

4050

4415

2953

1829

2194

1153 / 1169

2226 / 2242

80 / 96

2085 933x1945 933x1945 795x1520

180

8640

5085

19900

11713

4050

4050

2953

1829

1357

2714

80

2085 1137x1945 1137x1945 795x1520

230

10640

6262

24600

14479

4050

4050

2953

1829

1357

2714

80

2493 1137x2353 1137x2353 740x1913

300

13491

7941

32900

19364

4415

4415

3318

2194

1656

3312

80

2585 1436x2445 1436x2445 933x1945

400

18704

11009

44500

26192

4415

4415

3318

2194

1889

3778

80

3085 1669x2945 1669x2945 933x2650

500

22399

13184

54000

31783

4415

4415

3318

2194

1889

3778

80

3585 1669x3445 1669x3445 1199x3150

650

28725

16907

71400

42025

4416

4416

3319

2194

2366

4732

80

3697 2146x3557 2146x3557 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
K* - Distance with the sets with drop eliminator
H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.
Applying a priority air treatment function.
Change of interrelated settings of a heater and a cooler results in changing the code of a specific AHU.

46

440x821

Supply-exhaust AHUs: rotary exchanger


Mixing box, Heating, Cooling
Base AHU
VS 21650 sizes
K

H
Hs
L

VS -

- R - RMHC

VS 21650 sizes
K

H
Hs
L

VS -

VS

- R - RMCH

H 2*Hs*H*
Vmin Vmin Vmax* Vmax* LL*L1KK* (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[m3/h] [CFM] [m3/h] [CFM] [mm] [mm] [mm] [mm] [mm][mm][mm][mm][mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1193

702

2200

1295

4050

4415

2587

731

1097

528 / 544

976 / 992

80 / 96

961

313x821

313x821

250x660

30

1586

933

3100

1825

4050

4415

2587

731

1097

660 / 676

1240 / 1256

80 / 96

961

440x821

440x821

380x613

40

2099

1235

4100

2413

4050

4415

2587

731

1097

660 / 676

1240 / 1256

80 / 96

1168

440x1028 440x1028

440x821

55

2878

1694

6054

3563

4415

4781

2953

731

1097

795 / 811

1510 / 1526

80 / 96

1339

575x1199 575x1199 440x1028

75

3805

2240

8150

4797

4415

4781

2953

731

1097

915 / 931

1750 / 1766

80 / 96

1480

695x1340 695x1340 575x1199

100

4863

2862

10700

6298

4781

5147

3318

731

1097

1015 / 1031

1950 / 1966

80 / 96

1660

795x1520 795x1520 695x1340

120

5985

3523

13300

7828

4781

5147

3318

731

1097

1052 / 1068

2024 / 2040

80 / 96

1891

832x1751 832x1751 795x1520

150

7415

4364

16400

9653

5147

5513

3684

731

1097

1153 / 1169

2226 / 2242

80 / 96

2085

933x1945 933x1945 795x1520

180

8640

5085

19900

11713 5147

5147

3684

731

1357

2714

80

2085 1137x1945 1137x1945 795x1520

230

10640

6262

24600

14479 5147

5147

3684

731

1357

2714

80

2493 1137x2353 1137x2353 740x1913

300

13491

7941

32900

19364 5513

5513

4050

731

1656

3312

80

2585 1436x2445 1436x2445 933x1945

400

18704

11009

44500

26192 5513

5513

4050

731

1889

3778

80

3085 1669x2945 1669x2945 933x2650

500

22399

13184

54000

31783 5513

5513

4050

731

1889

3778

80

3585 1669x3445 1669x3445 1199x3150

650

28725

16907

71400

42025 5513

5513

4050

731

2366

4732

80

3697 2146x3557 2146x3557 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
K* - Distance with the sets with drop eliminator
H*, H2*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).

VS -

15

size of an AHU

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

47

Supply-exhaust AHUs: rotary exchanger


Heating, Cooling, Heating
Base AHU

VS 21650 sizes
K

H
Hs
L

VS -

VS

- R - RHCH

H2*Hs*H*
Vmin Vmin Vmax* Vmax*LL*L1KK* (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[m3/h] [CFM] [m3/h] [CFM] [mm] [mm] [mm] [mm] [mm][mm][mm][mm][mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1193

702

2200

1295

3684

4050

2221

1463

1829

528 / 544

976 / 992

80 / 96

961

313x821

313x821

250x660

30

1586

933

3100

1825

3684

4050

2221

1463

1829

660 / 676

1240 / 1256

80 / 96

961

440x821

440x821

380x613

40

2099

1235

4100

2413

3684

4050

2221

1463

1829

660 / 676

1240 / 1256

80 / 96

1168 440x1028 440x1028

55

2878

1694

6054

3563

4050

4415

2587

1829

2194

795 / 811

1510 / 1526

80 / 96

1339 575x1199 575x1199 440x1028

75

3805

2240

8150

4797

4050

4415

2587

1829

2194

915 / 931

1750 / 1766

80 / 96

1480 695x1340 695x1340 575x1199

100

4863

2862

10700

6298

4415

4781

2953

2194

2560

1015 / 1031

1950 / 1966

80 / 96

1660 795x1520 795x1520 695x1340

120

5985

3523

13300

7828

4415

4781

2953

2194

2560

1052 / 1068

2024 / 2040

80 / 96

1891 832x1751 832x1751 795x1520

150

7415

4364

16400

9653

4415

4781

2953

2194

2560

1153 / 1169

2226 / 2242

80 / 96

2085 933x1945 933x1945 795x1520

180

8640

5085

19900

11713

4415

4415

2953

2194

2194

1357

2714

80

2085 1137x1945 1137x1945 795x1520

230

10640

6262

24600

14479

4415

4415

2953

2194

2194

1357

2714

80

2493 1137x2353 1137x2353 740x1913

300

13491

7941

32900

19364

4781

4781

3318

2560

2560

1656

3312

80

2585 1436x2445 1436x2445 933x1945

400

18704 11009

44500

26192

4781

4781

3318

2560

3291

1889

3778

80

3085 1669x2945 1669x2945 933x2650

500

22399 13184

54000

31783

4781

4781

3318

2560

3291

1889

3778

80

3585 1669x3445 1669x3445 1199x3150

650

28725 16907

71400

42025

4782

4782

3319

2560

3291

2366

4732

80

3697 2146x3557 2146x3557 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
K* - Distance with the sets with drop eliminator
H*, H2, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.
Applying a priority air treatment function.

48

440x821

Supply-exhaust AHUs: rotary exchanger


Mixing box, Heating, Cooling, Heating
Base AHU

VS 21650 sizes
K

H
Hs
L

VS -

VS

- R - RMHCH

H2*Hs*H*
Vmin Vmin Vmax* Vmax*LL*L1KK* (H(min) / (H(max)) (H2(min) / H2(max)) (Hs(min) / (Hs(max)) W
[m3/h] [CFM] [m3/h] [CFM] [mm] [mm] [mm] [mm] [mm][mm][mm][mm][mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1193

702

2200

1295

4415

4781

2587

1097

1463

528 / 544

976 / 992

80 / 96

961

313x821

313x821

250x660

30

1586

933

3100

1825

4415

4781

2587

1097

1463

660 / 676

1240 / 1256

80 / 96

961

440x821

440x821

380x613

40

2099

1235

4100

2413

4415

4781

2587

1097

1463

660 / 676

1240 / 1256

80 / 96

1168 440x1028 440x1028

55

2878

1694

6054

3563

4781

5147

2953

1097

1463

795 / 811

1510 / 1526

80 / 96

1339 575x1199 575x1199 440x1028

440x821

75

3805

2240

8150

4797

4781

5147

2953

1097

1463

915 / 931

1750 / 1766

80 / 96

1480 695x1340 695x1340 575x1199

100

4863

2862

10700

6298

5147

5513

3318

1097

1463

1015 / 1031

1950 / 1966

80 / 96

1660 795x1520 795x1520 695x1340

120

5985

3523

13300

7828

5147

5513

3318

1097

1463

1052 / 1068

2024 / 2040

80 / 96

1891 832x1751 832x1751 795x1520

150

7415

4364

16400

9653

5513

5878

3684

1097

1463

1153 / 1169

2226 / 2242

80 / 96

2085 933x1945 933x1945 795x1520

180

8640

5085

19900 11713

5513

5513

3684

1097

1357

2714

80

2085 1137x1945 1137x1945 795x1520

230

10640

6262

24600 14479

5513

5513

3684

1097

1357

2714

80

2493 1137x2353 1137x2353 740x1913

300

13491

7941

32900 19364

5878

5878

4050

1097

1656

3312

80

2585 1436x2445 1436x2445 933x1945

400

18704 11009 44500 26192

5878

5878

4050

1097

1889

3778

80

3085 1669x2945 1669x2945 933x2650

500

22399 13184 54000 31783

5878

5878

4050

1097

1889

3778

80

3585 1669x3445 1669x3445 1199x3150

650

28725 16907 71400 42025

5879

5879

4050

1097

2366

4732

80

3697 2146x3557 2146x3557 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
K* - Distance with the sets with drop eliminator
H*, H2, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).

VS -

15

size of an AHU

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

49

Supply-exhaust AHUs: glycol system


Heating
Base AHU

VS 21650 sizes

HxW

Hs
L

VS -

VS

- R - GH

Hs*H*
Vmin Vmin Vmax* Vmax*L(H(min) / (H(max)) (Hs(min) / (Hs(max)) W
[m3/h] [CFM] [m3/h] [CFM] [mm][mm][mm][mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1167

687

3080

1813

1856

528 / 544

80 / 96

660

313x821

313x821

250x660

30

1586

933

4322

2544

1856

660 / 676

80 / 96

800

440x821

440x821

380x613

40

1958

1152

5661

3332

1856

660 / 676

80 / 96

961

440x1028

440x1028

440x821

55

2878

1694

8216

4836

2221

795 / 811

80 / 96

961

575x1199

575x1199

440x1028

75

3805

2240

11379

6697

2221

915 / 931

80 / 96

1168

695x1340

695x1340

575x1199

100

4863

2862

13550

7975

2587

1015 / 1031

80 / 96

1339

795x1520

795x1520

695x1340

120

5815

3423

18079

10641

2587

1052 / 1068

80 / 96

1480

832x1751

832x1751

795x1520

150

7167

4218

22420

13196

2587

1153 / 1169

80 / 96

1660

933x1945

933x1945

795x1520

180

8640

5085

27220

16021

2587

1357

80

1891

1137x1945 1137x1945

795x1520

230

10398

6120

33460

19694

2587

1357

80

2085

1137x2353 1137x2353

740x1913

300

13491

7941

44760

26345

2953

1656

80

2085

1436x2445 1436x2445

933x1945

400

18704

11009

60501

35610

2953

1889

80

2493

1669x2945 1669x2945

933x2650

500

21817

12841

74350

43761

2953

1889

80

2585

1669x3445 1669x3445 1199x3150

650

28725

16907

98500

57975

2953

2366

80

3085

2146x3557 2146x3557 1520x3250

H*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.

50

Supply-exhaust AHUs: glycol system


Heating, Cooling
Base AHU
VS 1015 sizes (suspended)*

HxW

Hs
L

VS -

- R - GHC

VS 21650 sizes

HxW

Hs
L

VS -

VS

- R - GCH

Hs*H*
L*(H(min) / (H(max)) (Hs(min) / (Hs(max)) W
[mm][mm][mm][mm]

Vmin Vmin Vmax* Vmax*L


[m3/h] [CFM] [m3/h] [CFM] [mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1167

687

2200

1295

2221

2587

528 / 544

80 / 96

961

313x821

313x821

250x660

30

1586

933

3100

1825

2221

2587

660 / 676

80 / 96

961

440x821

440x821

380x613

40

1958

1152

4100

2413

2221

2587

660 / 676

80 / 96

1168

440x1028

440x1028

440x821

55

2878

1694

6054

3563

2587

2953

795 / 811

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

8150

4797

2587

2953

915 / 931

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

10700

6298

2953

3318

1015 / 1031

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

13300

7828

2953

3318

1052 / 1068

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

16400

9653

2953

3318

1153 / 1169

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

19900

11713

2953

2953

1357

80

2085

1137x1945 1137x1945

795x1520

230

10398

6120

24600

14479

2953

2953

1357

80

2493

1137x2353 1137x2353

740x1913

300

13491

7941

32900

19364

3318

3318

1656

80

2585

1436x2445 1436x2445

933x1945

400

18704

11009

44500

26192

3318

3318

1889

80

3085

1669x2945 1669x2945

933x2650

500

21817

12841

54000

31783

3318

3318

1889

80

3585

1669x3445 1669x3445 1199x3150

650

28725

16907

71400

42025

3319

3319

2366

80

3697

2146x3557 2146x3557 1520x3250

L* - Length of the supply section in conguration with drop eliminator installed behind the cooler
K* - Distance with the sets with drop eliminator
H*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).

VS -

15

size of an AHU

SE

access side
optional
functions
R - right
before a base
L - left (the option
AHU
available for VS 21-650
units)

PHCH
code of a base
AHU

EF
optional
functions
behind a base
AHU

the assembly method for VS 10-15 AHUs


(suspended AHUs)
COMPACT compact AHU

51

Exhaust AHUs: glycol system


Base AHU

VS 21650 sizes

HxW

Hs
L

VS -

VS

- R -G

Hs*H*
Vmin Vmin Vmax* Vmax*L(H(min) / (H(max)) (Hs(min) / (Hs(max)) W
[m3/h] [CFM] [m3/h] [CFM] [mm][mm][mm][mm]

hxw
[mm]

hxw
[mm]

h1 x w1
[mm]

21

1167

687

3080

1813

1490

528 / 544

80 / 96

961

313x821

313x821

250x660

30

1586

933

4322

2544

1490

660 / 676

80 / 96

961

440x821

440x821

380x613

40

1958

1152

5661

3332

1490

660 / 676

80 / 96

1168

440x1028

440x1028

440x821

55

2878

1694

8216

4836

1856

795 / 811

80 / 96

1339

575x1199

575x1199

440x1028

75

3805

2240

11379

6697

1856

915 / 931

80 / 96

1480

695x1340

695x1340

575x1199

100

4863

2862

13550

7975

2221

1015 / 1031

80 / 96

1660

795x1520

795x1520

695x1340

120

5815

3423

18079

10641

2221

1052 / 1068

80 / 96

1891

832x1751

832x1751

795x1520

150

7167

4218

22420

13196

2221

1153 / 1169

80 / 96

2085

933x1945

933x1945

795x1520

180

8640

5085

27220

16021

2221

1357

80

2085

1137x1945 1137x1945

795x1520

230

10398

6120

33460

19694

2221

1357

80

2493

1137x2353 1137x2353

740x1913

300

13491

7941

44760

26345

2587

1656

80

2585

1436x2445 1436x2445

933x1945

400

18704

11009

60501

35610

2587

1889

80

3085

1669x2945 1669x2945

933x2650

500

21817

12841

74350

43761

2587

1889

80

3585

1669x3445 1669x3445 1199x3150

650

28725

16907

98500

57975

2587

2366

80

3697

2146x3557 2146x3557 1520x3250

H*, Hs* - heights options details on page 54

Vmax - Parametres description on page 20

Optional functions are presented on the bookmark (in the back cover).
** Optional functions are available for VS 21650 AHUs only.
*** Optional function is available for VS 10650 AHUs (VS 1015 AHUs are equipped with the function of mixing defined just as a set of two air dampers).
Inlet/Outlet configurations of E empty section are presented on page 53 and on the bookmark.
Inlet/Outlet configurations of M mixing box are presented on page 53 and on the bookmark.
Dimensions of optional functions are presented on page 53 and on the bookmark.

52

Optional functions and accessories

Optional functions
NElectric
pre-heater

E - empty section

S - silencer

LH

VS

LH
[mm]

mH
[kg]

VS

LE
[mm]

mE
[kg]

VS

LS
[mm]

mS
[kg]

10

731

31

10

15

731

37

15

22

10

731

26

25

15

731

21

731

44

31

313x821

220x500

33

21

1097

30

731

60

731

440x821

220x500

36

30

1097

40

68

40

731

440x1028

250x660

40

40

1097

79

55

731

575x1199

440x821

47

55

1097

101

hxw
[mm]

h2 x w2
[mm]

731

220x500

731

250x660

21

731

49

30

731

56

55

731

67

75

731

75

75

731

695x1340 440x1028

54

75

1097

116

100

731

86

100

731

795x1520 575x1199

60

100

1097

141

120

731

94

120

731

832x1751 575x1199

65

120

1097

159

150

731

105

150*

731/1097

933x1945 795x1520

72/116

150

1097

178

180

731

121

180*

731/1097 1137x1945 795x1520

81/132

180

1097

205

230

731

133

230*

731/1097 1137x2353 933x1945

89/148

230

1097

243

300

731

149

300*

731/1097 1436x2445 933x1945

100/171

300

1463

345

400

731

182

400*

731/1097 1669x2945 933x2650

125/217

400

1463

510

500

500*

731/1097 1669x3445 933x3150

136/241

500

1463

580

650

650*

731/1097 2146x3557 933x3250

150/280

650

1463

702

* Data regarding length and weight refers to the section with a horizontal or a top/bottom inlet/outlet respectively.

M - mixing box

VS

LM
[mm]

10
15

F - secondary lter

mM
[kg]

VS

LF
[mm]

mF
[kg]

10

15

220x500

213x380

40

21

731

39

731

220x500

313x380

43

30

731

43

731

250x660

313x380

49

40

731

47

55

731

440x821

413x380

62

55

731

57

75

731

440x1028

413x380

73

75

731

69

100

731

575x1199

613x380

85

100

731

78

120

731

575x1199

613x380

91

120

731

83

150

1097

795x1520

713x740

126

150

731

94

180

1097

795x1520

913x740

155

180

731

106

230

1097

933x1945

913x740

188

230

731

117

300

1097

933x1945 1213x740

202

300

731

140

400

1097

933x2650 1513x740

252

400

731

181

500

1097

933x3150 1513x740

282

500

731

200

650

1097

933x3250 1913x740

304

650

731

230

h2 x w2
[mm]

h3 x w 3
[mm]

21

731

30
40

Accessories

FC - exible connection

AD - air damper

53

CASING
VENTUS

Function and application

Operation parameters

Construction: Non-skeleton casing


Non-skeleton construction made of sandwich type
panels formed in C shape and reinforced with an
inner system of bulkheads.
Panels construction:
- external material: zinc coated steel sheet
S280GD+Z275 covered with anticorrosive coating;
- insulation: polyurethane foam.

Casing:
operation temperature: -40 +90C
Casing equipped with a system of connectors enabling casing heat transfer coefcient
suspension of the unit.
K= 0,6 W/mKCLASS T2 Acc. EN 1886:2007
thermal bridges coefcient:
Access to an AHU: from the bottom.
Kb = 0,69CLASS TB2 Acc. EN 1886:2007
mechanical strength of casing:
AHU designed for indoor installation.
-2500 Pa 2500 Pa < 2mm CLASS D1 Acc. EN 1886:2007
casing tightness:
-400 Pa - 0,05 l/smCLASS L1 Acc. EN 1886:2007

VS 1015

+700 Pa - 0,13 l/sm

Non-skeleton construction made on the basis of


sandwich type panels formed in C shape and
reinforced with an inner frame system.
Panels construction:
- external material: zinc coated steel sheet
S280GD+Z275 covered with anticorrosive coating;
- insulation: polyurethane foam;
- internal material: zinc coated steel sheet
S280GD+Z275.
VS 21650
Casing:
- VS 21-150 xed to anges (poliamid) or easyto-transport steel frame (optional), ability of both
suspension and foundation of the whole installation
on the oor.
- VS 180-650 xed to easy-to-transport steel frame
enable to place whole installation on the oor.
Access to the unit: from the side.

CLASS L1 Acc. EN 1886:2007

Panels:
operation temperature: -40 +90C
panel thickness: 40mm
metal sheet thickness: 0,5mm
thermal conductivity
PPU = 0,022 W/mK
casing re rating:
non-ammable material (NRO)
moisture absorption: 0,04%
PPU density: = 42kg/m
panel weight: m= 10kg/m
Color RAL 7031
Anticorrosive protection:
275g/m galvanized zinc (Zn) coating
external protection coating material/thickness:
polyester / 25m
Compliance with standards: EN1886.

Unit designed for both indoor and outdoor


installation.
Available options of AHU location
Location options

Supports

VS 21150
AHU

Transport
- foundation
frame

Transport
frame

VS 180-650
AHU

54

Foundation
frame

Hs = 80
[mm]

Hs = 80
[mm]

Hs = 96
[mm]

Hs = 80
[mm]

Supply AHUs

Exhaust AHUs

Supply and exhaust AHUs

The option is available for all systems

The option is available for all systems

The option is available for all systems

Possible transport up to 3.3 [m]

Possible transport up to 3.3 [m]

Transport not available

The option is available for all systems

The option is available for all systems

The option is available for all systems

Possible transport of systems up to 4.4


[m] equipped with a homogeneous
longitudinal element of the frame

Possible transport of systems up to 4.4


[m] equipped with a homogeneous
Possible transport of systems up to 4.4
longitudinal element of the frame and
[m] equipped with a homogeneous
with the top part projecting over the
longitudinal element of the frame
bottom one

The option is available for all systems


with the total length of 4.8-9.2 [m]

The option is available for all systems


The option is available for all systems with the total length of 4.8-9.2 [m], and
with the top part projecting over the
with the total length of 4.8-9.2 [m]
bottom one

Possible transport of all systems

Possible transport of all systems

Possible transport of AHUs with the top


part projecting over the bottom one

The option is available for all systems

The option is available for all systems

The option is available for all systems

Possible transport of systems up to 4.4


[m] equipped with a homogeneous
longitudinal element of the frame

Possible transport of systems up to 4.4


[m] equipped with a homogeneous
longitudinal element of the frame

Transport not available

Advantages

Teaching aids
Access side: VS 1015

energy loss reduction no thermal bridges


elimination of moisture condensation
phenomenon
high rigidity of construction
labyrinth modules connection elimination
of air leakages

Right hand access side

Left hand access side

Installation of: VS 1015


Suspended VENTUS AHUs, due to their small
dimensions and low weight, are ideal for installation
in the structural areas of buildings (suspended ceilings,
raised oors) directly in the ventilation duct system.
VS 1015 AHUs can also be installed vertically by
specic air processing units (lter, fan, water heater,
silencer).

elimination of moisture absorption


insulation material with a very long
decomposition period
smooth internal surfaces of the casing easy
to maintain hygiene
light inspection panels - easy handling

high resistance to external atmospheric


factors
high resistance to mechanical factors

Non-skeleton technology
In the construction of VTS AHUs a modern non-skeleton
technology is applied. The casing made of homogenous
laminar panel in C shape contains appropriate subassemblies carrying out a desired air handling process.
This kind of construction in connection with a labyrinth
system of modules connection constitutes a perfectly tight
system similar in its construction to a vacuum ask. As a
result both the number of thermal bridges (elimination of
energy loss and moisture condensation phenomena) as
well as air leakages have been reduced.
VENTUS AHUs

Frame constructions

non-skeleton casing

Access side: VS 21650

Right hand access side

Left hand access side

Connection pins of the exchangers for STANDARD AHUs are located on the access side and for the COMPACT AHUs
on the opposite side.

Device location
The AHU should be located in such a way so as to
enable connection of related systems (ventilation
ducts, piping, cable trays) without getting in the way
of inspection panels. For efcient installation,
operation and maintenance of the AHU, the
minimum distances between the access side and
xed structural components of the installation
location (walls, supports, pipelines, etc.) should be
kept.

W + 150

The access space can be built up with systems,


pipelines, support structures only in a way which
permits easy disassembly and assembly during
maintenance.
In the case of COMPACT AHUs it is necessary to take
an apropriate space for connecting exchangers on the
side opposite to the access side into consideration.

W x 0,9

Access space

55

FILTERS
Pre-lters

Function and application

Construction

Flat lters
Ventilation and air conditioning systems for rooms with
average requirements of air purity as the nal lter.

G4 type

Ventilation and air conditioning systems with high


purity requirements as a pre-lter in front of higher
efciency lters. Possible applications:
- hotels;
- restaurants;
- cinemas;
- theatres;
- department stores;
- concert halls.

pleated lter material encased in a wire mesh installed


in a frame 50mm thick
lter material made of polyester ber fabric
Assembly: system of guide rails enabling quick
and easy replacement of lters.

VS 10650

Preliminary bag lters


Ventilation and air conditioning systems for rooms with
average requirements of air purity as the nal lter.

G4/F5 type

Ventilation and air conditioning systems with high


purity requirements as a pre-lter before higher
efciency lters. Possible applications:
- hotels;
- restaurants;
- cinemas;
- theatres;
- department stores;
- concert halls.

ltration bags 300mm long installed in a frame 25mm


thick
lter material made of polyester ber fabric
vertical arrangement of ltration bags
Assembly: system of guide rails enabling quick
and easy replacement of lters.

VS 21650

Secondary lters

Function and application

Construction

Secondary bag lters


Ventilation and air conditioning systems for rooms
with high requirements of air purity as the nal lter:
- hospitals;
- pharmaceuticals;
- food industry;
- varnishing chambers;
- dehumidication chambers.

ltration bags 600mm long installed in a frame 25mm


thick
lter material made of polyester ber fabric
vertical arrangement of ltration bags

Ventilation and air conditioning systems for clean


rooms as the nal ltration stage.

ltration bags 600mm long installed in a frame 25mm


thick
lter material made of polyester ber fabric
vertical arrangement of ltration bags

Assembly: system of guide rails enabling quick


and easy replacement of lters.

F7 type

VS 21650

Secondary bag lters

F9 type

VS 21650

56

Ventilation and air conditioning systems for clean


rooms as the pre-lter stage for activated carbon
lters:
- production of electronic components,
- production of optical components,
- sterile operating theatres,
- pharmaceutical clean rooms.

Assembly: system of guide rails enabling quick


and easy replacement of lters.

Operation parameters

Teaching aids
Filter congurations

average ltration ratio Am=92%


max. pressure difference: p=150Pa
max. air velocity: v=4,2m/s
lter bypass leakage F9 Acc. EN 1886
ambient temperature: max. 70C / 100%

- in base units:
G4 at lter
ref. VS 10650

G4/F5 bag lter


ref. VS 21-650

- in optional functions - ref.VS 21:650 AHUs


Protection: The permitted level of lter contamination may be
signaled by the pressure differential control (an optional element).

G4 at lter

G4/F5 bag lter

F7/F9 bag lter

Compliance with standards: EN779.


Filters dimensions in optional functions are demonstrated on page 53
and on the bookmark including optional functions.

Classication of lters used

average ltration ratio Am=90%


max. pressure difference:
G4 - p=150Pa
F5 - p=250Pa
max. air velocity: v=4,6m/s
lter bypass leakage F9 Acc. EN 1886
ambient temperature: max. 70C / 100%
Protection: the permitted level of lter contamination may be
signaled by the pressure differential control (an optional element).

Class

B2

<85%
(gravimetric ltration
method)

initial efciency

>75%
(gravimetric ltration
method)

Average ltration
efciency

>90%
(gravimetric ltration
method)

>95%
(gravimetric ltration
method)

>85%
(parafn oil mist
method)

ASHRAE
St.52.2;1999

Class

MERV
6,6-7, 7-8, 6-8

EN 779:1992
greenDIN 24184

Class

G4

F5

F7

F9

Class

EU4

EU5

EU7

EU9

DIN 24185
EUROVENT 4/5

average effectiveness
for particulate

PN-B-76003:1996

MERV
8-9, 9-10

90%< m_A

Initial pressure of a clean lter [Pa]

50-80

150

Compliance with standards: EN779.

MERV
13-14

MERV
15

40%< m_E 80%< m_E


<_60%
<_90%

30-60

Maximum allowed pressure drop [Pa]

95< m_E

100-200

150-250

250

350

Sizes of some particulate in the air


nest

Operation parameters

ne

coarse
standard

FILTER TYPE

precipitator

active carbon

average ltration ratio Em= 8085%


max. pressure difference: p=250Pa
max. air velocity: v=3,6m/s
lter bypass leakage F9 Acc. EN 1886
ambient temperature: max. 70C / 100%

cyclone separators
sedimentation chambers

vapors
solid air pollutants

regular particulate

PARTICLE SIZE
viruses

bacteria

smoke or fumes

Protection: The permitted level of lter contamination may be


signaled by the pressure differential control (an optional element).

ultrashort waves

ultraviolet light

0,01

0,1

drops

y ash

visible light

WAVE
rtg radiation
LENGTH

0,001

rain
drizzle

soot

oil mist

Compliance with standards: EN779.

MKM

pollen
fog

tobacco smoke

macromolecules

heavy particulate

infrared light

10

100

1000

source: Recknagel, Sprenger

Average particulate content in air


average ltration ratio Em=9095%
recommended lter change: p=350Pa
max. air velocity: v=3,6m/s
lter bypass leakag F9 Acc. EN 1886
ambient temperature: max. 70C / 100%

Technological area or process

Non-urban areas
Large urban area

Protection: The permitted level of lter contamination may be


signaled by the pressure differential control (an optional element).
Compliance with standards: EN779.

During rain
During dry periods
Residential area
Industrial area
Industrial facilities
Habitats
Department stores
Workshops
Cement factories
Air in mines
Hand loaded
Mechanically loaded
Furnace ue gases

Coke red furnace


ue gases

Average
concentration
[mg/m3]
0,05
0,10
0,10
0,30-0,5

Most frequent
particle size
[mm]
0,8
2,0
7,0
20

Upper Limit
of the size
of particles [mm]
4
25
60
100

1,0-3,0
1-2
2-5
1-10
100-200
100-300
10-50
100-200
1000-15000

60
-

1000
-

source: Recknagel, Sprenger

57

Exchangers
Heaters

Function and application

Construction

Water heater
Heating of the air supplied to the room.
Heating of the air after the dehumidication process.
Used if a heating water system is available (local
boiler or municipal heating system).

WCL type

Water heater

40

~80*
~120**

c1

c1

DN

* VS 1040
** VS 55650

copper pipes with aluminium plate ns (Cu/Al)


distance between ns:
VS 1015 - 2,1mm
VS 21650 - 2,5mm
n thickness: 0,1mm (Al)
pipe wall thickness: 0,37mm
pipe diameter:
VS 1015
VS 21650
collector diameter::

VS

DN

Material

Connection

10,15

20

brass

thread R3/4

21
30,40 (4R)

25

brass

thread R1

30,40
55,75 (4R)
100,120,150 (2R)

32

brass

thread R11/4

55 (6R,8R)
100,120,150 (4R)
180 (2R)

50

steel

thread R2

120 650

80

steel

thread R3

180 400 (8R)


500 650 (2R)

2x80

steel

thread 2xR3

number of heater rows R: 28


connections of exchanger are equipped with drain and
vent
The connectors are on the tending side of the AHU.
Connecting the exchanger to the power supply in a
cocurrent system results in reduction of the heating
capacity of more than 10%.
Exchanger is connected to the hot water supply by
means of the top or bottom connector depending
on the access side of the AHU in order to enable
countercurrent air ow with reference to liquid ow in
the cooler universal design of exchanger: right/left.

Electrical heater
Heating of the air supplied to the room.
Heating of the air after the dehumidication process.
Used when heating water is not available or in case
of lower heating powers.

HE type

If the device is staged together with a control system,


the heater is integrated with a control module.
The wires are connected to the terminal strip of the
exchanger on the AHU access side.
Desired power can be obtained by means of the system
of smooth regulation (HE module as an optional control
element) or gradual regulation (a diagram of connections available in the manual).

VS 10650

Electrical heater

58

a complex of resistance heating elements made of Cr-Ni-Fr


alloy, power: 6kW/400V each
casing: frame made of zinc-coated steel
terminal strip
as standard, the heater is equipped with an overheat protection thermostat

Operation parameters

Teaching aids
Water heater capacity

max. temp. of the liquid: up to 150C (with the system control up to


140C)
max. operation pressure of the liquid: 1.6 MPa = 16 bar (tested 21
bar)
max. allowed air velocity: v = 4,4 m/s
max. glycol content: 50%
heating capacity - available in technical specication (CCOL)
uid pressure drop and uid ow rate - available in technical
specication (CCOL)
air gaps between the exchanger frame and the AHU casing: <2 mm

Heating capacity of water heater for heating the air flow rate V [m 3/h] from
temperature at point 1 to temperature at point 2 (x=const.)

Protection: Allowed minimum air temperature after the


exchanger is monitored by the anti-freeze thermostat (an
optional element).

Water heater thermal capacity (air)

Distance

Q = Mw cpw(tw1-tw2) [kW]
t w1 [C] water temperature before the heater
t w2 [C] water temperature after the heater
M w [kg/s] water flow rate
c pw = 4,19 kJ/kgK specific heat of water
x2

0%
=10

Q = V/3600 p cp(t2-t1) [kW]*

Geometry of water heaters


VS

Water heater capacity (liquid)

Exchangers Capacity

C [mm]

C1[mm]

2R [l]

4R [l]

6R [l]

8R [l]

10

115

0,70

1,40

2,10

15

140

1,04

2,08

3,12

21

164

1,77

3,54

5,31

7,08

30

294

2,48

4,96

7,43

9,91

40

294

3,25

6,49

9,74

12,98

55

347

4,71

9,42

14,14

18,85

75

459

6,53

13,05

19,58

26,11

100

554

8,54

17,08

25,62

34,15

120

586

10,37

20,74

31,11

41,48

150

681

12,87

25,74

38,61

51,47

180

872

380

15,62

31,24

46,86

62,47

230

872

379

19,2

38,39

57,59

76,78

300

1189

478

25,69

51,38

77,07

102,76

400

1380

554

34,71

69,42

104,13

138,84

500

1412

553

42,65

85,30

127,95

170,6

650

1888

711

56,79

113,58

170,37

227,16

The exchange surface area can be found on page 61 in teaching


aids.

V [m 3/h] air flow rate


t 1 [C] air temperature before the heater
t 2 [C] air temperature after the heater
p [kg/m 3] air density (1,2 kg/m 3 for 20C)
c p [kJ/kgK] = 1,005 specific heat of dry air
* estimated value

x1

t2>t1
x2=x1

or/and

Q = V/3600 p (h2-h1) [kW]


V [m 3/h] air flow rate
h 1 [kJ/kg] enthalpy of air before the heater
h 2 [kJ/kg] enthalpy of air after the heater
p [kg/m 3] air density (1,2 kg/m 3 for 20C)

Temperature and humidity in a room


The human body continuously emits heat, the amount of which depends on the level
of physical activity. In order to assess the amount of the heat a unit called MET is used.
When people are idle the coefcient is 58W from each sqm of the surface of human
body. We would like to remind you that an average person has a body surface
of 1.8 sqm. Since indoor air must receive the heat emitted by people the air
temperature in the room is a parameter determining the state of heat comfort.
Most often it can be assumed that the optimum temperature is: for winter 20-22C,
for summer 22-24C. The relative humidity limits are from 35 to 65% (see graph).

Compliance with standards: EN 305, EN 1216, EN 13053.

max. allowed air velocity:


v= 4,5m/s
max. allowed ambient temperature around heating elements:
65C
airs gaps between the exchanger frame and AHU casing: < 2mm
heating elements joined in groups: power: 18kW each

Permissible temperature (summer)

air temperature
in a room C

Capacity range for specic sizes of AHUs


VS

Pel [kW]

10
15
21
30
40
55
75
100
120
150
180
230
300
400
500
650

18
36
36
54
72
90
90
108
108
108
108
108
108
108
212
212

outdoor temperature: _C

Air humidity in a room

Fig. Diagram illustrating connections of heating elements

Source: EN ISO 7730, ASHRAE 55.

59

Exchangers
Coolers

Function and application

Construction

Water cooler
Cooling of the air supplied to the room.
Air dehumidication during summer.
Exchanger used in complex air conditioning systems
several or even more units powered from one
source of chilledwater system (chiller) or in case of
using a unit with a relatively high cooling capacity.

copper pipes with aluminium plate ns (Cu/Al)


in pitch distance between ns:
VS 1015 - 2,1mm
VS 21650 - 2,5mm
n thickness: 0,1mm (Al)
pipe wall thickness: 0,37mm
pipe diameter:
VS 1015
VS 21650
Collector diameter:

WCL type

Water cooler
40

~80*
~120**

c1

c1

DN

* VS 1040
** VS 55650

VS

DN

Material

Connection

10,15

20

brass

thread R3/4

21
30,40 (4R)

25

brass

thread R1

30,40
55,75 (4R)
100,120,150 (2R)

32

brass

thread R11/4

55 (6R,8R)
100,120,150 (4R)
180 (2R)

50

steel

thread R2

120 650

80

steel

thread R3

180 400 (8R)


500 650 (2R)

2x80

steel

thread 2xR3

number of cooler rows R: 28


drain pan (made of stainless steel)
connectors of the exchanger are equipped with the drain
and vent
The connectors are on the access side of the AHU.
Connecting the exchanger to the chilled water supply
in a paralell ow fashion results in reduction of the
cooling capacity by more than 10%.

Direct expansion cooler


Cooling of air supplied to the room.
Air dehumidication during summer.
Used for lower cooling capacity systems in
comparison to water coolers (compressor units) in
single air conditioning systems.

DX type

copper pipes with aluminium plate ns (Cu/Al)


drain pan (made of stainless steel)
options:
- mono-section exchanger <100kW
- double-section exchanger (50%/50%) >50kW
n pitch distance between ns:
VS 1015 - 2,1mm
VS 21650 - 2,5mm
n thickness: 0,1mm (Al)
pipe wall thickness: 0,37mm
pipe diameter:
VS 1015
VS 21650
collector diameter:

VS

Din

Dout

1030

5/8

28

40650

DX cooler
40

number of cooler rows R: 26


The connectors are on the access side of the AHU.

60

CCOL

Operation parameters

Teaching aids

min. liquid temperature for chilled water: +2C


max. operaiton pressure of the liquid: 1.6 MPa = 16 bar (tested 21
bar)
max. glycol content: 50%
max. air velocity: v=2,8m/s
cooling capacity - available in technical specication (CCOL)
uid pressure drop and uid ow rate - available in technical
specication (CCOL)
air gap between the exchanger frame and AHU casing: < 2 mm
Geometry of water heaters
VS
10

Distance

Exchangers Capacity

C [mm]

C1[mm]

2R [l]

4R [l]

6R [l]

8R [l]

115

0,70

1,40

2,10

15

140

1,04

2,08

3,12

21

164

1,77

3,54

5,31

7,08

30

294

2,48

4,96

7,43

9,91

40

294

3,25

6,49

9,74

12,98

55

347

4,71

9,42

14,14

18,85

75

459

6,53

13,05

19,58

26,11

100

554

8,54

17,08

25,62

34,15

120

586

10,37

20,74

31,11

41,48

150

681

12,87

25,74

38,61

51,47

180

872

380

15,62

31,24

46,86

62,47

230

872

379

19,2

38,39

57,59

76,78

300

1189

478

25,69

51,38

77,07

102,76

400

1380

554

34,71

69,42

104,13

138,84

500

1412

553

42,65

85,30

127,95

170,6

650

1888

711

56,79

113,58

170,37

227,16

Exchanger is connected to the chilled water supply by means


of the top or bottom connector depending on the access side
of the AHU in order to enable counter-current air ow with
reference to liquid ow in the cooler universal design of
exchanger: right/left.
Compliance with standards: EN 305, EN 1216, EN 13053.
min. cooling agent evaporation temperature: +3C
max. operaiton pressure of the liquid: 2.2 MPa = 22 bar (tested 29
bar)
max. allowed air velocity: v = 2.8m/s
cooling capacity - available in technical specication (CCOL)
air gaps between the exchanger frame and AHU casing: < 2 mm
The exchanger can be selected for a wide range refrigerants
(R12, R22, R134a, R407c...).
Geometry of DX coolers
Distance
VS

10
15
21
30
40
55
75
100
120
150
180
230
300
400
500
650

C [mm]
195
195
244
374
374
467
586
684
718
817
1017
1021
1315
1543
1538
2014

Exchangers Capacity
3R [l]4R [l]6R [l]
2R [l]
1
sekc./1 sekc./1 sekc./
1 sekc./
2 sekc.2 sekc.2 sekc.
2 sekc.
1,05
/ x1,40 / x2,1 / x
0,7 / x
1,56 / x2,08 / x3,12 / x
1,04 / x
3,54 / x5,31/ x7,08 / x
1,77 / x
4,96 / x7,43 / x9,91 / 7,43
2,48 / x
6,49 / x9,74 / 6,4912,98 / 9,74
3,25 / x
9,42
/ 7,0714,14 / 9,42 18,85 / 21,20
4,71 / x
13,05
/ 9,79 19,58 / 13,05 26,11 / 29,37
6,53 / x
17,08 / 12,81 25,62 / 17,08x / 25,62
8,54 / 8,54
20,74
/
15,56 31,11 / 20,74x / 31,11
10,37 / 10,37
12,87 / 12,87 25,74 / 19,30 38,61 / 25,74x / 38,61
31,24
/
23,43x
/ 31,24x / 46,86
15,62 / 15,62
x / 28,79x / 38,39x / 57,59
x / 19,20
x / 38,53x / 51,38x / 77,07
x / 25,69
x / 52,06x / 69,42x / 104,13
x / 34,71
x / 63,97x / 85,30x / 127,95
x / 42,65
x / 85,18x / 113,58x / 170,37
x / 56,79

The exchange surface area of the water heater/cooler


VS

2R
[m2]

4R
[m2]

6R
[m2]

8R
[m2]

10

5,94

11,87

17,81

15

8,83

17,66

26,50

21

10,74

21,47

32,21

42,94

30

15,03

30,06

45,09

60,12

40

19,69

39,37

59,06

78,75

55

28,58

57,16

85,73

114,31

75

39,59

79,17

118,76

158,34

100

51,79

103,58

155,37

207,15

120

62,90

125,80

188,71

251,61

150

78,05

156,11

234,16

312,21

180

94,73

189,46

284,19

378,93

230

116,43

232,86

349,29

465,72

300

155,82

311,64

467,46

623,28

400

210,53

421,05

631,58

842,10

500

258,69

517,37

776,06

1034,74

650

344,45

688,90

1033,35

1377,80

t 1 [C] - air temperature before the cooler


t 2, t 3 [C] - air temperature behind cooler

Cooling capacity
Cooling capacity for cooling air flow V [m 3/h] from the temperature
at point 1 to the temperature at point 2 (x=const) or to the temperature
at point 3 (x= var)
Dry cooling (alteration 1-2)
Q = V/3600 p (h1-h2) [kW]; x1=x2, w=0
V [m 3/h] - air flow capacity, h1 [kJ/kg] enthalpy of air flow before the cooler
h 2, h 3 [kJ/kg] enthalpy of air flow after the cooler
p [kg/m 3] air density (1,2 kg/m 3 for 20C)t 2<t1 x2=x1
Wet cooling (alteration 1-3)
Q = V/3600 p (h1-h3) [kW]
W = V/3600 p (x1-x3) [kg/s]
V [m 3/h] - air flow capacity, W [kg/s] - amount of condensed moisture
x 1 [kg/kg] amount of moisture before the cooler, x 2, x 3 [kg/kg] amount
of moisture after the cooler, h 1 [kJ/kg] enthalpy of air before the cooler
h 2, h 3 [kJ/kg] enthalpy of air behind the cooler, p [kg/m 3] air density
t3<t1 x3<x1(1,2 kg/m 3 dla 20C)

The exchange surface area of the DX cooler


VS

2R
[m2]

3R
[m2]

4R
[m2]

6R
[m2]

10
15

5,94

8,91

11,87

17,81

8,83

13,25

17,66

26,50

21

10,84

16,27

21,69

32,53

30

15,18

22,77

30,36

45,54

40

19,89

29,83

39,77

59,66

55

28,87

43,30

57,73

86,60

75

39,98

59,98

79,97

119,95

100

52,31

78,46

104,62

156,93

120

63,53

95,30

127,07

190,60

150

78,84

118,26

157,67

236,51

180

95,68

143,52

191,37

287,05

230

117,60

176,40

235,20

352,80

300

157,38

236,08

314,77

472,15

400

212,64

318,96

425,28

637,92

1.

<600

60

500

261,28

391,93

522,57

783,85

2.

600-1000

100

650

347,91

521,87

695,82

1043,73

3.

1000-1400

140

4.

1400-1800

180

5.

1800-2200

200

6.

2200-2600

240

VS

Full Fan
pressure [Pa]

Working
height
H[mm]

1 section / 2 section 1 section or 2 section water cooler


(capacity 50/50%).
Compliance with standards: EN 305, EN 1216, EN 13053.

61

Energy recovery
Regeneration

Function and application

Construction

Non- hydroscopic and hydroscopic rotary exchanger


Indirect energy recovery (sensible heat) accumulated in
the exhaust air ow and its transfer to the counter current
supply air ow.
Indirect recovery of latent heat (moisture) when the rotor
surface temperature on the side of the exhaust air is lower
than the supply air dew-point temperature.
Energy recovery without total separation of the supply and
exhaust air ows (air leakages of 2 5%).
Application in block supply-exhaust AHUs.
Type: AIR - AIR

the rotor which is 200mm thick, is installed on a shaft with


bearing and built in a steel construction frame
rotor lling: a spiral built of two alternating layers of at and
corrugated aluminium sheets 0.07mm thick creating ducts
of hydraulic diameter D=1.6mm
variable rotary speed drive system enabling max. exchanger
efciency and regulation of energy recovery level
purge sector reducing the penetration of dirty exhaust air
into the supply air to the minimum
brush seals placed on the rotors perimeter and the dividing
line providing additional protection against air leakages

brush seals placed on the rotors perimeter and the


dividing line providing additional protection against air
leakages

vertical system: VS 21650

Recuperation

Function and application

Construction

Cross-ow exchanger
Indirect energy recovery (sensible heat) accumulated
in the stream of exhaust air and its transfer to the
ventilation air supplied to the rooms.
Heat recovery at very high separation of the streams of
supplied and exhaust air (99.9%).
Application in block supply-exhaust AHUs.
Type: AIR - AIR

a system of crosswise formed 0.120.2mm thick


aluminium plates, between which separated streams of
supply and exhaust air ow in an alternating crosswise
pattern
internal by-pass duct (VS-21650) with installed air
damper which allows to divert air ow outside the
exchanger window:
- disabling energy recovery function
- function of the exchangers anti-freeze protection
drop eliminator with a drain pan

horizontal system: VS 1015


vertical system: VS 21650

Glycol system, Run-around coil


Indirect energy recovery (sensible heat) with a total
(100%) separation of supply and exhaust air ows.
System applied when there is a necessity to separate
(even at signicant distances) supply from exhaust
AHUs.

Type: AIR
INTEMEDIARY
LIQUID - AIR

VS 21650

62

system of two exchangers placed in the exhaust air ow,


which takes over the heat (cooler) and transfers it through
an intermediate agent (water and glycol solution) to an
exchanger, mounted in the supply air ow (heater)
construction of exchangers included in the recovery
system is similar to the construction of water VTS
exchangers
number of rows R: 8

Glycol installation system with a circulating pump and


control system is not included in VTS offer.
The connectors are placed on the access side of the
AHU.
Exchanger is connected to the liquid supply by
means of the top or bottom connector depending
on the access side of the AHU in order to enable
countercurrent air ow with reference to liquid ow
in the exchanger universal exchanger right/left type.
Connecting the exchanger to the liquid supply in a
paralell ow fashion system results in reduction of the
cooling by up to 20%.

Operation parameters

Teaching aids

efciency up to 85% (depends on the temperature differences


between the air streams, moisture and ratio of air ows) exchanger
class A acc. EN 13053
exchanger tightness for nominal operation parameters: 97%
max. permissible air ow speed: 5,2m/s
rotor rotational speed: 10rpm
life of bearings:
L10= 50000h / L50=250000h (<VS-120)
L10= 25000h / L50=125000h (> VS-120)
recommended max. pressure drop: 450Pa
ambient temperature: -3070C

Total heat recovery efciency


(sensible and latent heat)
(h2-h1)
c = (h3-h1)

(t2-t1)
(t3-t1)

t =

Enthalpy and temperature of the supply air:


h 1 [kJ/kg], t 1 [ oC] before the exchanger
h 2 [kJ/kg], t 2 [ oC] behind the exchanger

Cooperation between the exchanger and the fan unit

Basic conguration

Heat recovery sensible efciency


(sensible heat)

Exhaust air enthalpy and temperature:


h 3 [kJ/kg], t 3 [ oC] before the exchanger
h 4 [kJ/kg], t 4 [ oC] behind the exchanger

Supply air

Conguration for a unit


cooperating with an internal
mixing box

V2

V1

t 2:x 2

3
x3

t 1:x 1

V3

V4

t 3:x 3

t 4:x 4

x
4 x4

Exhaust air

t2>t1
x2>x1

Compliance with standards: EN 308, EN 13053.

x2

t4<t3
x4<x3

1
x1

Operation parameters

efciency up to 75% (depends on the temperature differences


between the air streams, moisture and ratio of air streams) exchanger
class B acc. EN 13053
V1
exchanger tightness for nominal operation parameters: 99.9%
t 1:x 1
max. permissible air ow speed: 3.8m/s
recommended max. pressure drop: 450Pa
max. difference between air ow pressures of supply and exhaust air:
1500Pa
ambient temperature: -4080C
V3
t 3:x

Supply air

V4
t 4:x 4

V2
t 2:x 2

t2

Exhaust air

efciency up to 55% - exchanger class C acc. EN 13053


max. permissible air ow speed:
heater: v=3,8m/s
cooler: v=2,8m/s
max. operation pressure of the agent: 1.6MPa=16 bar (tested 21 bar)
min. agent temperature depends on the glycol concentration
glycol content: max. 50%
pressure drop on the exchangers/agent ow available in technical
specication (CCOL)

x4
4
1
x1

Exhaust air

V4
t 4:x

V3

t2

t 1:x

t3

t 3:x 3

V1
Compliance with standards: EN 779, EN 13053.

tR

t4<t3
x4=x3

x3

2
x2

t4

Compliance with standards: EN 308, EN 13053.


t2>t1
x2=x1

t3

x3

2
x2

V2
t 2:x 2

tR
t4

Supply air

t2>t1
x2=x1

1
x1

x4
4

t4<t3
x4<x3

63

Fan units
Function and application

Construction

PLUG fan unit with a direct drive


Low and medium pressure ventilation and air
conditioning systems, with total pressures of up to
2000 Pa.
Single-draw centrifugal fan without casing with
impellers blades curved backwards.
VS 10 equipped with the fan set and a motor with the
following parameters n= 2790 rpm, P=0,55 kW.
SWSI type

VS 15 equipped with the fan set and a motor with the


following parameters n=2850 rpm, P=0,75 kW.

the fan and motor unit is placed on a common frame


isolated from the AHU structure by rubber vibration
isolators
drive type: direct the fan impeller is installed on the
motor shaft
TEFC type motors (Totally Enclosed Fan Cooled)
one speed motors complying with the IEC standard
frequency converter (a standard element of the fan
unit)
Impeller made of SAN (styrene/acrylonitryle) construction material with 20% glass ber.

VS 21VS 150 equipped with fan sets (direct driven).


VS 180VS 300 equipped with double fan sets (direct
driven).
VS 400VS 500 equipped with triple fan sets (direct
driven).
VS 650 equipped with fourfold fan sets (direct driven).

Optional VS 10 low pressure fan, 230 VAC


Low and medium pressure and air conditioning
systems with total pressures up to 450 Pa
VS 10

Centrifugal fan with double-sided suction with the


impellers blades curved forwards

Integrated fan and motor unit is placed on a common


drive shaft
A unit isolated from the AHU structure by rubber
vibration insulators
Drive type: direct
TEFC type motors (Totally Enclosed Fan Cooled)
Three speed motors complying with the IEC standard

DWDI type

Optional VS 15 low pressure fan set, 230 VAC


Low and medium pressure and air conditioning
systems with total pressures up to 450 Pa
VS 15

DWDI type

64

Centrifugal fan with double-sided suction with the


impellers blades curved forwards

Integrated fan and motor unit is placed on a common


drive shaft
A unit isolated from the AHU structure by rubber
vibration insulators
Drive type: direct
TEFC type motors (Totally Enclosed Fan Cooled)
Three-speed motors complying with the IEC standard

Operation parameters

Teaching aids
AHU outlet congurations - PLUG centrifugal fan

voltage rating: 3x400V AC


motor rpm.: 1440 rpm, 2860 rpm
protection type: PTC
motor winding insulation class F: life (co-operation with exchanger)
life-span of bearings: L10= 20000h / L50 = 100000h
level of protection: IP55
ambient temperature: 60C
Technical specication of frequency converters: p. 74.
Protection: operation of the fan unit may be monitored by a
pressure differential switch (optional element).
Compliance with standards: EN 1886, EN 25136, ISO 5801, AMCA
standard 210.

VS

hxw
[mm]

h 1 x w1
[mm]

10

220x500

15

250x660

21

313x821

250x660

30

440x821

380x613

40

440x1028

440x821

55

575x1199

440x1028

75

695x1340

575x1199

100

795x1520

695x1340

120

832x1751

795x1520

150

933x1945

795x1520

180

1137x1945

795x1520

230

1137x2353

740x1913

300

1436x2445

933x1945

400

1669x2945

933x2650

500

1669x3445

1199x3150

650

2146x3557

1520x3250

VS 1015

VS 21650

SFP common indicator of the ventilation system capacity


SFP (Specific Fan Power) indicates the relation of electrical energy consumption
to the amount of supplied and/or exhaust air through mechanical ventilation unit
within a given time limit. It is the only parameter which reflects characteristics of air
flow in an AHU as well as the one in the whole network with one value only.

rated voltage: 1x230V AC (In=2,4A)


motor rpm.: 1600rpm
nom. motor power: P=0,25 kW
life-span of bearings: L10 = 20000h / L50 =100000h
level of protection: IP20
ambient temperature: 40C

SFP =

Psupply el. + Pexhaust el.

[kW/m3/s] or [W/m3/h]

Vmax
For calculations in the case of supply-exhaust AHUs a greater value of air flow
capacity for supply or exhaust air should be assumed.
The analyses of ventilation systems energetic capacity indicate that values between
1.8 and 2.3 m/s are optimum linear air flow speeds in a ventilation unit cross
section.

Optional VS 10 low pressure fan performance


p [Pa]

700

Change of fans capacity in


relation to change of rotary
speed

600

500

400

V2
V1

300

n2
n1

200

rated voltage: 2x230V AC (In=2,4)


rated motor rotation: 1600rpm
rated motor power: P=2x0,25kW
protection type: TK
motor winding insulation class: F
bearing life: L10 = 20000h / L50 =100000h
protection class: IP20
ambient temperature: 40C

100

Change of fans accumulation


in relation to change of rotary
speed

0
500

1000

1500

2000

Optional VS 15 low pressure fan performance


P2

p [Pa]

P1

800

()
n2
n1

700

Demand for fan power in


relation to change of rotary
speed

600

500

400

P2

300

P1

()
n2
n1

200

100

0
0

500

1000

1500

2000

2500

3000

65

Mixing box, Silencer


Recirculation

Function and application

Construction

Mixing box
Direct energy recovery (sensible heat, latent heat) as
a result of mixing two streams of air the external air
with a part of the exhaust air.
AHU operation in fast heating mode for units
equipped with an internal mixing box.

M type

mixing box is equipped with an appropriate


doublesystem of inlets/outlets armed with air throttles
regulating the proportional share of the external air to
the exhaust one (the recirculation air)
congurations of inlets/outlets:

In case of high concentration of toxic substances


in a room using the recirculation function is
forbidden.
The recirculation function constitutes an optional
element of a units equipment.

VS 21650

Dimensions of inlets/outlets: p. 53 or the bookmark.

Air damper

Silencing

Function and application

Construction

Silencers
Reduction of the level of acoustic power and in
consequence acoustic pressure (noise) from the
draw and discharge side of the ventilation or air
conditioning AHU, generated by the fan unit.

SLCR type

Silencing function constitutes an optional element


of a units equipment.

140 mm thick silencing elements (plates) internal lling is


made of sound absorbing and incombustible mineral wool
of 60 and 80 kg/m3 density, respectively
plates casing: plastic frame
the outer surface of the elements is covered with a thin
unwoven fabric (veil), which prevents mineral wool
particles from getting into the supply air ow
number of plates per silencer: 2-13 (depending on the size
of a specic AHU)

NC curve distribution (Noise criteria)

Level of
acoustic
pressure
[dB]

Audibility
treshold

Frequency in octave bands [Hz]

66

Operation parameters

Teaching aids

efciency up to 90% - exchanger class A acc. EN 13053


operation temperature: -40 +70C

exhaust air

Compliance with standards: EN 13053.

V4

V3

t 4:x 4

t 3:x

x2

Mixing box inlet and outlet dimensions

VS
21
30

inlet (outlet) top (bottom) face


h2xw2
220x500

Side inlet (outlet)

W1

H1

L1

h3xw3

L1

H1

228

112

200

213x380

165

115

165

131

165

131

165

149

165

209

165

159

165

177

165

178

228

178

200

40

250x660

252

163

200

55

440x821

257

135

200

75

440x1028

224

195

200

228

200

125

344

196

125

280

137

200

100
120
150
180
230
300

575x1199
795x1520
933x1945

280

239

200

272

200

125

318

319

125

400

933x2650

215

436

125

500

933x3150

215

436

125

650

933x3250

220

674

125

313x380
413x380
613x380
713x740
913x740
1213x740
1513x740
1913x740

165

180

165

180

165

179

165

146

165

146

165

184

V1

V2

t 1:x 1

t 2:x

supply air

V1
V2

V1
V

2M
1M
2M
12

h2 - hM
==
hM - h1
V2
V

x1

x2 - xM
xM - x1
=

1M
12

t [ oC] - air temperature


w [kg/kg] - amount of moisture in the air
h [kJ/kg] - enthalpy of air
V [m 3/h] - air flow

Level of acoustic power


The acoustic power level, which is an objective value describing the source of noise
in acoustic terms, is used for acoustic calculations (it is neither dependent of the
distance of the sound source nor the room type).

Level of acoustic pressure

Operation parameters

The measure of acoustic pressure of sound in relation to reference pressure


amounting to
po = 2105 Pa (audibility threshold):

maximum air velocity: v=5m/s


operation conditions: -40 +70C

Lp = 20 log (p/po) [dB]

Compliance with standards: EN ISO 7235:2005.

Acoustic pressure as a value perceived by human ear depends on the sound source
and room type. Therefore the gures provided in technical specications of
equipment describe only an approximate value of the level of acoustic pressure.

Silencing values for VENTUS AHU silencers

Two and more sound sources

VS

125Hz 250Hz

500Hz 1000Hz 2000Hz 4000Hz 8000Hz Lw[dB]

10

6,3

9,4

15,7

18,8

20,1

20,4

20,0

26,4

15

6,8

10,2

17,0

20,4

21,7

22,0

21,5

28,0

21

10,6

16,0

26,7

32,0

34,1

34,7

33,9

40,0

30

8,7

13,0

21,7

26,1

27,8

28,2

27,6

33,9

40

10,0

15,0

24,9

30,0

32,0

32,5

31,8

37,9

55

9,4

14,1

23,5

28,1

30,0

30,4

29,9

36,0

75

9,0

13,5

22,4

26,9

28,7

29,1

28,6

34,7

100

8,9

13,4

22,3

26,8

28,6

29,1

28,5

34,7

120

9,5

14,3

23,8

28,6

30,5

31,0

30,3

36,5

150

9,5

14,2

23,7

28,5

30,3

30,8

30,2

36,3

180

8,4

12,6

21,0

25,2

26,9

27,3

26,8

33,0

230

9,5

14,2

23,7

28,4

30,3

30,8

30,1

36,3

300

11,4

17,1

28,3

34,0

36,3

36,9

36,0

42,2

400

11,7

17,4

29,0

34,9

37,2

37,8

36,9

43,0

500

12,8

19,3

32,1

38,5

41,1

41,7

40,9

46,9

650

11,2

16,8

28,0

33,6

35,8

36,4

35,7

41,7

Summation of noise level from identical


sound sources:
Ls = L+10 lg n [dB(A)]

level increase
[dB]

Level difference

Where n number of sources


L s - total sound level
L - sound level of individual sources

n
Level difference

For two sources (n=2) with identical acoustic power the sound level rises
by 3 dB(A) at n=10 increase by 10 dB(A). For summation of two sources with
different sound levels, the level of the louder source must be increased according
to the chart depending on the level difference between the two sources. For more
sound sources all sound sources should be totaled one by one.
The letter A added to the acoustic pressure level unit [dB(A)] - shows
that the indicated noise level takes into account the reaction of human
middle ear to sounds of different frequencies. It is known that low
frequencies of the same acoustic pressure are more tolerable to humans
than high frequencies, which is shown by the A curve.

67

Optional elements
Function and application

Construction

Air damper
Cutting off the air ow through AHU.

Plastic blades (ABS) protected with rubber seals on the


edges
aluminum frame
driven by plastic gears istalled inside aluminium
framework of the damper
damper is equipped with a square pin adjusted for
cooperation with an actuator (dampers with hydraulic
diameters greater than 4m2 have two pins coupled with
a connector

Control of air ow through AHU.


Control of air mixing rate in the supply and exhaust
AHU system.
Protection of cross-ow exchanger - by-pass type air
damper.
A.DAMP
type

Assembly:
- outside AHUs casing;
- mixing box: inside AHUs casing.

Flexible connection
Protection of the ventilation system (ducts) against
transmission of vibrations from the ventilation or air
conditioning AHU.

Flange: PVC-C material with UV stabilizer. Surrounding


temperature: -30oC to +97oC.
Fire resistance: UL 94HB [ISO 1210]
Elastic material: polyester fabric covered with PVC.
Surrounding temperature -30oC to +70oC
Operation position: span 110 mm
PE are equipped with ground load in order to equalize
potentials

Compensation of axial symmetry of ventilation ducts in


relation to the AHUs axis.
FLX.CNC
type

Optional:
Galvanized steel collar - thickness 1 mm, width
30 mm

Air intake, Air terminal


Protection of the ventilation or air conditioning AHU
against the effects of outdoor factors (water, sand) for
outdoor systems.

Air intake: made from aluminum, air intake handlebars


made from ABS
Air terminal: made from aluminum, air terminal handlebars made from ABS

Each of these components can operate as an


independent option.

VS 21650

Lighting
INT.LGHT
type

AHU inspection and maintenance.

casing
glow tube
Installation: Filtration compartment, Fan compartment.

VS 21650

air intake
air damper AD

optional function M

68

base AHU HCH

optional function E optional function F

Operation parameters

Teaching aids

leakages behind the closed blades: 50m3/h/m2 at pressure difference 0.6


of 100Pa
ambient temperature: -40 +70 C
Air flow

Air ow velocity in a populated


area

0.5

velocity
average value
[m/s]

Usually in a populated area (up to


1.8m above the oor and at 0.15m
intervals from all surfaces of the room)
at 24C the recommended velocity of
air ow is 0,15 m/s. You can
approximately determine air velocity
in the room using the chart. Use
the standards for more accurate
calculations.

lu
va e lu
va e
to
perge

0.4

av a

climatic
comfort

0.3

0.2
ttom
bo

0.1

20

21

22

23

24

25

lue
va

26

Source: EN ISO 7730, ASHRAE 55.


27

28

air temperature [C]

pressure strength of material in accordance with DIN24194


position of operation: span 110mm
ambient temperature: -40 +70 C
Type of room

Auditorium

68

Bank

23

Bar

VS
21
30
40
55
75
100
120
150
180
230
300
400
500
650

[mm]

[mm]

[mm]

128
128
128
128
128
128
128
128
128
128
128
128
128
128

881
881
1088
1259
1400
1580
1810
2002
2002
2410
2504
3003
3504
3615

373
493
493
630
730
830
893
993
1193
1193
1493
1730
1730
2193

Library

35
36

Garage

46

Cinema, theatre

46

Theatre

00

Classroom
Kitchen
Physical laboratory

lighting
ventilation duct

You need to remember that the method


of determining the amount of ventilation
air based on the replaced multiple is a
simplied method not considering the
thermal load of the room, the number of
persons or concentration of pollutants.
The values in the table based on the DIN
1946, ASHRAE standard should be treated
as approximate.

35

5 15
46

Swimming pool

34

Hotel room

48

Ofce room

38

Utility room

12

Calculation of the amount of


ventilation air depending on
the number of people
V = n Vi [m3/h]
V i - [m 3/h] amount of the outdoor air
(so called hygienic minimum) per person
n number of persons

48

Laundry

10 15

Restaurant

8 12

Server room

V p [m 3] cubic capacity of the room


n [h -1] required multiple of replacement
in the room

10 30

Warehouse

Conference room

V = n Vp [m3/h]

10 15

Department store

Retail premises

power supply voltage: 230V AC


power: 11W
protection clas: IP54
ambient temperature: 0 +70C

Calculating the amount of ventilation


air considering the required
multiple of replacement

Multiple of air
replacement [h-1]

Usually the value of Vi is assumed from 20 to


60 m3/h per person, depending on the type
of a room. In any case, the amount of air
calculated in this way is at the same time the
minimum amount of outdoor air that must be
supplied to the room.

68
5 10

Shop

68

Cloakroom

46

Mechanical workshop

36

Source: DIN 1946, ASHRAE standard.

Vi

Type of room
recommended

minimum

Theatres, movie theatres, conference


room (no smoking)

40 m3/h
per person

20 m3/h
per person

Restaurants, cafes (smoking allowed)

60 m3/h
per person

40 m3/h
per person

exible connection FC

69

Automation

70

Automation
Control elements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Control applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Supply AHUs
Heating: AS-1, AS-65 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Cooling: AS-4, AS-68 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Heating, Cooling: AS-5, AS-69 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Exhaust AHUs
Ventilation: AE-0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Supply-exhaust AHUs: cross-ow exchanger
Ventilation: AP-0 (VS 1015) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Heating: AP-1 (VS 1015) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Cooling: AP-4 (VS 1015) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Heating, Cooling: AP-5 (VS 1015) . . . . . . . . . . . . . . . . . . . . . . . . . 85
Ventilation: AP-32 (VS 21650) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Heating: AP-33 (VS 21650) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Cooling: AP-36 (VS 21650) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Heating, Cooling: AP-37 (VS 21650) . . . . . . . . . . . . . . . . . . . . . . . 87
Supply-exhaust AHUs: rotary exchanger
Ventilation: AR-0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Heating: AR-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Cooling: AR-4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Heating, Cooling: AR-5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Supply-exhaust AHUs: run-around-coli system
Ventilation: AG-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Heating: AG-257 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

Stable operation, easy control


The new VENTUS mean a totally new automatics ensuring professional
and easy control over ventilation and air conditioning system. It achieves air desired
comfort conditions most cost effectively.
An easily programmable controller interfacing with the users HMI is the heart of the
new system. It guarantees unprecedented comfort and simplicity in regulation of air
parameters. It is open to other, external control elements as well.

71

Control elements
Function and application

Construction

Duct temperature sensor


Measuring the temperature of supply, exhaust and
outdoor air.

resistance measuring element installed in an


aluminium bayonet probe 25cm long

Securing max. and min. supply air temperature.

Room temperature sensor


Measuring air temperature inside a room.

resistance measuring element installed on a


printedcircuit board

Control of lters contamination level in a unit


measuring the permissible difference of air pressures
before and behind the lter.

a membrane coupled with levers mechanism, when


an acceptable pressure difference is exceeded, the
membrane warps and disconnects electrical contact
(lters contamination signal or fan unit operation)
casing: ABS

Differential pressure switch

Control of the operation of a fan unit with a belt drive


signaling fans ram effect by means of measuring
pressures on the supply and exhaust side of the fan.
Control of fan unit operation with a direct drive in
case of a unit with electric heater.

Anti-frost thermostat on air side


Anti-frost protection of water heater: based on the
measurement of minimum acceptable temperature of air
going through a heater.
When the minimum air temperature is exceeded, the
signal transferred to the controller closes the air damper
on air inlet, turns off the fan and opens the water valve
to the max.

measuring element:
capillary with length of
2m for VS 1040
6m for VS 55650
lled with refrigerant
thermostat is equipped with adjusting screws which
enable setting the minimum operation temperature as
well as the temperature when the device switches on
again (hysteresis)
casing: plastic

The thermostat is always installed on the rst


water heater in the AHU.

Electric pre-heater control thermostat


Switching on anf off the electric pre-heater equipped
with MHE control system.
In case the air temperature behind the heater drops
below a set value a signal from the thermostat switches
the MHE control module which heats external air.

measuring element:
capillary with length of
2m for VS 1040
6m for VS 55650
lled with refrigerant
thermostat is equipped with adjusting screws which enable
setting temperature of heating and temperature of again start
of the heater (hysteresis)
casing: plastic

Over-heat protection thermostat


Over-heating protection for electric heater - switching
off the heater and automatic resume once the
temperature is lowered by the hysteresis value.
The element constitutes an optional equipment of
electric heater.

72

bimetallic element installed inside metal casing

Operation parameters

HMI BASIC EVO


DESCRIPTION

measurement: -50 +110C


measurement accuracy: 0,5K
measuring element: PT1000
output signal: resistant
length of communication wires: max. 150m
protection class: IP67
The connection between the sensor and control box is made with
shielded cable.
measurement: -20 +70C
measurement accuracy: 0,5K
measuring element: PT1000
output signal: resistant
length of communication wires: max. 150m
protection class: IP20
The connection between the sensor and control box is made with
shielded cable.

measurement: -30+500Pa (ltersclass G4F9)


rated voltage: 250V AC (Imax=3A)
output signal: voltage free (contact) NO or NZ respectively
a number of cycles: 1mln (in 60C)
protection class: IP54
ambient temperature: -20 +60C

temperature measurement: -18 +15C


anti-frost signal setpoint value: +5C (set by manufacturer)
hysteresis: 1,7 12K
rated voltage:
30 V DC
230 V AC
output signal: voltage free (dry contact)
protection class: IP 44

The thermostats capillary should be installed at the lowest


temperature zone of the liquid supplying the exchanger.

1. LCD: Shows the actual temperature in the room or the set temperature value (+/-6
C),
operation mode, fan speed, time and day.
Pictograms: sun Comfort mode; moon Economy mode; leaf recovery
active; clock calendar mode operation.
2. ON/OFF button: switching between ON and OFF (forces the AHU to stop or enables
selection of the operation mode).
3. Presence button: Forces Comfort mode (the fans start, the AHU adjusts the
temperature)
e.g. when the AHU is stopped from the calendar programme.
4. PROG button: Button for setting the basic calendar programme
5. Adjustment button : Button for adjusting the temperature setting
6. Adjustment button +: Button for adjusting the temperature setting
7. OK button: Button for conrming the entered settings
8. Fan button: Button for setting the fan speed
9. Mode button: Operation mode button selections: Auto (calendar)/ Ekono
6/Comfort
(+/- 2 C)
HMI Basic EVO functions:
Measurement and display of temperature in the room
Changing and displaying temperature setting adjustment +/- 6 C relative to the main
setting
with HMI Advanced
Changing and displaying the fans setting (max 6 steps: 7%, 33%, 50%, 67%,
83%, 100% however not lower than the minimum speed setting that is safe for the fan
assembly)
Switching the AHUs operation modes
Information about alarms (the alarm codes are available in the
technical and maintenance documentation of control units of the supply and exhaust
AHUs)
HMI Basic is active, if HMI Advanced is set to Auto operation mode while
the
Calendar is set to a mode other than Off.
Displays the temperature of the room sensor
or the adjustment value of the temperature setting
Note: The setting range is 6

temperature measurement: -18 +15C


recommended value of temperature setting (-15C)
hysteresis: 1,7 12K
rated voltage:
30 V DC
230V AC
output signal: voltage free (dry contact)
protection class: IP44

The thermostat is installed at a certain distance from the electric


heater.
overheating setpoint value: 65C
hysteresis switch off value: 22K
output signal: voltage free (dry contact)
rated voltage:
20V DC
230V AC

Icons for activating recirculation, cooling or


heating
Icons for switching the operation mode: Comfort or
Economy
Time indicator
Displays the fans speed settings or indicates that the
fan is in automatic operation mode
Day indications
Recovery activation icon
Activated presence mode icon
Alarm event icon
Stop mode icon

73

Control elements
Function and application

Construction

Carbon monoxide (CO) detector


Indoor carbon monoxide detection. Exceeding the
acceptable threshold carbon monoxide concentration
activates the outputs controlling the fans rotational
speed.

measuring element with microprocessor circuit


installed inside a high rigid casing
casing: plastic

Optional control element.

ON-OFF and 0-10V air damper actuator


ON OFF; 0
- 10V type

Air-ow open/cut off in air handling unit: ON/Off


actuator.
Mixing level control for outdoor and room-exhaust air
(recirculation): 0-10 type actuator.
Control of bypass air damper opening level for crossow exchangers anti-frost protection of exchanger
(VS 21-650): 0-10 type actuator.

mechanical system with an electric motor installed inside


plastic casing
actuator tted for installation with a square stem
1016mm or a round one 1020mm
For air handling units equipped with water heater,
the air damper actuator is additionally equipped
with a return spring - air damper is closed when no
supply voltage is present.

Electric heaters control module MHE type

MHE VS
10400
type

Powering, protecting and smooth regulation of electric power master switch disconnecting power supply of the electric
(thermal) of multi-stage electric heaters by means of PWM
heater
(Pulse Width Modulation) signal.
control module
set of connectors switching heater circuits on
set of system switches- securingwires and receivers
Power of the heater is controlled by means of alternate
connected to the system against the effects of shortcuts
switching on and off the rst stage of heating equipped
and overloads
with semi-conductive relays. Subsequent stages of heating
are activated with the help of connectors the moment the
rst stage reaches its maximum power. After a subsequent
Steering module is integrated with electric heater
stage has been activated power of the rst one drops tothe
- no possibility of module complectation as an
minimum.
independent elements of automatics

Three-way valve with electric actuator


Temperature control of liquid owing through
the water exchanger (heater). Qualitative control:
maintaining the constant ow of the liquid supplied to
the exchanger, upon its temperature change.
Control of mass liquid ow supplied to the exchanger
retaining constant temperature cooler (placing the
valve on the installation carrying the liquid away from
the exchanger).
In order to minimize the risk of liquid freezing in the
exchanger (heater), integration between the valve and
a circulating pump is recommended.

Actuator:
mechanical system with an electric motor installed inside
plastic casing enabling smooth regulation of valve opening
Valve:
Body: brass
Ball: stainless steel

Connection type - SCR:


DN15 for kvs=2,5; 4,0
DN20 for kvs=6,3
DN25 for kvs=10; 16
DN32 for kvs=25
DN40 for kvs=40
DN50 for kvs=63
DN80 for kvs=100

Frequency converter
Smooth control of the air ow by proportional change
of rotational speed of the motor fan unit.
Maintaining xed AHUs operation parameters at
variable ductworks ow resistances.
The converter is tted only for VS 10 650, AHUs
equipped with direct drive fan sets.

74

electronic circuit which enables changing voltage


frequency powering motor and maintaining optimum
U/f characteristics
the circuit is installed inside a plastic casing
fan enabling internal cooling of the unit
control panel enabling entering the frequency
converters parameters

Operation parameters

HMI ADVANCED EVO


DESCRIPTION

supply voltage: 230V AC


output signal: 12V DC / max 0.1A voltage free (dry contact)
power consumption: 5W
protection class: IP 40
ambient temperature: -10 +40C

2
control type:
- two-point
- open/closed 0-100%
supply voltage: 24 V AC/DC
input signal:
ON/OFF
0 - 10 V DC
torque: 16 Nm
rotation angle: 90

opening duration: ON/OFF:


80120s (spring 10s)
0-10V: 8090s (spring 10s)
number of cycles: 60 000
max. air damper area: 4 m2
protection class: IP54
ambient temperature:
-20 +50C

control range: 10 100 Hz


supply voltage:
1- and 3- phase 200 240V AC
3- phase 380 480V AC
frequency range:
48 63 Hz
control terminals
(programmable):
- 5 binary inputs (LG SV..iC5,
Danfoss MicroDrive); 8 binary
inputs (LG SV..iG5A)
- 1 analog input 0..10V
(LG); 0/4..20mA (Danfoss

5
1. LCD: Displays the available settings and the current settings.
Key symbol in the upper left corner the password-protected maintenance access is
shown.
Top line page title.
Numbers in the upper right corner, e.g.: 5/12 indicates that the cursor is in
line 5 of 12.
If the text is longer than the maximum line length, the test is scrolled when
marked with the cursor.

control range: 0100%


supply voltage: 3*400V/50Hz
control voltage: 24V AC
input signal:
digital 3x 24V DC
output signal:
digital 6x 24V DC
PWM 1x 24V DC
ambient temperature: 050C

Actuator
control range: 0 - 100%
supply voltage: 24V AC/DC
input signal: 0-10V DC
rated torque:
8Nm for kvs=2,563
rated pressure load:
1800N for kvs=100
rotation angle: 90
protection class: IP54
ambient temperature:
-20 +50C

2. Turning button (knob): Main navigation and control tool.


- Turn to search the menu
- Push to open the menu, select and change the settings.
If a setting is highlighted by the cursor, it can be edited.
If a setting is not highlighted, it can only be read.
The symbol indicates that you can switch to the next screen. Push the
knob to switch.

Valve
operation characteristics: percentage constant/proportional
range kvs: 2,5 / 4,0 / 6,3 / 10 / 16
/ 25 / 40 / 63 / 100
pressure drop:
- max = 200 kPa kvs 25
- max = 240 kPa kvs > 25
average temperature:
kvs= 2,510: up to 120C
kvs= 16100: up to 140C
glycol percentage in medium:
50%
ambient temperature:
-20 +50C

3. INFO button (information & LED): Switch to the start screen.


LED off Modes: Off/ Overrun/Fire mode
LED lit:
- green solid Modes: Comfort/Economy
- green blinking Modes: Start-up/Night time cooling/Standby mode
- orange Modes: Alarm/Emergency shutdown/Conguration mode
4. CHIME button: Switch to the alarms screen
The button is lit red if an alarm requires conrmation.
5. ESC button:
Short press Go to the previous page or leave the setting change
Long press Exit to the HMI Advanced EVO maintenance menu
Exit to the controllers selection list when working with Process Bus.

MicroDrive)
- 1 relay output with
changeover contact changeover
- 1 binary output transistor (LG
SV..iC5, LG SV..iG5A)
- 1 analog output 0/4..20mA
(Danfoss Micro-Drive)
serial communication:
Modbus RTU RS485
motor connection: 3-phase
ambient temperature: 0 40C
protection class: IP20
forced cooling by built fan

Above parameters constitute general description of Frequency


Converters being offered.
Type and model of FC used in air handling unit each time should
be conrmed with VTS Technical and Commercial adviser.
Frequency converters conform with EMC Directive 89/336/EEC
(RFI lters for the secondary environment are not required).

75

Control elements
Function and application

Construction

HMI BASIC users room interface


Control of the air temperature in a room.
Controlling and reading of basic parameters
of ventilation and air conditioning unit:
- air parameters;
- efciency change;
- change mode;
- breakdown states.

electronic circuit with a resistance measuring element


installed inside plastic casing
LCD screen
control panel

Optional element of automatics system.

HMI ADVANCED users external interface


Displays ventilation and read out of a ventilation and
air handling units operation parameters:
Managing operation of one or more AHUs from any
location in a building by means of serial
communication with a controller (controllers).
Managing operation of one or more AHUs from any
location in a building by means of communication.

electronic circuit installed inside plastic casing


Easy to read LCD text model, 8 lines
x 20 characters
Innovative knob Push & Roll for the rapid
navigation and parameter changing
Communication cable (standard 3m) expandable to 1200

Optional element of automatics system.

VS supply and supply-exhaust air AHU control box


Regulation, control, protection of ventilation or air
conditioning units operation parameters operation,
temperature, air efciency, breakdown states.
Scheduled operation of a unit (in accordance with
calendar) with a possibility of division into time zones.

set of elements protecting motors operation


driver
main disconnector
Polycarbonate (PC) casing, dimensions:
450mm x 460 mm x 170 mm

Control of units operation from any location in a


building with the help of external communication
elements HMI BASIC EVO or HMI ADVANCED EVO
users interface.
Cooperation with external circuits in the eld of:
- START signal;
- re alarm;
- START/STOP system.

VS exhaust AHU control box


Regulation, control, protection of ventilation units
operation parameters operation, breakdown states.
Cooperation with external circuits in the eld of:
- START signal;
- re alarm;
- START/STOP system;
- CO detector.

76

set of elements protecting motors operation


main disconnector
steering and control panel with a rotational speed
controller
Polycarbonate (PC) casing, dimensions:
340x460x170mm

Operation parameters

HMI ADVANCED

supply voltage: 1215VDC


Temperature measurement
measurement: 0 40C
measurement accuracy: +-0,5K
measuring element: NTC
output signal: communication line Process Bus
length of communication cable: max. 350m
protection class: IP30
operation conditions: 0 50C / <85%

Supply voltage: 24V DC


Communication port 1: serial port, standard RS485, up to 1200 m 1:1
connection
Communication port 2: Process Buss, based on KNX TP1 up to 350 m
(between I points) and up to 1000 m (entire network) - 1: n connection
protection class: IP31
operation conditions: -20 60C / <85%

- Air temperature reading at all measurement points of the AHU (e.g. supply,
exhaust,
external, in the room and behind the recovery system);
- changing efciency (two gears St1 / St2 for fast selection each with freely
adjustable
speed);
- changing the method for adjusting temperature in Komf (comfort mode, more
accurate)/
Eko (the economy mode allows for greater variations to the set value);
- operation calendar settings (base weekly calendar + special settings for holidays
etc. +
conguring out-of-service periods, e.g. in the holiday season);
- switching
the AHUs
operation
mode
Off / Auto
/ Eko
St1 / Eko
St2802.3U)
/ Komf St1 / Komf
Network
interface
TCP/IP
(optional)
in 10/100
MBit
standard
(IEEE
St2;
supporting three functionalities:
-Web-HMI
fault status.
Advanced emulation accessible through a web browser;
connection to BMS as Modbus TCP/IP Server via port 502
connection of the Scope programme via port 4242 (max 3 Clients
simultaneously)

supply voltage: 3x400V or 1x230V AC


frequency: 50Hz + 1Hz
control voltage: 24V AC
Driver
external communication
Serial port
- standard: RS-485
- protocol: Modbus RTU local communication with frequency
inverters
- protocol: Siemens
communication 1:1 HMI Advanced EVO
Port Process Bus based on KNX TP1 - connection 1:1 HMI Basic
TCP/IP network interface (optional)

A single HMI Advanced EVO can work with several controllers in the network via
the
the PB (Process Bus) socket instead of the standard connection via T-HI. HMI Basic
EVO
cannot be used because they use the same PB port.

No.1

HMI Advanced

ACX36 EVO
ACX36 EVO WEB

CE CE+

CE CE+

MAX. 350m

No.1

No.2

No.3 (MAX.5)

ACX36 EVO
ACX36 EVO WEB

ACX36 EVO
ACX36 EVO WEB

ACX36 EVO
ACX36 EVO WEB

CE CE+

supply voltage: 3x400V or 1x230V AC


frequency: 50Hz + 1Hz
control voltage: 24V AC
protection class: IP54
ambient temperature: 0 50C

CE CE+

MAX. 350m

HMI Advanced

CE CE+

MAX. 350m

CE CE+

MAX. 350m

MAX. 1000m

77

AS - Applications for supply units


Applications intended for VS 21-650 equipped
with frequency converters

Applications intended for VS 10-15 AHUs

Functions available in particular applications


Application
code

78

HW

HE

CW

DX

CWHW

PRC.
BPS

MIX. SUM. PHT.


CMBRERHW

Functions available in particular applications


FAST.
HTG

Application
code

AS

AS

AS

AS

AS

AS

AS

AS

AS

AS

AS

AS

AS

AS

AS

10

AS

10

AS

16

AS

16

AS

65

AS

65

AS

66

AS

66

AS

68

AS

68

AS

69

AS

69

AS

70

AS

70

AS

72

AS

72

AS

73

AS

73

AS

74

AS

74

AS

80

AS

80

AS

193

AS

193

AS

194

AS

194

AS

196

AS

196

AS

197

AS

197

AS

198

AS

198

AS

200

AS

200

AS

201

AS

201

AS

202

AS

202

AS

208

AS

208

AS

257

AS

258

AS

261

AS

262

AS

265

AS

266

HW

HE

CW

DX

CWHW

PRC.
BPS

MIX. SUM. PHT.


CMBRERHW

Designation of automatics applications:

Designations:

AS - automatics application for supply AHUs,


AD - automatics application for supply and exhaust AHUs,
AG - automatics application for supply and exhaust AHUs
with glycol recovery,
AP - automatics application for supply and exhaust AHUs
with a cross-ow recuperator,
AR - automatics application for supply and exhaust AHUs
with a rotary regenerator,
AE - automatics application for exhaust AHUs (not working
with supply AHUs)

HW - water heater,
HE - electric heater,
CW - water cooler,
DX - direct agent evaporation cooler
CW/HW- alternating operation of the water exchanger
(heating/cooling),
PRC.BPS- bypass operation of the cross-ow exchanger,
MIX.CMBR - mixing chamber
SUMM.ER - cold recovery,
PHT.HW- water pre-heater (preheating),
FAST.HTG - fast heating function

FAST.
HTG

Control applications
Supply AHUs

Control
Indoor temperature control (HMI BASIC EVO), optional for supply/exhaust
air.
Control of the energy recovery level rst stage of heating/cooling.
Air ow control.
Operation according to calendar temperature, efciency, operation mode
(OPERATION, STAND-BY, STOP).
STAND-BY maintaining the minimum, set indoor temperature.
* Initial heating of external air.

Information
Information on outdoor, supply, exhaust and indoor air temperatures.
Filter contamination info.
Alarm status info.
Analog and digital input and output status info.

Protection
Limiting the allowed supply air temperature.
Fan unit protection the function is active:
- if an electric heater is applied.
Overload protection of a drive unit.
Anti-frost protection of a water heater.
Protection against overheating of an electric heater.

The control application layouts have been prepared on the basis of water
exchangers.
The quantity of applied pressure switches for lters depends on the lters
conguration (p. 57).

79

Control applications
Supply AHUs

Control
Indoor temperature control (HMI BASIC EVO), optional for supply/exhaust
air.
Control of the energy recovery level rst stage of heating/cooling.
Air ow control.
Operation according to calendar temperature, efciency, operation mode
(OPERATION, STAND-BY, STOP).
STAND-BY maintaining the minimum, set indoor temperature.
* Initial heating of external air.

Information
Information on outdoor, supply, exhaust and indoor air temperatures.
Filter contamination info.
Alarm status info.
Analog and digital input and output status info.

80

Protection
Limiting the allowed supply air temperature.
Fan unit protection the function is active:
- if an electric heater is applied.
Overload protection of a drive unit.
Anti-frost protection of a water heater.
Protection against overheating of an electric heater.

The control application layouts have been prepared on the basis of water
exchangers.
The quantity of applied pressure switches for lters depends on the lters
conguration (p. 57).

Control applications
Supply AHUs

Control
Indoor temperature control (HMI BASIC EVO), optional for supply/exhaust
air.
Control of the energy recovery level rst stage of heating/cooling.
Air ow control.
Operation according to calendar temperature, efciency, operation mode
(OPERATION, STAND-BY, STOP).
STAND-BY maintaining the minimum, set indoor temperature.
* Initial heating of external air.

Information
Information on outdoor, supply, exhaust and indoor air temperatures.
Filter contamination info.
Alarm status info.
Analog and digital input and output status info.

Protection
Limiting the allowed supply air temperature.
Fan unit protection the function is active:
- if an electric heater is applied.
Overload protection of a drive unit.
Anti-frost protection of a water heater.
Protection against overheating of an electric heater.

The control application layouts have been prepared on the basis of water
exchangers.
The quantity of applied pressure switches for lters depends on the lters
conguration (p. 57).

81

Control applications
Exhaust AHUs

Control
Air ow control.
Air ow control depending on CO condensation ratio.

Protection
Fan unit protection the function is active:
- for the fan unit with belt drive;
Overload protection of a drive unit.

Information
Information on outdoor, supply, exhaust and indoor air temperatures.
Filter contamination info.
Alarm status info.
Analog and digital input and output status info.

82

The quantity of applied pressure switches for lters depends on the lters
conguration (p. 57).

AP - Applications for supply exhaust AHUs with plate-crossow energy recovery


system
Applications intended for VS 21-650 equipped
with frequency converters
Functions available in particular applications
Application
code

HW

HE

CW

DX

CWHW

PRC.
BPS

MIX. SUM. PHT.


CMBRERHW

Functions available in particular applications


FAST.
HTG

Application
code

AP

32

AP

544

AP

33

AP

545

AP

34

AP

546

AP

36

AP

548

AP

37

AP

549

AP

38

AP

550

AP

40

AP

552

AP

41

AP

553

AP

42

AP

554

AP

48

AP

560

AP

160

AP

672

AP

161

AP

673

AP

162

AP

674

AP

164

AP

676

AP

165

AP

677

AP

166

AP

678

AP

168

AP

680

AP

169

AP

681

AP

170

AP

682

AP

176

AP

688

AP

288

AP

800

AP

289

AP

801

AP

290

AP

802

AP

292

AP

804

AP

296

AP

808

AP

416

AP

928

AP

417

AP

929

AP

418

AP

930

AP

420

AP

932

AP

424

AP

936

HW

HE

CW

DX

CWHW

PRC.
BPS

MIX. SUM. PHT.


CMBRERHW

FAST.
HTG

Applications intended for VS 10-15 AHUs


Functions available in particular applications
Application
code

HW

HE

CW

DX

CWHW

PRC.
BPS

MIX. SUM. PHT.


CMBRERHW

Functions available in particular applications


FAST.
HTG

Application
code

AP

AP

128

AP

AP

129

AP

AP

130

AP

AP

132

AP

AP

133

AP

AP

134

AP

AP

136

AP

AP

137

AP

10

AP

138

AP

16

AP

144

HW

HE

CW

DX

CWHW

PRC.
BPS

MIX. SUM. PHT.


CMBRERHW

FAST.
HTG

83

Control applications
Supply-exhaust AHUs: cross-ow exchanger

Control
Indoor temperature control (HMI BASIC EVO), optional for supply/exhaust
air.
Control of the energy recovery level rst stage of heating/cooling.
Air ow control.
Operation according to calendar temperature, efciency, operation mode
(OPERATION, STAND-BY, STOP).
STAND-BY maintaining the minimum, set indoor temperature.
* Initial heating of external air.

Information
Information on outdoor, supply, exhaust and indoor air temperatures.
Filter contamination info.
Alarm status info.
Analog and digital input and output status info.

84

Protection
Limiting the allowed supply air temperature.
Fan unit protection the function is active:
- if an electric heater is applied.
Overload protection of a drive unit.
Anti-frost protection of a water heater.
Protection against overheating of an electric heater.
Anti-frost protection of an energy recovery exchanger.

The control application layouts have been prepared on the basis of water
exchangers.
The quantity of applied pressure switches for lters depends on the lters
conguration (p. 57).

Control applications
Supply-exhaust AHUs: cross-ow exchanger

Control
Indoor temperature control (HMI BASIC EVO), optional for supply/exhaust
air.
Control of the energy recovery level rst stage of heating/cooling.
Air ow control.
Operation according to calendar temperature, efciency, operation mode
(OPERATION, STAND-BY, STOP).
STAND-BY maintaining the minimum, set indoor temperature.
* Initial heating of external air.

Information
Information on outdoor, supply, exhaust and indoor air temperatures.
Filter contamination info.
Alarm status info.
Analog and digital input and output status info.

Protection
Limiting the allowed supply air temperature.
Fan unit protection the function is active:
- if an electric heater is applied.
Overload protection of a drive unit.
Anti-frost protection of a water heater.
Protection against overheating of an electric heater.
Anti-frost protection of an energy recovery exchanger.

The control application layouts have been prepared on the basis of water
exchangers.
The quantity of applied pressure switches for lters depends on the lters
conguration (p. 57).

85

Control applications
Supply-exhaust AHUs: cross-ow exchanger

Control
Indoor temperature control (HMI BASIC EVO), optional for supply/exhaust
air.
Control of the energy recovery level rst stage of heating/cooling.
Air ow control.
Operation according to calendar temperature, efciency, operation mode
(OPERATION, STAND-BY, STOP).
STAND-BY maintaining the minimum, set indoor temperature.
* Initial heating of external air.

Information
Information on outdoor, supply, exhaust and indoor air temperatures.
Filter contamination info.
Alarm status info.
Analog and digital input and output status info.

86

Protection
Limiting the allowed supply air temperature.
Fan unit protection the function is active:
- if an electric heater is applied.
Overload protection of drive unit.
Anti-frost protection of a water heater.
Protection against overheating of an electric heater.
Anti-frost protection of an energy recovery exchanger.

The control application layouts have been prepared on the basis of water
exchangers.
The quantity of applied pressure switches for lters depends on the lters
conguration (p. 57).

Control applications
Supply-exhaust AHUs: cross-ow exchanger

Control
Indoor temperature control (HMI BASIC EVO), optional for supply/exhaust
air.
Control of the energy recovery level rst stage of heating/cooling.
Air ow control.
Operation according to calendar temperature, efciency, operation mode
(OPERATION, STAND-BY, STOP).
STAND-BY maintaining the minimum, set indoor temperature.
* Initial heating of external air.

Information
Information on outdoor, supply, exhaust and indoor air temperatures.
Filter contamination info.
Alarm status info.
Analog and digital input and output status info.

Protection
Limiting the allowed supply air temperature.
Fan unit protection the function is active:
- if an electric heater is applied.
Overload protection of a drive unit.
Anti-frost protection of a water heater.
Protection against overheating of an electric heater.
Anti-frost protection of an energy recovery exchanger.

The control application layouts have been prepared on the basis of water
exchangers.
The quantity of applied pressure switches for lters depends on the lters
conguration (p. 57).

87

AR - Applications for supply exhaust AHUs with rotary


regenerator energy recovery system
Applications intended for VS 21-650 equipped
with frequency converters
Functions available in particular applications
Application
code

88

HW

HE

CW

DX

CWHW

PRC.
BPS

MIX. SUM. PHT.


CMBRERHW

Functions available in particular applications


FAST.
HTG

Application
code

AR

AR

512

AR

AR

513

AR

AR

514

AR

AR

516

AR

AR

517

AR

AR

518

AR

AR

520

AR

AR

521

AR

10

AR

522

AR

16

AR

528

AR

128

AR

640

AR

129

AR

641

AR

130

AR

642

AR

132

AR

644

AR

133

AR

645

AR

134

AR

646

AR

136

AR

648

AR

137

AR

649

AR

138

AR

650

AR

144

AR

656

AR

256

AR

768

AR

257

AR

769

AR

258

AR

770

AR

260

AR

772

AR

261

AR

773

AR

262

AR

774

AR

264

AR

776

AR

265

AR

777

AR

266

AR

778

AR

384

AR

896

AR

385

AR

897

AR

386

AR

898

AR

388

AR

900

AR

389

AR

901

AR

390

AR

902

AR

392

AR

904

AR

393

AR

905

AR

394

AR

906

HW

HE

CW

DX

CWHW

PRC.
BPS

MIX. SUM. PHT.


CMBRERHW

FAST.
HTG

Control applications
Supply-exhaust AHUs: rotary exchanger

Control
Indoor temperature control (HMI BASIC EVO), optional for supply/exhaust
air.
Control of the energy recovery level rst stage of heating/cooling.
Air ow control.
Operation according to calendar temperature, efciency, operation mode
(OPERATION, STAND-BY, STOP).
STAND-BY maintaining the minimum, set indoor temperature.
* Initial heating of external air.

Information
Information on outdoor, supply, exhaust and indoor air temperatures.
Filter contamination info.
Alarm status info.
Analog and digital input and output status info.

Protection
Limiting the allowed supply air temperature.
Fan unit protection the function is active:
- if an electric heater is applied.
Overload protection of drive unit.
Anti-frost protection of a water heater.
Protection against overheating of an electric heater.
Anti-frost protection of an energy recovery exchanger.

The control application layouts have been prepared on the basis of water
exchangers.
The quantity of applied pressure switches for lters depends on the lters
conguration (p. 57).

89

Control applications
Supply-exhaust AHUs: rotary exchanger

Control
Indoor temperature control (HMI BASIC EVO), optional for supply/exhaust
air.
Control of the energy recovery level rst stage of heating/cooling.
Air ow control.
Operation according to calendar temperature, efciency, operation mode
(OPERATION, STAND-BY, STOP).
STAND-BY maintaining the minimum, set indoor temperature.
* Initial heating of external air.

Information
Information on outdoor, supply, exhaust and indoor air temperatures.
Filter contamination info.
Alarm status info.
Analog and digital input and output status info.

90

Protection
Limiting the allowed supply air temperature.
Fan unit protection the function is active:
- if an electric heater is applied.
Overload protection of a drive unit.
Anti-frost protection of a water heater.
Protection against overheating of an electric heater.
Anti-frost protection of an energy recovery exchanger.

The control application layouts have been prepared on the basis of water
exchangers.
The quantity of applied pressure switches for lters depends on the lters
conguration (p. 57).

Control applications
Supply-Exhaust AHUs: Glycol System (Run-around coil)
AG - 1
2S1H**

2M1

E7
2Y1

2Y1
B2*

1S2H**

Y1

1S1H

2Y1
T

S2F

N2/N3
1M1

2Y1

B1

B1
T

B2*

S3F

1M2

*
Y1
T

S4F

AG - 257
2S1H**

2M1
E7
B4

2Y1
1S2H**

Y7

1S1H

T
B6

S2F

N2/N3
1M1

1Y1

B3

B2*

B1
T

S6F

E6

B2*

S3F

1M2

*
Y6
T

Y1

S4F

Control
Indoor temperature control (HMI BASIC EVO), optional for supply/exhaust
air.
Control of the energy recovery level rst stage of heating/cooling.
Air ow control.
Operation according to calendar temperature, efciency, operation mode
(OPERATION, STAND-BY, STOP).
STAND-BY maintaining the minimum, set indoor temperature.
* Initial heating of external air.

Information
Information on outdoor, supply, exhaust and indoor air temperatures.
Filter contamination info.
Alarm status info.
Analog and digital input and output status info.

Protection
Limiting the allowed supply air temperature.
Fan unit protection the function is active:
- if an electric heater is applied.
Overload protection of a drive unit.
Anti-frost protection of a water heater.
Protection against overheating of an electric heater.
Anti-frost protection of an energy recovery exchanger.

The control application layouts have been prepared on the basis of water
exchangers.
The quantity of applied pressure switches for lters depends on the lters
conguration (p. 57).

91

Psychrometric chart

air
temperature

92

Potrebbero piacerti anche