Sei sulla pagina 1di 80

Technical Description FBP FieldBusPlug

V6

tion
e nta 3 Universal Motor Controller
cum ion UMC22-FBP
Do Vers

2CDC 34 2 011 F0003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Universal Motor Controller


for high-grade motor protection and control, current range 0.24 to 63 A,
with 6 digital inputs and 3 digital outputs, to connect to fieldbuses via FieldBusPlug

2CDC 342 012 F0003


Fig. 1: Universal Motor Controller UMC22-FBP

Contents Page

Features ....................................................................................................................................................... 5

Device construction ................................................................................................................................... 6


Overview ................................................................................................................................................ 6
Terminals, monitoring LEDs and operating elements on the front plate .............................................. 7

Planning and commissioning ................................................................................................................... 8


Guide to an operating installation (Overview) ....................................................................................... 8
Wiring and internal 24 V / 0 V connections ........................................................................................... 9
Interfacing with contactors ................................................................................................................... 10
Motor current = Set current versus wiring ........................................................................................... 12
External current transformer for higher currents ................................................................................. 13
Interfacing to the fieldbus, addressing ................................................................................................ 14
Configuring the bus master and binding in the UMC22-FBP as slave ............................................... 16
Parameterization of the UMC22-FBP, proceeding .............................................................................. 18
Switch on / off motor, local control ...................................................................................................... 19
Info available on LEDs ......................................................................................................................... 20
Info available on the Control Panel ..................................................................................................... 21

FieldBusPlug / Issue: 10.2003 UMC22-FBP 3


Universal Motor Controller
UMC22-FBP
Technical Description V6

Maintenance .............................................................................................................................................. 23
Replacement of an UMC22-FBP in an operating installation ............................................................. 23
Replacement of the controller unit only ............................................................................................... 23

Data overview ............................................................................................................................................ 24


Device inputs and outputs ................................................................................................................... 24
Monitored signals / Commands ........................................................................................................... 25
Diagnosis ............................................................................................................................................. 27
Parameters, Overview ......................................................................................................................... 28
Parameters, Description ...................................................................................................................... 29

Technical data ........................................................................................................................................... 32


Main power lines .................................................................................................................................. 32
Control unit ........................................................................................................................................... 33
Digital inputs ........................................................................................................................................ 33
Digital outputs ...................................................................................................................................... 33
FieldBusPlug connection ..................................................................................................................... 34
Environment and mechanical data ...................................................................................................... 34
Ordering data ....................................................................................................................................... 35
Dimensions .......................................................................................................................................... 36

Appendix A: Control Functions


Transparent ......................................................................................................................................... A-2
Overload relay ..................................................................................................................................... A-4
Direct starter ....................................................................................................................................... A-8
Reversing starter .............................................................................................................................. A-13
Star-delta starter 1 ............................................................................................................................ A-19
Pole-changing starter 1 ....................................................................................................................A-25

Appendix B: Control Panel


Overview ............................................................................................................................................. B-2
Menu ................................................................................................................................................... B-3

4 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Features

Overview
- The Universal Motor Controller UMC22-FBP provides high-grade motor protection and control for the
current range 0.24 up to 63 A with one type.
For higher currents additional protection current transformers (class 5P10) can be used.
- With the integrated FieldBusPlug interface the UMC22-FBP can be connected to different fieldbuses
using the appropriate type of FieldBusPlug.
- 6 digital inputs and 3 relay outputs offer to realize a wide range of predefined control functions and
applications such as direct starter and star-delta starter including local operation via digital inputs
and others as selected by parameters.
- Depending on the parameterization, the status of the digital inputs and outputs, the actual current,
detailed diagnosis information and all parameters are accessible via the fieldbus (supposed the
fieldbus offers the appropiate features).
- LEDs on the UMC22-FBP monitor 'Ready', 'Motor On' or 'Fault'.
- Additional Control Panel ACS100-PAN (separate delivery) offers similar access to all important
information. The Control Panel is necessary to set the fieldbus slave address and can be snapped in
on the front of the UMC22-FBP.
- Also, the overload protection behaviour and other functions can be changed by parameters in a wide
range. More details see chapters "Data overview, Parameters ...".
- The control function Overload relay is dedicated to use the UMC22-FBP similar to an overload relay
with and without fieldbus connection. The other control functions can be used stand-alone, too.

Construction
- The UMC22-FBP consists of two separate parts: Current transformer set and controller unit,
mounted as one device.
- Mounting on DIN rail or with screws. W x H x D = 70 x 105 x 110 mm. Degree of protection IP20.
- Current-carrying motor lines are lead through the current transformer set.
- Replacement of the controller unit without removing the current-carrying motor lines.
- Parameters are stored in the current transformer set even if power down happens. This allows to
replace the controller unit without reparameterization.

Overload protection
- Measuring the motor current (value is also provided to be sent to the fieldbus)
- Electronic overload protection for nominal currents of 0.24 A to 63 A (whole range with onIy one type
of device). Set currents selectable with parameter via fieldbus or Control Panel.
- Trip classes 5, 10, 20 and 30 (selectable with parameter)
- Phase-loss protection
- Short circuit protection of the motor lines by external fuses on the line side.

Other features
- With parameter it can be selected between 'Relays off' or 'Relays retain status' in case of control
system or fieldbus failure.
- Diagnostic information available via LEDs, fieldbus and Control Panel.
- Preventive diagnosis functions (e.g. number of starts)
- Function blocks or similar software tools to be implemented into the program of the control system

FieldBusPlug / Issue: 10.2003 UMC22-FBP 5


Universal Motor Controller
UMC22-FBP
Technical Description V6

Device construction

Overview

UMC22-FBP:
current transformer set

UMC22-FBP:
controller unit

label

Control Panel
ACS100-PAN:
(optional)

complete
device

4
FieldBusPlug
2CDC 342 013 F0003

Fig. 2: UMC22-FBP: Device construction

6 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Device construction (continued)


Terminals, monitoring LEDs and operating elements on the front plate

current path (for measuring the motor current)

mounting by 4 screws M4

connecting terminals for the digital outputs


pawl to snap on the Control Panel
switch for selecting the internal electronics supply voltage:
left position: external supply (via terminals 10/11)
1 2 3 4 5 6 7 8 9
right position: supply via FieldBusPlug
UMC22
SWITCH

READY plug connection for the Control Panel


MOT.ON
LEDs:
FAULT
green READY (ready for operation)
INT. 5 6 7 8 9 yellow MOT. ON (motor on)
EXT.
DO DO DO DO DO red FAULT (overload, failure)
C C 0 1 2

connector for the FieldBusPlug


EXT. DIN rail
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18 front label, e.g. for slave address

Control Panel holder. Insert the Control Panel at this


holder and then snap it into the pawl on the upper side.
The electrical contacts are automatically connected.

connecting terminals for the digital inputs


connecting terminals for the external supply voltage
(supply for internal electronics)

current path (for measuring the motor current)

Snap-mountable Control Panel ACS100-PAN for


monitoring and control / adjust:
– slave address
– control function
– overload parameters
– local diagnosis
MENU
– etc.
LOC REM The Control Panel ACS100-PAN is not shipped together
with the UMC22-FBP. It must be ordered separately.
2CDC 342 014 F0003

ENTER

Fig. 3: UMC22-FBP: Terminals, indicators and operating elements

FieldBusPlug / Issue: 10.2003 UMC22-FBP 7


Universal Motor Controller
UMC22-FBP
Technical Description V6

Planning and commissioning


Guide to an operating installation (Overview)

Wiring and internal 24 V / 0 V connections


Hard-wire with switch apparatus and other components referring to the application requirements,
see Appendix A "Control functions", example "Direct starter".
Use external supply (SWITCH to EXT), if components are distant to the UMC22-FBP.

Interfacing with contactors


Use spark suppression, for larger contactors also interface relays to keep good lifetime of the
UMC22-FBP internal relays.

Motor Current = Set current versus wiring


Have a look at the wiring of the motor to define the correct set current for complete motor
protection.

External current transformer for higher currents


Connect external current transformers for higher currents.

Connection to the fieldbus, addressing


Use the appropriate FieldBusPlug.
Change slave address.
The bus master is normally defined by the control system.

Configuring the bus master and binding in the UMC22-FBP as slave


Load slave configuration file into the programming tool.
Example: ABB_078F.GSD for UMC22-FBP as PROFIBUS DP slave.
Create fieldbus configuration together with the application program in the control system.
For some control systems dedicated function blocks or example programs are available.

Parameterization of the UMC22-FBP, proceeding


As default the control function selected in the UMC22-FBP is transparent: The inputs and outputs
are directly controlled by the fieldbus telegram.
To control and protect a motor optimal a motor control function e.g. Direct starter must be
selected. After parameterization and power-on the motor can be started.
Details see chapter "Data overview, Parameters ...".
The parameterization tool depends on the fieldbus type and the control system.
Examples:
- The slave configuration file (e.g. GSD file for PROFIBUS DP) contains the parameterization
medias. The parameters can be changed during configuration of the fieldbus and are loaded
into the UMC22-FBP during power-on.
- Parameterization as a part of the application program.
- Parameterization with the Control Panel. Details see Appendix B "Control Panel“.
As a special feature the Control Panel allows the user to read the complete parameter set of an
UMC22-FBP and to transfer it to another UMC22-FBP, see Appendix B "Control Panel“.

Start Motor with RUN command. See also:


Switch on / off motor, local control
Info available on LEDs , Info available on the Control Panel

bold: sub clause in this chapter

8 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Planning and commissioning (continued)


Wiring and internal 24 V / 0 V connections
Example: Direct starter

With the parameter 'Control function' = 3 ('Direct starter') Free outputs, commands
the relay output DO0 is used to control the main contactor direct from fieldbus

230 V N DO1 DO2 690 / 400 V

K1
K1

5 6 7 8 9
DO DO DO DO DO
C C 0 1 2
UMC22
EXT

INT

0V
FieldBus SWITCH
24 V
Plug

max.
70 mA

0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18

K1
2CDC 342 060 F0003

24 V 24 V
0V 0V

Fig. 4: UMC22-FBP: 0V 24V 24V DI1 DI2 DI3 DI4 DI5


Direct starter (example) if EXT to supply
supply inputs

With the parameter 'Check-back' = 1 ('Auxiliary Free outputs, monitoring


contacts') the digital input DI0 is used to survey signals directly to the fieldbus
the contactor (default: 2 ('Motor current'))

Important:
Normally the inputs and the internal electronic circuits are supplied locally via the terminals 10 and 11. In
this case the SWITCH must be set to EXT. The connection of distant contacts or sensors requests
urgently this kind of supply.
If only contacts nest to the UMC22-FBP are used - that means the 24 V wiring can be surveyed easily -
the supply via the fieldbus and the FieldBusPlug is possible (SWITCH to INT).

FieldBusPlug / Issue: 10.2003 UMC22-FBP 9


Universal Motor Controller
UMC22-FBP
Technical Description V6

Planning andcCommissioning (continued)


Interfacing of contactors
(For info about contactors refer to the actual main catalogue)

Spark suppression
Spark suppression is always necessary to avoid early failure of the relay contacts.

Contactor type connected to the UMC22-FBP Type B6, B7 A9 to A40


Appropriate suppressor for 230 V AC VDR RV-BC 6/250 RV 5/250
Appropriate suppressor for 24 V AC / DC VDR RV-BC 6/60 RV 5/50

230 V N 690 / 400 V AC

Contactor type: A45 and larger


K1
K1
K2
Spark suppression K2

5 6 7 8 9
DO DO DO DO DO
C C 0 1 2
UMC22
EXT
INT

0V
SWITCH
24 V

max.
70 mA

0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18

K1

0 V 24 V 24 V
if EXT supply output
2CDC 342 061 F0003

For check-back the auxiliary contact of the main contactor has to be used!

Fig. 5: UMC22-FBP: Connecting contactors with peak current > 0.5 A: Types A45 and larger

10 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Planning and commissioning (continued)


Overview of available ABB contactors (examples)
Contactor type Inrush current [A] Holding current [A] Inrush power [VA] Holding power [VA]
BC6-30-10-2.4 0.015 0.015 3.5 3.5
A9, A12, A16 0.30 0.03 70 8
A26, A30, A40 0.52 0.05 120 12
A45, A50, A63, A75 0.78 0.08 120 12
A95, A110 1.52 0.10 180 18
A145, A185 2.39 0.15 550 35
A210, A260, A300 5.87 0.26 1350 60
The contactor BC6-30-10-2.4 is recommended as interface contactor due to internal spark suppression.
Contactors A145 to A300 also with electronic interface available (AF145 etc.), larger contactors only with
electronic interface.

Lifetime UMC22-FBP mechanical 500 000 switching cycles


relays (see chapter 0.50 100 000 switiching cycles
"Technical data") 1.00 50 000 swiching cycles

+ 24 V DC - 230 V AC 690 / 400 V AC

Remark:
Slide switch on the left
side to position "PLC" (up)

1 K1
ON
2 OFF-N
3 COM

5 6 7 8 9
DO DO DO DO DO
C C 0 1 2

UMC22
2CDC 342 062 F0003

Fig. 6: UMC22-FBP: Connecting larger contactors with electronic interface (AF 145 and larger)

FieldBusPlug / Issue: 10.2003 UMC22-FBP 11


Universal Motor Controller
UMC22-FBP
Technical Description V6

Planning and commissioning (continued)


Motor current = Set current versus wiring

Star Delta 1 Delta冑 3


Power line: Power line: Power line:
690 V 400 V 400 V
IP IP IP

UMC 22 UMC 22 UMC 22

ISC=IP ISC=IP ISC=0.577*IP

U1 V1 W1 U1 V1 W1 U1 V1 W1

W2 U2 V2 W2 U2 V2 W2 U2 V2

Example for motor: Example for motor: Example for motor:

Motor rating plate Motor rating plate Motor rating plate


400 V / 690 V 400 V / 690 V 400 V / 690 V
4.9 A / 2.8 A 4.9 A / 2.8 A 4.9 A / 2.8 A
IP=2.8A / I SC=2.8A IP=4.9A / I SC=4.9A IP=4.9A / I SC=2.8 A

Parameter Parameter Parameter


'Set current' = 2.80 'Set current' = 4.90 'Set current' = 2.80

Terminal box Terminal box Terminal box

U1 V1 W1 U1 V1 W1 U1 V1 W1

W2 U2 V2 W2 U2 V2 W2 U2 V2
2CDC 342 063 F0003

Fig. 7: UMC22-FBP: Motor current = Set current versus wiring

The Delta 冑 3 circuitry is normally used for larger motors to reduce the current transformer size. The
parameter 'Set current' is the nominal motor current devided by 冑 3.

12 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Planning and commissioning (continued)


External current transformer for higher currents
All types of protection current transformers class 5P10 referring the Standard EN 60044 can be used.
The selection should be made based on the requirements:
- secondary current range (= current in the UMC22-FBP) about 5 A (recommended current
transformers have 4A)
- through-hole area if single cores are used,
- accuracy in the measuring range (50 - 150%) should be class 1, because the inaccuracy is added to
the inaccuracy of the UMC22-FBP,
- max. burden 60 m⏲ (UMC22-FBP: 30 m⏲ , conductor 2x2 m 2.5 mm2: 30 m⏲)
The pass through sense of the strands does not affect the operation.
For the current range up to 850 A space saving combinations are recommended.

2CDC 342 064 F0003


max. length 2 x 2 m, cross section 2.5 mm2

Fig. 8: UMC22-FBP: External current transformer for higher currents

Type / Current range Recom- Second. Hole Cables Link kit (bar) type*
Star, mended current area (E/EN  for contactor
Delta 1 range range WxH 60204) (order code see
[A] [A] [A] [mm] [mm2] "Technical data")
UMC22-FBP without 0.24 ... 63 0.24 ... 63 - 11 쏗 max. 252 -
current transformer **
KORC 4L185 46 ... 185 60 ... 185 1.3 ... 4 22 x 28 1 x 702 DT450 / A185
 AF145 - AF185
KORC 4L310 80 ... 310 180 ... 310 2.3 ... 4 22 x 28 2 x 702 DT450 / A300
 AF260 - AF300
KORC 5L500 125 ... 500 300 ... 500 2.4 ... 4 41 x 22 3 x 702 DT500 / AF460S*
 AF400 - AF460
KORC 5L850 213 ... 850 500 ... 850 2.4 ... 4 41 x 22 - DT500 / AF750S*
 AF580 - AF750
* Link kits for Star-delta starter. (Others see catalogue.)
** max. cable diameter with insulation 11 mm

Accuracy class: actual / nominal current 5% 20 % 100 % 120 % 500 %


accuracy class 3 1.5 1 1 5

Remark:
For Delta 冑 3 circuitry - normally used for larger motors - the parameter 'Set current' is the nominal motor
current devided by 冑 3, see preceeding chapter.

FieldBusPlug / Issue: 10.2003 UMC22-FBP 13


Universal Motor Controller
UMC22-FBP
Technical Description V6

Planning and commissioning (continued)


Interfacing to the fieldbus, addressing
The normal requirement is that the slave address corresponds with the motor. That means: The slave
address shall be adjusted and saved in the connected UMC22-FBP. This is possible for all fieldbuses
except the AS-Interface fieldbus (actual integrated AS-Interface circuits do not allow).
To adjust the address the Control Panel can be used. Immediately when mounted or when the
combination is switched on, the address is monitored. Details see Appendix B "Control Panel".

The UMC22-FBP does not contain a valid address.


(A000 is a valid address but could be reserved de-
CPU coupler, pending on the type of the fieldbus). The status
bus master "no valid address" can be restored setting A999.
The slave does not start on the bus without a
valid address.

2CDC 342 015 F0003

Fig. 9: UMC22-FBP: Adressing

An other way to adjust the address in the FieldBusPlug is to use the "Addressing Set" CAS21-FBP.0
(Interface unit + PC with addressing SW). See technical description 2CDC 190 012 D02--.

14 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Planning and commissioning (continued)


Interfacing to the fieldbus, addressing (continued)
When switching on the combination UMC22-FBP  FieldBusPlug, both or one or none of them can
contain a fieldbus address.
The behaviour in these cases depends on the parameter 'Address check', see chapter "Data overview,
Parameters, Description".
'Address check' = 'Off' (= 0) (default):
1. Neither the UMC22-FBP nor the FieldBusPlug contains a valid address:
- The UMC22-FBP does not start to operate and to communicate.

2. Only the UMC22-FBP contains a valid address:


- The FieldBusPlug gets the address and saves it. Operation and communication starts.

3. Only the FieldBusPlug contains a valid address:


- The UMC22-FBP gets the address and saves it. Operation and communication starts.

4. The UMC22-FBP and the FieldBusPlug contain the same address:


- Operation and communication starts.

5. The UMC22-FBP and the FieldBusPlug contain different addresses:


- The FieldBusPlug stores the address received from the UMC22-FBP. Operation and
communication starts.
'Address check' = 'On' (= 1). Mainly used for draw-out design.
This parameter can only be set via bus master and fieldbus.
1. Neither the UMC22-FBP nor the FieldBusPlug contains a valid address:
- The UMC22-FBP does not start to operate and to communicate.

2. Only the UMC22-FBP contains a valid address:


- The FieldBusPlug gets the address and saves it. Operation and communication starts.

3. Only the FieldBusPlug contains a valid address:


- The UMC22-FBP gets the address and saves it. Operation and communication starts.

4. The UMC22-FBP and the FieldBusPlug contain the same address:


- Operation and communication starts.

5. The UMC22-FBP and the FieldBusPlug contain different addresses:


- Neither the operation nor the communication starts.
- The Control Panel displays alternating (3 seconds each):

Address of UMC22-FBP:
Address of the FieldBusPlug:
- Communication fault (F003) is set.
- With the Control Panel the menu 2.3 'Change address' has to be selected and the desired
address must be adjusted. Details see Appendix B "Control Panel".
- After leaving this menu operation and communication starts immediately. Both the FieldBusPlug
and the UMC22-FBP store the adjusted address.

Remark: If the adjusted FieldBusPlug address is not configured in the fieldbus master the
communication does not start and the red LED on the FieldBusPlug displays fault.

FieldBusPlug / Issue: 10.2003 UMC22-FBP 15


Universal Motor Controller
UMC22-FBP
Technical Description V6

Planning and commissioning (continued)


Configuring the bus master and binding in the UMC22-FBP as slave
The control systems, programming tools and the fieldbus types are totally different.
This means: There is no common rule to configure the fieldbus master and to bind in
FieldBusPlug slaves into the application program.

Example
UMC22-FBP connected to an ABB CPU type 07 KT 97 via PROFIBUS DP

Preparation of the programming tool 907AC1131:


Before starting the programming tool 907AC1131 the file - ABB_078F.GSD must be copied into the
programming SW subdirectory, normally into: ...\AC1131\Library\PLCConf.
The appropriate ABB_078F.GSD has the version 1.3 (2003-11-09):

2CDC 342 088 F0003


Configuration of the bus master:
- Start programming SW 9 07AC1131
- Select <Resources> in the main menu (left side, below, R....)
- Change <Card number> and - under Bus parameters - <Baudrate> if desired.
- Set - under Standard parameters <Automatic addressing> = on
- Now the bus master is defined:
2CDC 342 082 F0003

Hardware-Configuration
R.....
07 KT 97-DPM (DP-Master)
place pointer, click right mouse key twice

Binding in the slave:


- <Append DP-Slave>: <ABB FBP 2003-03-13 (Default)>
2CDC 342 083 F0003

Hardware-Configuration

07 KT 97-DPM [DP-Master]
ABB FBP 2003-03-13 [DP-Slave]

place pointer, click right mouse key twice


- Select <Properties>, <UMC22>, <SELECT> to transfer into the column right
- Select <Properties>, table <Standard Parameters> to change station (=slave) address
- Select <Properties>, table <Inputs/Outputs>,<UMC22>, <SELECT> to transfer into the column right

16 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Planning and commissioning (continued)


Configuring the bus master and binding in the UMC22-FBP as slave (continued)
I/O addresses are allocated automatically if <Automatic addressing> is selected during bus master
configuration: Allocation of the I/Os based of the slave address follow the rule:

(S-2) x 2

coupler slot 1 x2

S=6 Input %IW1.8 %IB1.16 %IX1..8.0 ...1.8.7 RUN REVERSE*


Slave to PLC %IB1.17 %IX1..8.8 ...1.8.15 not used*
address (Monitorings) %IW1.9 %IB1.19 %IX1..9.0 ...1.9.7 motor current, high byte
%IB1.20 %IX1..9.8 ...1.9.15 motor current, low byte
Output %QW1.8 %QB1.16 %QX1.8.0 ...1.8.7 RUN REVERSE*
from PLC %QB1.17 %QX1.8.8 ...1.8.15 not used*
(Commands) %QW1.9 %QB1.19 %QX1.9.0 ...1.9.7 not used*
%QB1.20 %QX1.9.8 ...1.9.15 not used*
*
only lowest bit shown

Parameterization of the UMC22-FBP, proceeding


Some parameters define the application circuit diagram, others are used for current setting and overload
features etc. This requests and means: The UMC22-FBP starts operation only after receiving valid
parameters. Details see chapter "Data overview, Parameters, Description".
The possibility to write and to read parameters depends definitely on the fieldbus and the control system.
Examples:

The transfer of parameters


between the control station
and the automation station

PROFIBUS DP (/V0)
LAN
Write parameters with
GSD file during power-on.
Read not possible. Configuration file:
CPU coupler ABB_078F.GSD
--> Master Class 1

PROFIBUS DP/V1
fieldbus Write and read parameters
whenever desired.
--> Master Class 2

DeviceNet:
Write and read parameters
whenever desired. Configuration file:
ABB_UMC22-FBP-ESD
2CDC 342 065 F0003

(EDS = Electronic Data Sheet)

Fig. 10: UMC22-FBP: Write and read parameters

FieldBusPlug / Issue: 10.2003 UMC22-FBP 17


Universal Motor Controller
UMC22-FBP
Technical Description V6

Planning and commissioning (continued)


Parameterization of the UMC22-FBP, proceeding (continued)
 Additional: The parameterization can be done with the Control Panel. Details see Appendix B
"Control Panel".
 Special feature of the Control Panel: It can be used to read the complete parameter set of a
parametrized UMC22-FBP and to transfer it to another UMC22-FBP, see Appendix B "Control
Panel".

Example continued
Configuring the UMC22-FBP as slave connected to the 07 KT 97 via PROFIBUS DP
- Select <Properties> on table <Input/Output> when UMC22-FBP is present in the column right
Now the parameters can be changed (left then right mouse key).

2CDC 342 089 F0003


The procedure, however, can be more or less different for other control systems and fieldbuses .

18 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Planning and commissioning (continued)


Switch on / off motor, local control

Motor control:

via control system


CPU

via Control Panel

via digital inputs

2CDC 342 066 F0003


Fig. 11: UMC22-FBP: Motor control

In an operating installation, the motor contactors are switched On and Off normally by the control system
with the commands RUN FORWARD, RUN REVERSE and OFF.
Switching On (Run) and Off is possible when the UMC22-FBP is parameterized with one of the motor
controlling Control functions e.g. 'Direct starter, 'Star-delta starter' etc. The exceptions are 'Transparent'
and 'Overload relay'. Switching On (Run) and Off can be done:
via control system  via Control Panel  via digital inputs

FieldBusPlug / Issue: 10.2003 UMC22-FBP 19


Universal Motor Controller
UMC22-FBP
Technical Description V6

Planning and commissioning (continued)


Switch on / off motor, local control (continued)
Table of conditions:

always possible

control system

if menu
'Local control' OFF
is activated*
Control Panel

if parameter
'Local control via
digital inputs' = 'On'
digital inputs
dominating

control system sends to the AUTO MODE = 1


UMC22-FBP the command: AUTO MODE = 0

if not blocked by AUTO MODE = 1


local control (blocked if
via Control Panel AUTO MODE = 0*)
control system
dominating RUN
FORWARD
if menu
/ REVERSE
'Local control' is
activated** (after OFF
0-1
Control Panel
dominating transition
necessary)

if parameter if not locked by AUTO MODE = 0


'Local control via local control via (blocked if
digital inputs' = 'On' Control Panel AUTO MODE = 1)*
digital inputs
alternatively:
2CDC 342 087 F0003

connection to
control station
interrupted

* AUTO MODE = 1: UMC22-FBP ignores RUN from digital inputs, monitors LOCAL CONTROL = 0,
AUTO MODE = 0: UMC22-FBP ignores RUN from control station, monitors LOCAL CONTROL = 1.
** When local control is entered the UMC22-FBP monitors LOCAL CONTROL to the control system.
local control is immediately stopped when Control Panel is removed or menu 'Local control' is left.
The status of the outputs is not changed when entering or leaving local control.

20 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Planning and commissioning (continued)


Info available on LEDs

Connection to the fieldbus:


Caused by the definitions of the
fieldbus type the meaning can
differ slightly.
green = on, red = off:
 normal data exchange
green = off, red = off:
 check power supply
one of the LEDs flashing:
 no connection to the bus- 1 2 3 4 5 6 7 8 9
ABB UMC22 green: ready for operation
master or configuration error SWITCH
or parameters not valid READY yellow: motor running
MOT.ON
FAULT (overload, check-
For more info see approriate INT
back fault, blocking
FieldBusPlug description. EXT
55 6 7 8 9
DO DO DO DO DO
C C 0 1 2
stops the motor)
Connection to the device: red: Fault (overload, other

2CDC 342 090 F0003


green = on, red = off:
EXT
0 24 24 DI DI DI DI DI DI
failure)
V V V 0 1 2 3 4 5
 normal data exchange 10 11 12 13 14 15 16 17 18

green = off, red = off: If no LED is on, check whether


 check power supply power is on and the switch
(above the FieldBusPlug
both LEDs flashing:
socket) is in the appropriate
 self test
position: EXT if supplied via
one of the LEDs flashing: terminals, INT if supplied via
 no connection to UMC22-FBP. FieldBusPlug.
For more info see approriate
FieldBusPlug description.

Info available on the Control Panel


The Control Pannel can be mounted on the front of the UMC22FBP and offers access to:
- Slave address
- Status of the motor (running, off) and status of the UMC22-FBP inputs and outputs,
- Actual current and 'Set current',
- Detailed diagnosis information,
- Service data
- All important parameters
In addition the Control Panel allows to start and stop the motor (local control)

The access is arranged in three levels:


- Monitoring: Offers only to check, not to modify values and parameters
- Edit 1: Needs password and allows to change parameters during commissioning and also
local control
- Edit 2: Accessible via Edit 1, to change parameters that are used mainly associated with the
circuitry.

FieldBusPlug / Issue: 10.2003 UMC22-FBP 21


Universal Motor Controller
UMC22-FBP
Technical Description V6

Planning and commissioning (continued)


Info available on the Control Panel
Overview of the levels

Monitoring,
S e.g..
t - address
a - I/O-signals Edit 1
r - Current e.g.
t - fault incl.. - password
acknowledge check
- ... - local control Edit 2
- address e.g.
adjust - password
- current change
- trip class - control function
- ... e.g. Y- ,
- fault input
mAVs - behaviour if
LOC
bus fails
REM kHz%
FAULT Cprm
- ...
OUTPUT PAR SET MENU FWD REV

MENU

MENU

ENTER
LOC REM

2CDC 342 091 F0003


ENTER

For details see Appendix B "Control Panel“.

Remarks:
 Most of the changed parameters are taken over after motor off.
 Some parameters are taken over during power-on.
Remark: Some control systems overwrite the parameters on principle during power-on. This can lead
to the opinion that the parameterizing via Control Panel is not effective.

22 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Maintenance
Replacement of an UMC22-FBP in an operating installation
The UMC22-FBP can be disconnected from the FieldBusPlug without disturbing the fieldbus and the
other slaves. The FieldBusPlug is supplied via the voltage conducted together with the bus lines.
The FieldBusPlug keeps stored the actual slave address and informs the control system that the
connected device is lost.
After mounting and connecting a new UMC22-FBP, the control system will be informed that the missing
slave is complete again (supposed that the new UMC22-FBP contains an invalid address A - - -).
This allows the control system to download the former parameters and to start up the new UMC22-FBP
again with correct parameters.

Replacement of the controller unit only

Replace only the controller:

 The complete wiring,


particularly the power lines, can
be left unchanged.

 The parameters remain


stored in the current
transformer unit.
The new controller reads the
parameters during power-on *.

current
transformer
unit

2CDC 342 016 F0003

controller out of order new controller

Fig. 12: UMC22-FBP: Replacing the controller unit

* In addition the parameters can be stored also in the control system and downloaded after power-on.

FieldBusPlug / Issue: 10.2003 UMC22-FBP 23


Universal Motor Controller
UMC22-FBP
Technical Description V6

Data overview
Device inputs and outputs
The function of the hardware inputs and outputs is fixed by parameterization. Refer parameters Control
function and Attached control functions.

Example (1)
Control function 'Transparent'
All Inputs and outputs are directly connected to the Fieldbus as monitoring signals and commands.

Terminal 13 14 15 16 17 18
Device DI0 DI1 DI2 DI3 DI4 DI5
Input to bus to bus to bus to bus to bus to bus
Terminal 7 8 9
Device DO0 DO1 DO2
Output from bus from bus from bus

Example (2)
Control function 'Direct starter'
One output is used to control the contactor coil. Access via fieldbus is not possible.The other inputs and
outputs are still transparent to the fieldbus

Terminal 13 14 15 16 17 18
Device DI0 DI1 DI2 DI3 DI4 DI5
Input to bus to bus to bus to bus to bus to bus
Terminal 7 8 9
Device Contactor DO1 DO2
Output coil from bus from bus

Example (3)
Control function 'Direct starter' with
Attached control function 'Local control via digital inputs'
Additional inputs are used to allow local control. Details see Appendix B "Control Functions".

Terminal 13 14 15 16 17 18
Local control Local control
Device DI0 DI1 DI2 DI3
Run Fwd. Off
Input to bus to bus to bus to bus
DI4 to bus DI5 to bus

Terminal 7 8 9
Device Contactor DO1 DO2
Output coil from bus from bus

24 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Data overview (continued)


Monitored signals / Commands
Monitored signals are sent from the UMC22-FBP to the control station,
commands are received by the UMC22-FBP from the control station.
The commands and monitored signals depend on the Control function and the Attached control
functions'.
Complete overview on all signals

Bit No. 7 6 5 4 3 2 1 0
REVERSING
Monitor LOCAL RUN RUN
WARNING FAULT LOCK-OUT - OFF
Byte 0 CONTROL FORWARD REVERSE*
TIME*
Monitor DI5 DI4 DI3 DI2 DI1 DI0
- -
Byte 1 (UMC input) (UMC input) (UMC input) (UMC input) (UMC input) (UMC input)
Monitor
MOTOR CURRENT (% of Set current)
Byte 2/3

Command FAULT AUTO RUN RUN


- - - OFF
Byte 0 RESET MODE FORWARD REVERSE
Command DO2* DO1* DO0*
- - - - -
Byte 1 (UMC output) (UMC output) (UMC output)

* used depending on the control function

Example
Control function 'Direct starter' with
Attached control function 'Local control via digital inputs'

Bit No. 7 6 5 4 3 2 1 0

Monitor LOCAL RUN


WARNING FAULT - - OFF -
Byte 0 CONTROL FORWARD

Local control Local control


Monitor DI3 DI2 DI1 DI0
OFF RUN FOR. - -
Byte 0 (UMC input) (UMC input) (UMC input) (UMC input)
DI5 to bus DI4 to bus
Monitor
MOTOR CURRENT (% of Set current)
Byte 2/3

Command FAULT AUTO RUN


- - - OFF -
Byte 0 RESET MODE FORWARD
Command DO2 DO1
*** - - - - -
Byte 1 (UMC output) (UMC output)

*** corresponding UMC22-FBP output is used to control the motor contactor coil

FieldBusPlug / Issue: 10.2003 UMC22-FBP 25


Universal Motor Controller
UMC22-FBP
Technical Description V6

Data overview (continued)


Monitored signals (description)
RUN REVERSE 1: motor running reverse AND check-back (current/contact) = 1
OFF 1: motor stopped AND no current is flowing AND no RUN command is active
0: RUN command is active OR current is still flowing after off command
RUN FORWARD 1: motor running forward AND check-back (current/contact) = 1
LOCK-OUT TIME 1: Lock-out time running. Only for reversing starter / Starts with OFF command.
The command of the opposite direction is accepted only when reversing lock-
out time is over.
LOCAL CONTROL 1: Local control is activated via Control Panel or digital inputs. RUN commands
of the control system are ignored.
0: The control system can switch on with RUN commands. Details see chapter
"Planning and commissioning, Switch on / off motor, local control".
FAULT 1: A fault condition exists: Overload, no check-back when started, etc.
See Diagnosis, Fault Bytes 0 and 1. Can be acknowledged via fieldbus
command FAULT RESET or with Control Panel.
WARNING A warning exists. See Diagnosis, Warning Byte 2
UMC input DI0...DI5 Reads UMC22-FBP digital inputs DI0 ...DI5, independent of the parameterizing
Motor current Motor current of the highest loaded phase as a % of set current

Commands (description)
RUN REVERSE 0-1 transition: Motor starts running reverse
OFF 1: Motor stops as long as this signal is 1. OFF dominates RUN commands.
RUN FORWARD 0-1 transition: Motor starts running forward or with speed 1.
Remark:
To start the opposite direction or the other speed:
OFF command is necessary, starts immediately the reverse lock-out time.When
the reverse lock-out time has elapsed, the motor can be started with the 0-1
transition of the opposite / different RUN command.
AUTO MODE 0: Enables start of the motor (RUN) via digital inputs on the UMC22-FBP,
supposed the parameter 'Local control via digital inputs' is set. UMC22-FBP
ignores RUN command from control station. Off is always possible.
Details see chapter "Planning and commissioning, Switch on / off motor, local
control".
1: Run via digital inputs is blocked. Off is always possible.
FAULT RESET 0-1-transition: Resets all resettable faults (overload fault, check-back fault, etc.)
UMC output DO0...2 Transparent control of UMC22-FBP digital output DO..., if not used by any
Control function different from Transparent.

26 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Data overview (continued)


Diagnosis

Bit No. 7 6 5 4 3 2 1 0
Fault
Fault Self-test
- input - - - - -
Byte 0 failed
signal
Commu- Parameter Current Relay 2 Relay 1 Relay 0
Fault Overload Motor
nication out of check-back check-back check-back check-back
Byte 1 (trip) fault blocked*
fault range fault* fault* fault* fault*
Motor Motor Cooling Lock-out
Warning
current high current low - time time - - -
Byte 2
threshold* threshold* running running*

Fault Parameter number


Byte 3 (refers to Byte 1, Bit 4)

* if activated by appropriate control funtion

Fault (Byte 0, Byte 1 and Byte 3), description


Fault input signal 1: Input gets fault signal from external module, e.g. thermistor module.
DI2 = 1: no external fault,
DI2 = 0 sets Internal fault signal.
See 'Attached control functions' - 'Fault input'.
Self-test failed 1: Self-test during power-on has failed.
Relay 0 check-back fault 1: no signal from auxiliary contact 1 signal within 100 ms after
switching on contactor with output DO0.
See 'Attached control functions' - 'Check-back'.

Relay 1 check-back fault 1: ditto, contactor on DO1


Relay 2 check-back fault 1: ditto, contactor on DO2
Current check-back fault 1: no motor current within 100 ms after switching on contactor
Parameter out of range 1: Received parameter exeeds high or low limit (the accompanying
parameter number is shown in Byte 3).
Communication fault 1: UMC22-FBP does not receive valid telegramms (control system,
fieldbus or FieldBusPlug is out of order or interrupted).
Remark:
Is sent to the control system after reconnection.
Motor blocked 1: Motor current over blocking current threshold.
See 'Overload protection parameter '- 'Blocking current threshold'.
Overload (trip) fault 1: Trip due to thermal protection or phase loss.
Parameter number #: Number of the parameter which exeeds the high or low limit

Warnings (Byte 2), description


Lock-out time running 1: (Reversing) Lock-out time is running.
Cooling time running 1: Cooling time is running.
Motor current high threshold 1: Motor current is above the high threshold current.
See 'Overload protection parameter' - 'High current threshold'.
Motor current low threshold 1: Motor current is below the low threshold current.
See 'Overload protection parameter' - 'Low current threshold'.

FieldBusPlug / Issue: 10.2003 UMC22-FBP 27


Universal Motor Controller
UMC22-FBP
Technical Description V6

Data overview (continued)


Parameters, Overview
The parameters are arranged into groups that apply for:

 Application circuit diagram:


- Control function:
'Transparent', 'Direct starter', 'Star-delta starter', etc.:
(Descriptions with wiring etc. referring to the particular 'Control function see Appendix A).
- Attached control functions:
'Local control via digital inputs',
'Check-Back' via: 'Motor current', 'Auxiliary contacts', 'Simulation', etc.
(see chapters "Data overview, Parameters, ..." and Appendix A and B).

 Current setting:
- 'Set current 1',
- 'Set current 2' (two-speed),

 Overload protection:
- 'Trip class' (5, 10, 20, 30)
- 'Cooling time' (seconds)
- 'Blocking current threshold', ...
- etc.

 Communication:
- 'Communication fault reaction' (reaction on loss of communication to control system)

 no parameters, but service supporting data: Other Info:


- 'Operating hours'
- 'Number of starts'
- 'Number of trips'

To load parameters into the UMC22-FBP, different ways are possible depending on the fieldbus
and the control system:
 The slave configuration file (e.g. GSD file for PROFIBUS-DP) contains the parameters. The
parameters can be changed during configuration of the fieldbus and are loaded in the UMC22-FBP
during switching on.
 The parameterization is done via application program of the control system.
 The parameterization can be done with the Control Panel. Details see Appendix B "Control Panel".
 As a special feature the Control Panel can be used to read the complete parameter set of a
parameterized UMC22-FBP and to transfer it to another UMC22-FBP, see Appendix B "Control
Panel".

Remark:
Some parameters are taken over with power-on, others during motor off.
Refer to chapters "Data overview, Parameters, Description".

28 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Data overview (continued)


Parameters,  Some changed parameters are taken over after motor off, others during power-on.
Description  Some control systems or fieldbuses overwrite the parameters during power-on of the
UMC22-FBP. In this case the Control Panel seems to be but is not ineffective.

Para. Group Parameter value Select. De- Description / remark take-over


No. Parameter No. fault after
0100 Control functions co.Fu power-on
0101 Transparent 1 1 Direct access to DIs / DOs via fieldbus
0101 Overload relay 2 Similar to overload relay
Attention: Normal signal on output DO0 is On,
connected contactor starts the motor.
0101 Direct starter 3 Direct starter with check-back
0101 Reversing starter 4 Reversing starter with check-back
0101 Star-delta starter 1 5 Star-delta starter via 2 DOs, with check-back
0101 Pole-changing starter 1 6 Pole-changing starter with check-back

0200 Attached control functions


0201 Local control L.c t r motor off
via digital Off 0 0 No control via digital inputs
inputs On 1 Digital inputs prepared to control RUN /
OFF locally
For conditions see chapter "Planning and
commissioning, Switch on / off motor, local
control".
0202 Check-back bA.ch motor off
Auxiliary contacts 1 OK when auxiliary contacts are closed
100 ms after start
Motor current 2 2 OK when current >40% of set current is
present 100 ms after start
Simulation 3 Simulated check-back (e.g. for test without
motor).
Simulation is recommended only to be set via
Control Panel. The control system must only
set Auxiliary contacts or Motor current to
guarantee for an operating check-back after
next power-on.
0203 Fault input F.i nP UMC22-BP input DI2: Closed-circuit signal. motor off
Off 0 0 Fault input is not activated
On 1 0 sets internal Fault signal ,1-signal = OK
0204 Fault output F.out motor off
Off 0 0 DO2 is not used as Fault output
On 1 Digital output DO2 used to monitor the
fault signal
0205 Reversing 0.2 - 3600 s t i.r L 2s  Only for Reversing starter! motor off
lock-out time step 0.1 s  Starts with OFF (OFF is necessarry
between FORWARD and REVERSE)
 RUN Command in other direction is not
accepted while lock-out time is running
0206 Star-delta Sd.ch  Only for Star-delta starter. motor off
changeover Time 0 Change star  delta, when star-delta
mode starting time is over
Current 1 1 Change star  delta, when motor current
울 0,9 x set current
Remark: Fault is generated if the star-delta
starting time has elapsed before switching to
delta.

FieldBusPlug / Issue: 10.2003 UMC22-FBP 29


Universal Motor Controller
UMC22-FBP
Technical Description V6

Data overview (continued)


Parameters,  Some changed parameters are taken over after motor off, others during power-on.
Description  Some control systems or fieldbuses overwrite the parameters during power-on of the
(continued) UMC22-FBP. In this case the Control Panel seems to be but is not ineffective.

Para. Group Definition / Range Select. De- UMC behaviour: description take-over
No. No. fault after
0207 Star-delta 1 - 3600 s Sd.St 60 s  Star-delta starter only! motor off
starting time step 0.1 s Starts running with the RUN command

0300 Current
Settings
0301 Set current 1 0.24...63 A Cur 1 0.5 A Important: The UMC22-FBP measures the motor off
step 10 mA currents of the lines in the bushing holes. The
current ih the coming lines can be different de-
pending on the connection circuit.
More details see chapter "Planning and Com-
missioning, Motor current = Set current
versus wiring"
0302 Set current 2 0.24 - 63 A Cur 2 0.5 A  Pole-changing and Dahlander starter only! motor off
step 10 mA Used for overload calculation

0400 Overload
Protection
0401 Trip class triP Overload calculation (thermal motor image) motor off
Trip class 5 5
Trip class 10 10 10
Trip class 20 20
Trip class 30 30
0402 Phase loss Current of one phase: < 40% of other phases motor off
protection (condition: other phases > 70% of set current)
Off 0 Phase loss protection is not activated
On 1 1 Phase loss protection is activated
0403 Cooling time 30 - 3600 s t i .co 120 s Cooling time simulates the cooling behaviour motor off
step 0.1 s of the inoperating motor after switching off.
While cooling time is running RUN is not
accepted and WARNING is monitored.
0404 Automatic ArES motor off
fault reset Off 0 0 Acknowledgment is necessary to reset Fault.
To switch on cooling time must be elapsed.
On 1 Only for overload relay!
Due to safety considerations: Automatic
reset of fault when fault condition is off and
cooling time has elapsed. Fault is not
monitored.
0405 Start-up time 0 - 600 s 120 s Suppresses some signals / trips until motor is motor off
step 0.1 s in normal running status (Blocking, High/ Low
current threshold)
0406 Blocking 0 - 800% x set current 800% Fault signal when current is above threshold motor off
current step 5% for > 1 s and start-up time has elapsed.
threshold (800% means: Blocking protection is inactive).
Remark: Blocking sets the internal fault signal
and the monitoring telegram Bit OVERLOAD
and displays FAULT on the Control Panel but
cooling time is not started.
0407 Low current 30 - 100% x set current 50% Warning when below threshold and start-up motor off
threshold step 5% time has elapsed
0408 High current 100 - 800% x set current 150% Warning when above threshold and start-up motor off
threshold step 5% time has elapsed

30 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Data overview (continued)


Parameters,  Some changed parameters are taken over after motor off, others during power-on.
Description  Some control systems or fieldbuses overwrite the parameters during power-on of the
(continued) UMC22-FBP. In this case the Control Panel seems to be but is not ineffective.

Para. Group Definition / Range Select. De- UMC behaviour: description take-over
No. No. fault after
0500 Communication
5001 Communi- bu.co All cases when UMC22-FBP does not receive motor off
cation fault valid telegrams, either when control system or
reaction fieldbus or FieldBusPlug is out of order or
interrupted.
Relays off 0 0 Relay outputs of UMC22-FBP are switched
off
Relays retain status 1 Relay outputs of UMC22-FBP retain status
0502 Address power-on
check Off 0 0 UMC22-FBP address is valid on the fieldbus
On 1 0 If the UMC22-FBP and the FieldBusPlug
contain different addresses, the user must
decide.
Details see chapter "Planning and Commis-
sioning, connection to the fieldbus,
addressing“.

0600 Other Info


0601 Operating 0 - 99.999 oP ho 0 All operating hours are counted but the unit
hours step 1 h place is not displayed on the Control Panel.
The displayd range 00.00-99.99 corresponds
with real 00.000 to 99.999.
The control system can only read the value
(depending on the type of fieldbus)! Via Control
Panel the value can be presetted e.g. to zero.
0602 Number of 0 - 1.000.000 n o St 0 All starts are counted but the three lower
starts step 1 places are not displayed on the Control Panel.
The displayed range 0000-1000 corresponds
with real 0.000.000 to 1.000.000.
The control system can only read the value
(depending on the type of fieldbus)! Via Control
Panel the value can be presetted e.g. to zero.
0603 Number of 0 - 255 notr 0 All trips are counted and shown on the Control
trips step 1 Panel in a range of 0-255.
The control system can only read the value
(depending on the type of fieldbus)! Via Control
Panel the value can be presetted e.g. to zero.

0700 other info, LOCAL only


0701 Address see Appendix B "Control A___ see Appendix B "Control Panel" power-on
Panel“
0702 Bus Set / reset possible only via Control Panel. power-on
connection Allows to use the UMC22-FBP without Field-
(not a para- BusPlug, e.g. as overload relay.
meter, only Off 0 Stand alone, without FieldBusPlug / fieldbus
for stand On 1 1 Connection to FieldBusPlug / fieldbus
alone)

FieldBusPlug / Issue: 10.2003 UMC22-FBP 31


Universal Motor Controller
UMC22-FBP
Technical Description V6

Technical data
Main power lines
Voltage (three-phase systems) max. 690 V AC, 50 or 60 Hz
Conductor holes in the current transformers 11 mm
Set current range for overload protection 0.24 A ... 63 A
Three-phase motors complete overload protection
Phase loss detection: If current of ... one phase: < 40% of other phases
other condition: phases > 70% of set current
Trip classes, selectable by parameter 5, 10, 20, 30
Tripping diagram

cold Class 30
minutes

Class 20
Trip time
| seconds

warm

2CDC 342 068 F0003


Class 10

Current related to set current

Currents higher than 10 x set current evaluated as about 10 x set current


cooling time simulation After trip the internal thermal motor model calculates
the reduction of the motor temperature (independent
of the parameter cooling time)
Cooling time cnstant ca. 20 min
If UMC22-FBP is no longer supplied calculation continues for some minutes (typ. 20 min)
Accuracy class
Factory adjustment Class 1.5
any combination of current transformer Class 2.5
set and control unit
Burden per phase 30 m⏲
Higher currents with current transformer, see chapter "Planning and
commissioning, external current transformer for
higher currents'. External current transformer
causes additional inaccuracy.
Frequency range 48 - 62 Hz
Short-circuit protection separate fuses on line side

32 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Technical data (continued)


Control unit
Supply voltage mode Internal or external
(see chapter ''Planning and commissioning, Wiring
and internal 24 V / 0 V connections'')
Supply voltage 19.2 ... 31.2 VDC including ripple
Supply current incl. inputs, relays activated max. 130 mA (at 18 ... 30 V DC)
Total device dissipation max. 3.1 W (at 24 V DC)
Reverse polarity protection yes
Number of digital inputs 6 (DI0 ... DI5)
Number of relay outputs 3 (DO0 ... DO2)
Number of bus interfaces 1 (for connecting an ABB FieldBusPlug)
Number of Control Panel interfaces 1 (to mount Control Panel ACS100-PAN)
Internal signal processing of control Selectable by parameters
function and other properties (see chapter "Data overview, Parameters, ..." and
Appendix A and B)
Parameter setting via Fieldbus, via Control Panel, see Appendix A / B
LEDs on front 1, green: Device ready for operation
1, red: Fault (trip, device fault etc.)
1, yellow: Motor current > 33% of set current
Diagnosis See chapter "Data overview, Diagnosis"

Digital Inputs
Number of digital inputs 6 (DI0 ... DI5)
Supply for digital inputs (terminal 12) Internal or external
(see chapter ''Planning and commissioning, Wiring
and internal 24 V / 0 V connections'')
Supply output current for inputs (terminal 12) max. 70 mA
Voltage when standard contacts are used min.18 V
Isolation no (see chapter ''Planning and commissioning,
Wiring and internal 24 V / 0 V connections'')
Input signal bounce suppression typ. 4 ms
1-Signal range including ripple -31.2 V ... +5 V
0-Signal range including ripple +13 V ... +31.2 V
Input current per channel (24 V DC) typ. 6.0 mA
Input resistor to 0V 3.9 k⏲
Line length unshielded max. 600 m
Line length shielded max. 1000 m
Conductor size (solide or stranded) 0.2-1.5 mm2 / AWG 15-24
Tightening torque 0.4 Nm

Digital 0utputs
Number of digital outputs 3 (DO0 ... DO2)
Type of digital outputs Relay contacts
Grouping of contacts 3 contacts with 1 common
Voltage range of contacts 12 ... 250 V AC
Lowest switched power for correct signals 1 W or 1 VA

FieldBusPlug / Issue: 10.2003 UMC22-FBP 33


Universal Motor Controller
UMC22-FBP
Technical Description V6

Technical data (continued)


Digital outputs (continued)
Switching capacity per relay contact
240 V AC (AC15 / EN 60947-5-1) max. 1.5 A (AC15: electromagnetic load)
120 V AC (AC15 / EN 60947-5-1) max. 3 A (AC15: electromagnetic load)
250 V DC (DC13 / EN60947-5-1) max. 0.11 A (DC13, electromagnetic load)
125 V DC (DC13 / EN60947-5-1) max. 0.22 A (DC13, electromagnetic load)
24 V DC (DC13 / EN60947-5-1) max. 1 A (DC13, electromagnetic load)
Total current all contacts (terminal 5 or 6) max. 4 A (thermal limit)
Short circuit protection 6 A gL / gG
Switching of inductive power Inductive loads need additional measures for
spark suppression. Diodes for DC voltage and
varistors / RC elements for AC voltage are
suitable. Some DC coil contactors contain
rectifiers which suppress sparks optimal.
Relay contact lifetime, mechanical 500 000 switching cycles
Lifetime 250 V AC / 0.5 A 100 000 switching cycles
Lifetime 250 V AC / 1.5 A 50 000 switching cycles
Internal clearance and creepage distances > 5.5 mm (safety insulation up to 250 V AC)
relay contacts to 24 V circuits (EN60947-1, Pollution degree 2)

FieldBusPlug connection
Mounting Plug connection, fastening with supplied screw
Tightening torque of the fixing screw 0.8 Nm + rotation 90 degree
Suitable ABB FieldBusPlug types PDP22-FBP (PROFIBUS-DP)
DNP22-FBP (DeviceNet)
MRP21-FBP (MODBUS) in preparation
COP21-FBP (CANopen) in preparation

Environment and mechanical data


Mounting on DIN rail (EN 50022-35) or with 4 screws M4
(refer to chapter "Technical data, Dimensions")

Dimensions W x H x D 70 x 105 x 110 mm


(incl. FieldBusPlug and Control Panel)
Net. weight (current transformer + control unit) 0.39 kg
Terminals: Conductor cross section max. 2.5 mm² or max. 2 x 1.5 mm²
Current transformer bushing holes 11 mm Ø (25 mm²)
Degree of protection IP 20
Storage temperature range -25 ... +70 °C
Operation temperature range 0 ... +55 °C
Approvals CE
Approvals (pending) UL, CSA, GL, BV, LRS, ATEX
MTBF

34 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description

Technical data (continued)


Ordering data
Universal Motor Controller UMC22-FBP Order code: 1SAJ 510 000 R0100

Control Panel
Control Panel ACS100-PAN Order code: 1SAJ 510 001 R0001
(not in scope of delivery, to order separately)
Control Panel Extension Cable ACS100-CAB Order code: 1SAJ 510 002 R0001
(not in scope of delivery, to order separately)

FieldBusPlugs
PDP22-FBP (PROFIBUS DP)
Cable length: 0.25 m Order code: 1SAJ 240 000 R0003
Cable length: 0.50 m Order code: 1SAJ 240 000 R0005
Cable length: 1.00 m Order code: 1SAJ 240 000 R0010
Cable length: 2.00 m Order code: 1SAJ 240 000 R0020
Cable length: 5.00 m Order code: 1SAJ 240 000 R0050
DNP22-FBP (DeviceNet)
Cable length: 0.25 m Order code: 1SAJ 230 000 R0003
Cable length: 0.50 m Order code: 1SAJ 230 000 R0005
Cable length: 1.00 m Order code: 1SAJ 230 000 R0010
Cable length: 5.00 m Order code: 1SAJ 230 000 R0050
MRP-21-FBP (MODBUS) in preparation
COP21-FBP (CANopen) in preparation

External current transformers


Type (recommended current range)
KORC 4L185 R/4 (63 -185 A) Order code: 1SCA 022 193 R7830
KORC 4L310 R/4 (185 - 310 A) Order code: 1SCA 022 181 R0760
KORC 5L500 R/4 (310 - 500 A) Order code: 1SCA 022 208 R1010
KORC 5L850 R/4 (500 - 850 A) Order code: 1SCA 022 208 R1440

Link kit (bar)


Type (for contactor type)
DT450/A185 (AF145 - AF185) Order code: 1SAZ 501 901R1001
DT450/A300 (AF260 - AF300) Order code: 1SAZ 501 902R1001
DT500/AL460S (AF400, AF460)* Order code: 1SAZ 701 902R1011
DT500/AL750S (AF580, AF750)* Order code: 1SAZ 801 902R1011
(*Link kits for Star-delta starter. Others see catalogue)

FieldBusPlug / Issue: 10.2003 UMC22-FBP 35


Universal Motor Controller
UMC22-FBP
Technical Description V6

Technical data (continued)


Dimensions

2CDC 342 031 F0003

Fig. 13: UMC22-FBP: Dimensions

36 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Appendix A: Control Functions


Circuit arrangement, description, data and parameters, timing diagrams

230 V N DO1 DO2 690 / 400 V

K1
K1

5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT

Plug

0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18

0 V 24 V 24 V DI0 DI1 DI2 DI3 DI4 DI5


if EXT to supply
supply inputs

2CDC 342 070 F0003

Fig. A-1: UMC22-FBP: Control function 'Direct starter' (example)

Contents Page

Control function ....................................................................................................................................... A-1


Transparent ......................................................................................................................................... A-2
Overload relay ..................................................................................................................................... A-4
Direct starter ....................................................................................................................................... A-8
Reversing starter .............................................................................................................................. A-13
Star-delta starter 1 ............................................................................................................................ A-19
Pole-changing starter 1 .................................................................................................................... A-25

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-1


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Transparent
The UMC22-FBP parameterized with the 'Control function' = 'Transparent' (default) behaves like an I/O-
module with an integrated overload check. The outputs DO0 ... DO2 and the inputs DI0 ... DI5 are
directly connected to the fieldbus and are independent of the overload status.
The only possible exception: DO2 outputs the internal fault signal, if the parameter 'Fault output' is set to
'On'. Default is 'Off', in this case the output is controlled directly via the fieldbus.
All kinds of faults set the internal fault bit. Following the monitoring signal FAULT is sent to the fieldbus,
the red LED lights on and the FAULT signal on the Control Panel flashes.
If a motor overload is the cause of the fault signal, the cooling time is started additionally. The cooling
time is a parameter and can be adjusted.
More detailed information are monitored in the diagnosis telegram and on the Control Panel.
All faults must be acknowledged via fieldbus or via Control Panel.
The slave address of the UMC22-FieldBusPlug combination is not a parameter but can be set with the
Control Panel or with a separate Addressing Set. Details see general part chapter ''Planning and
commissioning, Interfacing to the fieldbus, addressing''.

Circuit diagram (Basis circuit)


Parameters to be changed (based on default)
 Control function = Transparent (default)  Address via Control Panel or Addressing Set if
 Set current 1, overload protection parameters connected to bus

230 V DO0 DO1 DO2 690 / 400 V

Fault

5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT

Plug

0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18

0 V 24 V 24 V DI0 DI1 DI2 DI3 DI4 DI5


if EXT to supply
supply inputs
2CDC 342 071 F0003

Fig. A-2: UMC22-FBP: Control function 'Transparent' (Basis circuit)

Appendix A-2 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Transparent (continued)
Important:
Normally the inputs and the internal electronic circuits are supplied locally via the terminals 10 and 11. In
this case the SWITCH must be set to EXT. The connection of distant contacts or sensors requests
urgently this kind of supply.
If only contacts nest to the UMC22-FBP are used - that means the 24 V wiring can be surveyed easily -
the supply via the fieldbus and the FieldBusPlug is possible (SWITCH to INT).
Details see general part chapter ''Planning and commissioning, Wiring and internal 24 V / 0 V
connections''.

Interface and data overview


Device inputs / outputs

Terminal 13 14 15 16 17 18
Device DI0 DI1 DI2 DI3 DI4 DI5
Input to bus to bus to bus to bus to bus to bus
Terminal 7 8 9
Device DO0 DO1 DO2*
Outputs from bus from bus (fault output)

Fieldbus telegram: Monitoring signals / Command

Bit No. 7 6 5 4 3 2 1 0

Monitor
WARNING FAULT - - - - - -
Byte 0

Monitor DI5 DI4 DI3 DI2 DI1 DI0


- -
Byte 1 (UMC input) (UMC input) (UMC input) (UMC input) (UMC input) (UMC input)
Monitor
MOTOR CURRENT (% of set current)
Byte 2/3

Command FAULT
- - - - - - -
Byte 0 RESET
Command DO2* DO1 DO0
- - - - -
Byte 1 (UMC output) (UMC output) (UMC output)

Fieldbus telegram: Diagnosis

Bit No. 7 6 5 4 3 2 1 0

Fault Self-test
- - - - - - -
Byte 0 failed

Commu- Parameter
Fault Overload Motor
nication out of - - - -
Byte 1 (trip) fault blocked*
fault range
Motor Motor Cooling
Warning
current high current low - time - - - -
Byte 2
threshold* threshold* running

Fault Parameter number


Byte 3 (refers to Byte 1, Bit 4)

Details see general part chapter "Data overview" * depending on parameterization

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-3


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Overload relay
The UMC22-FBP parameterized with the 'Control function' = 'Overload relay' provides excellent
protection of a motor. Dedicated to replace a standard overload relay, stand-alone operation can be
selected via Control Panel setting the parameter 'Bus connection' = 'Off'.

Circuit diagram (Basis circuit)


Main features
 Motor contactor K1 at output DO0
Parameters to be changed (based on default)
 Control function = Overload relay  Set current 1, overload protection parameters
 Bus connection = Off (used without Fieldbus)  Address if connected to the fieldbus, via Control
(to be selected by Control Pane)l Panel or Addressing Set

230 V N trip DO2 690 / 400 V

Fault

K1
K1

ON

OFF

5 6 7 8 9
SWITCH
UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT

Plug

0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18

0 V 24 V 24 V DI0 DI1 DI2 DI3 DI4 DI5


if EXT to supply
supply inputs
2CDC 342 072 F0003

Fig. A-3: UMC22-FBP: Control function 'Overload relay' (Basis circuit)

Appendix A-4 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Overload relay (continued)


Description
After parameterizing 'Control function' = 'Overload relay' and 'Bus connection = Off' power-on is necessa-
ry to start the operation. Immediately contact DO0 opens, contact DO1 closes. If 'Bus connection' = 'On',
the active connection to the control system is an additional condition to start the operation.
Attached control functions
With 'Fault output' = 'On', also the output contact DO2 operates similar to DO0.
Remark: If 'Fault output' = 'Off', output contact DO2 can be controlled via fieldbus.
Fault behaviour
All kinds of detected external and internal faults set the internal fault bit. In the following:
 contact DO0 (and DO2 if parameterized) closes,
 DO1 opens,
 the monitoring signal FAULT is sent to the fieldbus,
 the red LED on the UMC22-FBP lights on and
 the FAULT signal on the Control Panel display flashes.
If a motor overload is the cause of the fault signal, the cooling time'is started additionally . The cooling
time is a parameter and can be adjusted.
All faults must be acknowledged via fieldbus or via Control Panel. In addition the cooling time must be
elapsed to allow to restart the motor.
Exception: If the parameter 'Automatic fault reset' = 'On', the contacts DO0 (and DO2) closes and DO1
opens immediately when the cooling time is over (only available with overload relay).
Addressing
The slave address of the UMC22-FieldBusPlug combination is not a parameter but can be set with the
Control Panel or with a separate Addressing Set. Details see general part chapter ''Planning and com-
missioning, Interfacing to the fieldbus, addressing''.

Important:
When connected to a fieldbus via FieldBusPlug:
Normally the inputs and the internal electronic circuits are supplied locally via the terminals 10 and 11. In
this case the SWITCH must be set to EXT. The connection of distant contacts or sensors requests
urgently this kind of supply.
If only contacts nest to the UMC22-FBP are used - that means the 24 V wiring can be surveyed easily -
the supply via the fieldbus and the FieldBusPlug is possible (SWITCH to INT).
Details see general part chapter ''Planning and commissioning, Wiring and internal 24 V / 0 V
connections''.

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-5


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Overload relay (continued)

Interface and data overview


Device inputs / outputs

Terminal 13 14 15 16 17 18
Device DI0 DI1 DI2 DI3 DI4 DI5
Input to bus to bus to bus to bus to bus to bus
Terminal 7 8 9
Device trip DO2*
trip
Outputs inverted from bus

Fieldbus telegram: Monitoring signals / Command

Bit No. 7 6 5 4 3 2 1 0

Monitor
WARNING FAULT - - - - - -
Byte 0

Monitor DI5 DI4 DI3 DI2 DI1 DI0


- -
Byte 1 (UMC input) (UMC input) (UMC input) (UMC input) (UMC input) (UMC input)
Monitor
MOTOR CURRENT (% of set current)
Byte 2/3

Command FAULT SELF-


- - - - - -
Byte 0 RESET TEST
Command DO2*
- - - - - - -
Byte 1 (UMC output)

Fieldbus telegram: Diagnosis

Bit No. 7 6 5 4 3 2 1 0

Fault Self-test
- - - - - - -
Byte 0 failed

Commu- Parameter
Fault Overload Motor
nication out of - - - -
Byte 1 (trip) fault blocked*
fault range
Motor Motor Cooling
Warning
current high current low - time - - - -
Byte 2
threshold* threshold* running

Fault Parameter number


Byte 3 (refers to Byte 1, Bit 4)

Details see general part chapter "Data overview" * depending on parameterization

Appendix A-6 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Overload relay (continued)


Timing diagram: Overload

FAULT RESET end of


FAULT via fieldbus or cooling
(trip) Control Panel time

UMC internal FAULT

Command
(received telegram)
FAULT RESET

(/trip) DO0
UMC outputs
(trip) DO1

Monitoring signals FAULT


(telegram)
WARNING

2CDC 342 069 F0003


Cooling time running
Diagnosis
Overload (trip) fault

LEDs red LED (Fault LED)

Fig. A-4: UMC22-FBP: Control function 'Overload relay' - Timing diagram 'Overload'

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-7


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Direct starter
The UMC22-FBP parameterized with the 'Control function' = 'Direct starter' provides excellent protection
and control of a motor for one direction of rotation. The connection to a fieldbus is made via the appropri-
ate type of the FieldBusPlug.

Circuit diagram (Basis circuit)


Main features
 Contactor K1 at DO0  Check-back by motor current
Parameters to be changed (based on default)
 Control function = Direct starter  Set current 1, overload protection parameters
 Address via Control Panel or Addressing Set

230 V N DO1 DO2 690 / 400 V

K1
K1

5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT

Plug

0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18

0 V 24 V 24 V DI0 DI1 DI2 DI3 DI4 DI5


if EXT to supply
2CDC 342 070 F0003

supply inputs

Fig. A-5: UMC22-FBP: Control function 'Direct starter' (Basis circuit)

Appendix A-8 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Direct starter (continued)


Circuit diagram (Extended circuit)
Main features
 Contactor K1 at output DO0  Fault lamp at output DO2
 Check-back by auxiliary contacts at input DI0  Fault input (closed circuit) at DI2
 Local operation via inputs DI4 and DI5
Parameters to be changed (based on default)
 Control function = Direct starter  Set current 1, overload protection parameters
 Fault output signal = On  Check-back = Auxiliary contact
 Fault input = On  Local operation via digital inputs = On
 Address via Control Panel or Addressing Set

230 V N DO1 690 / 400 V

Fault

K1
K1

5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT

INT

Plug

0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18

thermistor
K1 switch 1)
2CDC 342 085 F0003

0 V 24 V 24 V DI1 PTC DI3 Fwd Off


if EXT to supply transparent Local operation via
supply inputs to bus digital inputs 2), 3)
Fig. A-6: UMC22-FBP: Control function 'Direct starter' (Extended circuit)

1)
Fault input: Closed circuit signal: 1 = no fault
2)
Fwd: Momentary-contact switch
3)
Off: Closed circuit signal: 0 = dominating Off

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-9


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Direct starter (continued)


Description
The UMC22-FBP parameterized with the 'Control function' = 'Direct starter' provides excellent protection
and control of a motor for one direction of rotation. The connection to a fieldbus is made via the appropri-
ate type of the FieldBusPlug.
With direct starter the output DO0 is defined to drive the motor contactor coil.

Attached control functions


The parameter set 'Attached control functions' prepares the direct starter to support different circuit
arrangements including the use of inputs and outputs for particular use.
Examples:
'Fault output' = 'On': The output contact DO2 closes if a fault appears.
'Fault input' = 'On': A closed circuit signal (24 V) on input DI2 corresponds to the fault-free status.
Remark: Only remaining outputs can be controlled but all inputs are monitored via fieldbus.
Other parameters define the protection behaviour and additional functions. Refer also general part
chapter ''Data overview, Parameters ...''.
Starting
After setting the parameter 'Direct starter', power-on is necessary to activate and to allow to start the
motor with the bus command RUN FORWARD or via local control. All other parameters are activated
with motor on.

Check-back
When the motor is started, the check-back status is expected within 100 ms, otherwise a fault is de-
tected. Selectable by parameter, motor current or auxiliary contact signal can serve as check-back
status.
Notice: 'Check-back' = 'Simulation' is recommended only to be set via Control Panel during commissio-
ning. The control system is only allowed to set 'Auxiliary contacts' or 'Motor current' to guarantee
that the check-back operates correctly after next power-on.

Fault behaviour
All kinds of detected external and internal faults set the internal fault bit. In the following:
 contact DO0 for the contactor coil opens,
 the monitoring signal FAULT is sent to the fieldbus,
 the red LED on the UMC22-FBP lights on and
 the FAULT signal on the Control Panel display flashes.
If a motor overload is the cause of the fault signal, the cooling time is started additionally . The cooling
time is a parameter and can be adjusted.
More detailed information are monitored in the diagnosis telegram and on the Control Panel.
All faults must be acknowledged via fieldbus or via Control Panel. In addition the cooling time must be
elapsed to allow to restart the motor.

Addressing
The slave address of the UMC22-FieldBusPlug combination is not a parameter but can be set with the
Control Panel or with a separate Addressing Set. Details see general part chapter ''Planning and com-
missioning, Interfacing to the fieldbus, addressing''.

Important:
Normally the inputs and the internal electronic circuits are supplied locally via the terminals 10 and 11. In
this case the SWITCH must be set to EXT. The connection of distant contacts or sensors requests
urgently this kind of supply.
If only contacts nest to the UMC22-FBP are used - that means the 24 V wiring can be surveyed easily -
the supply via the fieldbus and the FieldBusPlug is possible (SWITCH to INT).
Details see general part chapter ''Planning and commissioning, Wiring an d int ernal 24V / 0V
connections''.

Appendix A-10 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Direct starter (continued)

Interface and data overview


Device inputs / outputs

Terminal 13 14 15 16 17 18
Device DI0 DI1 DI2 DI3 DI4* DI5*
Input to bus to bus to bus to bus (local: Run) (local: Off)
Terminal 7 8 9
Device DO0 DO1 DO2*
Outputs from bus from bus (fault out)

Fieldbus telegram: Monitoring signals / Command

Bit No. 7 6 5 4 3 2 1 0

Monitor LOCAL RUN


WARNING FAULT - - OFF -
Byte 0 CONTROL FORWARD

Monitor DI5 DI4 DI3 DI2 DI1 DI0


- -
Byte 1 (UMC input) (UMC input) (UMC input) (UMC input) (UMC input) (UMC input)
Monitor
MOTOR CURRENT (% of set current)
Byte 2/3

Command FAULT AUTO RUN


- - - OFF -
Byte 0 RESET MODE FORWARD
Command DO2* DO1*
- - - - - -
Byte 1 (UMC output) (UMC output)

Fieldbus telegram: Diagnosis

Bit No. 7 6 5 4 3 2 1 0
Fault
Fault Self-test
- input - - - - -
Byte 0 failed
signal*
Commu- Parameter Current Relay 1
Fault Overload Motor
nication out of check-back - - check-back
Byte 1 (trip) fault blocked*
fault range fault* fault*
Motor Motor Cooling
Warning
current high current low - time - - - -
Byte 2
threshold* threshold* running

Fault Parameter number


Byte 3 (refers to Byte 1, Bit 4)

Details see general part chapter "Data overview" * depending on parameterization

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-11


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Direct starter (continued)


Timing diagram: Overload

RUN FAULT RESET RUN end of RUN


FOR- Over- via fieldbus or FOR- cooling FOR-
WARD load Control Panel WARD time WARD

RUN FORWARD
Command
(received telegram) OFF

FAULT RESET

UMC internal FAULT

UMC outputs DO0

Check-back Mot.cur. / Aux.cont.

RUN FORWARD

OFF

Monitoring signals
(telegram) WARNING

FAULT

(Aux.cont.) DI0

Cooling time running Cooling time


Diagnosis
Overload (trip) fault

2CDC 342 055 F0003


yellow LED (Mot. on)
LEDs
red LED (Fault LED)

Fig. A-7: UMC22-FBP: Control function 'Direct starter' - Timing diagram 'Overload'

Abbreviations:
Mot.cur. = Motor current
Aux.cont. = Auxiliary contact
Mot. on = Motor on

Appendix A-12 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Reversing starter
The UMC22-FBP parameterized with the 'Control function' = 'Reversing starter' provides excellent
protection and control of a motor for two directions of rotation. The connection to a fieldbus is made via
the appropriate type of the FieldBusPlug.

Circuit diagram (Basis circuit)


Main features
 Contactor K1 (forward) at output DO0  Contactor K2 (reverse) at output DO1
 Check-back by motor current
Parameters to be changed (based on default)
 Control function = Reversing starter  Set current 1, overload protection parameters
 Address via Control Panel or Addressing Set

230 V N DO2 690 / 400 V


K1 = forward
K2 = reverse

K1
K1
K2
K2

5 6 7 8 9
SWITCH
DO DO DO DO DO
FieldBus UMC22 C C 0 1 2
EXT

INT

Plug

0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18

0 V 24 V 24 V DI0 DI1 DI2 DI3 DI4 DI5


if EXT to supply
supply inputs
2CDC 342 073 F0003

Fig. A-8: UMC22-FBP: Control function 'Reversing starter' (Basis circuit)

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-13


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Reversing starter (continued)


Circuit diagram (Extended circuit)
Main features
 Contactor K1 (forward) at out. DO0  Contactor K2 (reverse) at out. DO1
 Fault lamp at output DO2  Check-back by auxiliary contact at input DI0
 Fault input (closed circuit) at DI2  Local operation via inputs DI3, DI4 and DI5
Parameters to be changed (based on default)
 Control function = Reversing starter  Set current 1, overload protection parameters
 Fault output = On  Check-back = Auxiliary contacts
 Fault input = On  Local operation via digital inputs = On
 Address via Control Panel or Addressing Set

230 V N 690 / 400 V

K1 = forward
K2 = reverse
Fault
K1
K1
K2
K2

5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT

INT

Plug

0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18

thermistor
K1 K2 switch 1)
2CDC 342 086 F0003

0 V 24 V 24 V DI1 PTC Rev Fwd Off


if EXT to supply transparent Local operation via
supply inputs to bus digital inputs 2), 3)

Fig. A-9: UMC22-FBP: Control function 'Reversing starter' (Extended circuit)

1)
Fault input: Closed circuit signal: 1 = no fault
2)
Fwd, Rev: Momentary-contact switch
3)
Off: Closed circuit signal: 0 = dominating Off

Appendix A-14 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Reversing starter (continued)


Description
The UMC22-FBP parameterized with the 'Control function' = 'Reversing starter' provides excellent
protection and control of a motor for two directions of rotation. The connection to a fieldbus is made via
the appropriate type of the FieldBusPlug.
With reversing starter, the outputs DO0 (forward) and DO1 (reverse) are defined to drive the motor
contactor coils.

Attached control functions


The parameter set 'Attached control functions' prepares the reversing starter to support different circuit
arrangements including the use of inputs and outputs for particular use.
Examples:
'Fault output' = 'On': The output contact DO2 closes if a fault appears.
'Fault input' = 'On': A closed circuit signal (24 V) on input DI2 corresponds to the fault free status.
Remark: Via Fieldbus, only remaining outputs can be controlled but all inputs are monitored.
To define the protection behaviour and other functions additional parameters are available. Refer also
general part chapter ''Data overview, Parameters ...''.

Starting
After setting the parameter 'Reversing starter' power-on is necessary to activate and to allow to start the
motor with the bus command RUN FORWARD / RUN REVERSE or via local control. All other
parameters are activated with motor on.

Change direction
 An OFF command is necessary before switching to the opposite direction.
 The OFF command starts the reversing lock-out time (parameterizable).
 The opposite RUN command - 0-1 transition - is accepted only when the reversing lock-out time has
elapsed.

Check-back
When the motor is started the check-back status is expected within 100 ms, otherwise a fault is detected.
Selectable by parameter, motor current or auxiliary contact signal can serve as check-back status.
Notice: 'Check-back' = 'Simulation' is recommended only to be set via Control Panel during commissio-
ning. The control system is only allowed to set 'Auxiliary contacts' or 'Motor current' to guarantee
that the check-back operates correctly after next power-on.

Fault behaviour
All kinds of detected external and internal faults set the internal fault bit. In the following:
 contact DO0 or DO1 for the contactor coil opens,
 the monitoring signal FAULT is sent to the fieldbus,
 the red LED on the UMC22-FBP lights on and
 the FAULT signal on the Control Panel display flashes.
If a motor overload is the cause of the fault signal, the cooling time is started additionally. The cooling
time is a parameter and can be adjusted.
All faults must be acknowledged via fieldbus or via Control Panel. In addition the cooling time must be
elapsed to allow to restart the motor with a 0-1 transition of the RUN FORWARD or RUN REVERSE
command.
More detailed information are monitored in the diagnosis telegram and on the Control Panel.

Addressing
The slave address of the UMC22-FieldBusPlug combination is not a parameter but can be set with
Control Panel or with separate Addressing Set. Details see general part chapter ''Planning and
commissioning, Interfacing to the fieldbus, addressing''.

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-15


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Reversing starter (continued)


Important:
Normally the inputs and the internal electronic circuits are supplied locally via the terminals 10 and 11. In
this case the SWITCH must be set to EXT. The connection of distant contacts or sensors requests
urgently this kind of supply.
If only contacts nest to the UMC22-FBP are used - that means the 24 V wiring can be surveyed easily -
the supply via the fieldbus and the FieldBusPlug is possible (SWITCH to INT).
Details see general part chapter ''Planning and commissioning, Wiring an d int ernal 24V / 0V
connections''.

Interface and data overview


Device inputs / outputs

Terminal 13 14 15 16 17 18
Device DI0* DI1 DI2* DI3* DI4* DI5*
Input (aux. cont.) to bus (ext. fault) (local: Rev) (local: Fwd) (local: Off)
Terminal 7 8 9
Device DO0 DO1 DO2*
Outputs (Forward) (Reverse) (fault out)

Fieldbus telegrams: Monitoring signals / Command

Bit No. 7 6 5 4 3 2 1 0
REVERSING
Monitor LOCAL RUN RUN
WARNING FAULT LOCK-OUT - OFF
Byte 0 CONTROL FORWARD REVERSE
TIME
Monitor DI5 DI4 DI3 DI2 DI1 DI0
- -
Byte 1 (UMC input) (UMC input) (UMC input) (UMC input) (UMC input) (UMC input)
Monitor
MOTOR CURRENT (% of set current)
Byte 2/3

Command FAULT AUTO RUN RUN


- - - OFF
Byte 0 RESET MODE FORWARD REVERSE
Command DO2* DO1*
- - - - - -
Byte 1 (UMC output) (UMC output)

Fieldbus telegram: Diagnosis

Bit No. 7 6 5 4 3 2 1 0
Fault
Fault Self-test
- input - - - - -
Byte 0 failed
signal*
Commu- Parameter Current Relay 1
Fault Overload Motor
nication out of check-back - - check-back
Byte 1 (trip) fault blocked*
fault range fault* fault*
Motor Motor Cooling Reversing
Warning
current high current low - time lock-out - - -
Byte 2
threshold* threshold* running time

Fault Parameter number


Byte 3 (refers to Byte 1, Bit 4)

Details see general part chapter ''Data overview''. * depending on parameterization


Appendix A-16 UMC22-FBP FieldBusPlug / Issue: 10.2003
Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Reversing starter (continued)


Timing diagram 1: Change direction

RUN
RUN REVERSE RUN
FORWARD OFF ignored REVERSE

RUN FORWARD
Command
(received telegram) RUN REVERSE

OFF

DO0 (forward)
UMC outputs
DO1 (reverse)

Check-back Mot.cur. / Aux.cont.

RUN FORWARD

RUN REVERSE
Monitoring signals
(telegram)
OFF

2CDC 342 056 F0003


LOCK-OUT TIME Rev.lock-out time

LEDs yellow LED (Mot. on)

Fig. A-10: UMC22-FBP: Control function 'Reversing starter' - Timing diagram 'Change direction'

Abbreviations:
Mot.cur. = Motor current
Aux.cont. = Auxiliary contact
Mot. on = Motor on
Rev.lock-out time = Reversing lock-out time
Remark:
 Opposite direction only possible after 'OFF'.
 Restart in the same direction without regard of the reversing lock-out time.

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-17


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Reversing starter (continued)


Timing diagram 2: Overload

RUN FAULT RESET RUN end of RUN


FOR- Over- via fieldbus or FOR- cooling FOR-
WARD load Control Panel WARD time WARD

RUN FORWARD

RUN REVERSE
Command
(received telegram)
OFF

FAULT RESET

UMC internal FAULT

DO0 (forward)
UMC outputs
DO1 (reverse)

Check-back Mot.cur. / Aux.cont.

RUN FORWARD

RUN REVERSE

OFF
Monitoring signals
(telegram)
WARNING

FAULT

(Aux.cont.) DI0

Cooling time running


Cooling time
Diagnosis
Overload (trip) fault
2CDC 342 057 F0003

yellow LED (Mot. on)


LEDs
red LED (Fault LED)

Fig. A-11: UMC22-FBP: Control function 'Reversing starter' - Timing diagram 'Overload'

Abbreviations:
Mot.cur. = Motor current
Aux.cont. = Auxiliary contact
Mot. on = Motor on
Remark:
 Restart possible only if cooling time has elapsed and fault is acknowledged.

Appendix A-18 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Star-delta starter 1
The UMC22-FBP parameterized with the 'Control function' = 'Star-delta starter 1' provides excellent
protection and control of a motor for one direction of rotation including the time or current conrolled star-
delta transition. The connection to a fieldbus is made via the appropriate type of the FieldBusPlug.

Circuit diagram (Basis cirsuit)


Main features
 Contactor K1 (star) at out. DO0  Contactor K2 (delta) at output DO1
 Motor contactor K3 (main) via auxiliary  Check-back by motor current
contact of the star and delta contactor
Parameters to be changed (based on default)
 Control function = Star-delta starter 1  Set current and overload protection parameters
 Address via Control Panel or Addressing Set

230 V N DO2 690 / 400 V


K1 = Star
K2 = Delta
K3 = Main

K3
K3
K2
K2
K1
K1

5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT

Plug

0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18

0 V 24 V 24 V DI0 DI1 DI2 DI3 DI4 DI5


2CDC 342 074 F0003

if EXT to supply
supply inputs

Fig. A-12: UMC22-FBP: Control function 'Star-delta starter 1' (Basis circuit)

Remark:
For this case of motor wiring the set current 1 has to be set to 58% of the nominal motor current. Details
see general part chapter ''Planning and commissioning, Set current = Motor current versus wiring''.

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-19


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Star-delta starter 1 (continued)


Circuit diagram (Extended circuit)
Main features
 Contactor K1 (star) at output DO0  Contactor K2 (delta) at output DO1
 Contactor K3 (main) at auxiliary contacts  Fault lamp at output DO2
 Check-back by auxiliary contacts at inputs DI0  Fault input (closed circuit) at DI2
and DI1  Local operation via inputs DI4 and DI5
Parameters to be changed (based on default)
 Control function = Star-delta starter 1
 Fault output = On  Check-back = Auxiliary contacts
 Fault input = On  Local operation via digital inputs = On
 Set current 1, overload protection parameters  Address via Control Panel or Addressing Set

230 V N 690 / 400 V

K1 = Star
K2 = Delta
K3 = Main
K3 Fault
K3
K2
K2
K1
K1

5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT

Plug

0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18

K1 K2 thermistor
switch 1)
K3
2CDC 342 087 F0003

0 V 24 V 24 V PTC DI3 Run Off


if EXT to supply Local operation via
supply inputs digital inputs 2), 3)
Fig. A-13: UMC22-FBP: Control function 'Star-delta starter 1' (Extended circuit)

Remark:
For this case of motor wiring the set current 1 must be set to 58% of the nominal motor current. Details
see general part chapter ''Planning and commissioning, Set current = Motor current versus wiring''.
1)
Fault input: Closed circuit signal: 1 = no fault
2)
Run: Momentary-contact switch 3)
Off: Closed circuit signal: 0 = dominating Off

Appendix A-20 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Star-delta starter 1 (continued)


Description
With star-delta starter 1, the outputs DO0 (star) and DO1 (delta) are defined to drive the motor contactor
coils. The main contactor is controlled via auxiliary contacts of the star and delta contactors. Once the
motor is started with RUN FORWARD, the star-delta-sequence is controlled automatically by the
UMC22-FBP.

Attached control functions


The parameter set 'Attached control functions' prepares the star-delta starter 1 to support different circuit
arrangements including the use of inputs and outputs for particular use.
Examples:
'Star-delta change over mode' = 'Time': The UMC22-FBP switches over after the parametrizable 'Star-
delta-starting time' (default 60 s).
'Star-delta change over mode' = 'Current': (Default) Switches over when current is lower than 90% of set
current 1. In this case the star-delta-starting time is used to
surveille the correct star-delta transition. The transition time
star to delta is fixed 50 ms after current is 0 or auxiliary
contacts are open resp.
'Fault output' = 'On': The output contact DO2 closes if a fault appears.
'Fault input' = 'On': A closed circuit signal (24 V) on input DI2 corresponds to the fault free status.
Remark: Via Fieldbus only remaining outputs can be controlled but all inputs are monitored.
To define the protection behaviour and other functions additional parameters are available. Refer also to
general part chapter 'Data overview, Parameters ...''.
Starting
After setting the parameter 'Star-delta starter 1', power-on is necessary to activate and to allow to start
the motor with the bus command RUN FORWARD or via local control. All other parameters are activated
with motor on.

Check-back
When the motor is started the check-back status is expected within 100 ms, otherwise a fault is detected.
Selectable by parameter, motor current or auxiliary contact signal can serve as check-back status.
Notice: 'Check-back' = 'Simulation' is recommended only to be set via Control Panel during commissio-
ning. The control system is only allowed to set 'Auxiliary contacts' or 'Motor current' to guarantee
that the check-back operates correctly after next power-on.

Fault behaviour
All kinds of detected external and internal faults set the internal fault bit. In the following:
 contact DO0 or DO1 for the contactor coil opens,
 the monitoring signal FAULT is sent to the fieldbus,
 the red LED on the UMC22-FBP lights on and
 the FAULT signal on the Control Panel display flashes.
If a motor overload is the cause of the fault signal, the cooling time is started additionally. The cooling
time is a parameter and can be adjusted.
More detailed information are monitored in the diagnosis telegram and on the Control Panel.
All faults must be acknowledged via fieldbus or via Control Panel. In addition the cooling time must be
elapsed to allow to restart the motor with a 0-1 transition of the RUN FORWARD command.

Addressing
The slave address of the UMC22-FieldBusPlug combination is not a parameter but can be set with the
Control Panel or with a separate Addressing Set. Details seegeneral part chapter ''Planning and
commissioning, Interfacing to the fieldbus, addressing''.

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-21


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Star-delta starter 1 (continued)


Important:
Normally the inputs and the internal electronic circuits are supplied locally via the terminals 10 and 11. In
this case the SWITCH must be set to EXT. The connection of distant contacts or sensors requests
urgently this kind of supply.
If only contacts nest to the UMC22-FBP are used - that means the 24 V wiring can be surveyed easily -
the supply via the fieldbus and the FieldBusPlug is possible (SWITCH to INT).
Details see general part chapter ''Planning and commissioning, Wiring and internal 24 V / 0 V
connections''.

Interface and data overview


Device inputs / outputs

Terminal 13 14 15 16 17 18
Device DI0* DI1 DI2* DI3 DI4* DI5*
Input (aux.cont.) to bus (ext. fault) to bus (local: Run) (local: Off)
Terminal 7 8 9
Device DO0 DO1 DO2*
Outputs (star) (delta) (fault out)

Fieldbus telegram: Monitoring signals / Command

Bit No. 7 6 5 4 3 2 1 0

Monitor LOCAL RUN


WARNING FAULT - - OFF -
Byte 0 CONTROL FORWARD

Monitor DI5 DI4 DI3 DI2 DI1 DI0


- -
Byte 1 (UMC input) (UMC input) (UMC input) (UMC input) (UMC input) (UMC input)
Monitor
MOTOR CURRENT (% of set current)
Byte 2/3

Command FAULT AUTO RUN


- - - OFF -
Byte 0 RESET MODE FORWARD
Command DO2*
- - - - - - -
Byte 1 (UMC output)

Fieldbus telegram: Diagnosis

Bit No. 7 6 5 4 3 2 1 0
Fault
Fault Self-test
- input - - - - -
Byte 0 failed
signal*
Commu- Parameter Current Relay 1 Relay 0
Fault Overload Motor
nication out of check-back - check-back check-back
Byte 1 (trip) fault blocked*
fault range fault* fault* fault*
Motor Motor Cooling
Warning
current high current low - time - - - -
Byte 2
threshold* threshold* running

Fault Parameter number


Byte 3 (refers to Byte 1, Bit 4)

Details see general part chapter ''Data overview'' * depending on parameterization

Appendix A-22 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Star-delta starter 1 (continued)


Timing diagram 1: Star-delta start

RUN FORWARD OFF

Command RUN FORWARD


(received telegram)
OFF

DO0 (Star) Star-delta starting time


UMC outputs
DO1 (Delta)
Change-over time 50 ms

Check-back Mot.cur. / Aux.cont.

RUN

Monitoring signals OFF


(telegram)
DI0 (Aux.cont. star)

2CDC 342 058 F0003


DI1 (Aux.cont. delta)

LEDs yellow LED (Mot. on)

Fig. A-14: UMC22-FBP: Control function 'Star-delta starter 1' - Timing diagram 'Star-delta start'

Abbreviations:
Mot.cur. = Motor current
Aux.cont. = Auxiliary contact
Mot. on = Motor on

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-23


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Star-delta starter 1 (continued)


Timing diagram 2: Overload

RUN FAULT RESET RUN end of RUN


FOR- Over- via fieldbus or FOR- cooling FOR-
WARD load Control Panel WARD time WARD

RUN FORWARD
Command
(received telegram) OFF

FAULT RESET

UMC internal FAULT

UMC outputs DO0 (than DO1)

Check-back Mot.cur. / Aux.cont.

RUN

OFF

Monitoring signals
WARNING Cooling time
(telegram)

FAULT

(Aux.cont.) DI0

Cooling time running


Diagnosis
Overload (trip) fault

yellow LED (Mot. on) 2CDC 342 059 F0003


LEDs
red LED (Fault LED)

Fig. A-15: UMC22-FBP: Control function 'Star-delta starter 1' - Timing diagram 'Overload'

Abbreviations:
Mot.cur. = Motor current
Aux.cont. = Auxiliary contact
Mot. on = Motor on

Appendix A-24 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Pole-changing starter 1
The UMC22-FBP parameterized with the 'Control function' = 'Pole-changing starter 1' provides excellent
protection and control of a two-pole or Dahlander motor for one direction of rotation. The change from
one speed to the other is possible immediately. The connection to a fieldbus is made via the appropriate
type of FieldBusPlug.

Circuit diagram - Two-pole motor (Basis circuit)


Main features
 Contactor K1 at output DO0  Contactor K2 at output DO1
 Check-back by motor current
Parameters to be changed (based on default)
 Control function = Pole-changing starter 1  Set current 1, Set current 2, Overload protection
 Address via Control Panel or Addressing Set parameters

230 V N DO2 690 / 400 V


K1 = Speed 1
K2 = Speed 2

K2

K1

5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT

Plug

0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18

0 V 24 V 24 V DI0 DI1 DI2 DI3 DI4 DI5


if EXT to supply K1 K2
supply inputs
2CDC 342 075 F0003

U1 U2
V1 V2
W1 W2

Fig. A-16: UMC22-FBP: Control function 'Pole-changing starter1 - Two-pole motor' (Basis circuit)

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-25


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Pole-changing starter 1 (continued)


Circuit diagram - Two-pole motor (Extended circuit)
Main features
 Contactor K1 at output DO0  Contactor K2 at output DO1
 Fault lamp at output DO2  Check-back by aux.contacts on DI0
 Fault input (closed circuit) at DI2  Local operation via inputs DI4 and DI5
Parameters to be changed (based on default)
 Control function = Pole-changing starter 1  Set current 1, Set current 2, overload protection
 Fault output = On parameters
 Fault input = On  Check-back = Auxiliary contacts
 Address via Control Panel or Addressing Set  Local operation via digital inputs = On

230 V N 690 / 400 V

K1 = Speed 1
K2 = Speed 2
Fault
K2

K1

5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT

INT

Plug

0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18

thermistor
switch 1)
K1 K2 K2 K1

U1 U2
V1 V2
0 V 24 V 24 V DI1 PTC Run RUN Off W1
2CDC 342 077 F0003

W2
K2 K1
if EXT to supply Local operation via
supply inputs digital inputs 2), 3)

Fig. A-18: UMC22-FBP: Control function 'Pole-changing starter 1 - Two-pole motor' (Extended circuit)

1)
Fault input: Closed circuit signal: 1 = no fault
2)
Run A, Run B: Momentary-contact switch 3)
Off: Closed circuit signal: 0 = dominating Off

Appendix A-26 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Pole-changing starter 1 (continued)

Circuit diagram - Dahlander motor (Basis circuit)


Main features
 Contactor K1 output DO0  Contactor K2a at output DO1
 Contactor K2b via auxiliary contact of the  Check-back by motor current
contactor B2
Parameters to be changed (based on default)
 Control function = Pole-changing starter 1  Set current 1, Set current 2, overload protection
 Address via Control Panel or Addressing Set parameters

230 V N DO2 690 / 400 V

K1 = Speed 1
K2a/b = Speed 2
K2a

K2b

K1

5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT

INT

Plug

0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18

0 V 24 V 24 V DI0 DI1 DI2 DI3 DI4 DI5 K1 K2a


if EXT to supply
supply inputs K2b
2CDC 342 076 F0003

U1 U2
V1 V2
W1 W2
Fig. A-17: UMC22-FBP: Control function 'Pole-changing starter1 - Dahlander motor' (Basis circuit)

Remark:
Output DO1 controls contactor K2b. Do not change!

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-27


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Pole-changing starter 1 (continued)


Circuit diagram - Dahlander motor starter (Extended circuit)
Main features
 Contactor K1 at output DO0  Contactor K2b at output DO1
 Contactor K2a via auxiliary contact of the  Fault lamp at output DO2
contactor K2b  Check-back by auxiliarycontacts DI0 and DI1
 Fault input (closed circuit) at DI2  Local operation via inputs DI4 and DI5
Parameters to be changed (based on default)
 Control function = Pole-changing starter 1  Set current1, Set current 2, overload protection
 Fault output = On parameters
 Fault input = On  Check-back = Auxiliary contacts
 Address via Control Panel or Addressing Set  Local operation via digital inputs = On

230 V N 690 / 400 V


K1 = Speed 1
K2a/b = Speed 2

K2a Fault

K2b

K1

5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT

INT

Plug

0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18

thermistor
switch 1)
K1 K2a K1 K2a

K2b

U1 U2
0 V 24 V 24 V DI1 PTC Run Run Off V1 V2
2CDC 342 078 F0003

K2 K1 W1 W2
if EXT to supply Local operation via
supply inputs digital inputs 2), 3)

Fig. A-19: UMC22-FBP: Control function 'Pole-changing starter 1 - Dahlander motor' (Extended circuit)

0)
K2b controls K2a, do not change! 1)
Fault input: Closed circuit signal: 1 = no fault
2)
Run K1, Run K2: Momentary-contact switch 3)
Off: Closed circuit signal: 0 = dominating Off

Appendix A-28 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Pole-changing Starter 1 (continued)


Description
With pole-changing starter 1 the outputs DO0 and DO1 are defined to drive the contactor coils as shown
in the circuit diagrams. The contactors are locked electronically to avoid short circuit due to not extinct
spark. The lock-out time is fixed 50 ms.
To keep this lock-out function for dahlander start also the contactors K1 and K2b must be controlled by
the UMC22-FBP outputs. Contactor K2a is controlled by an auxiliary contact of the contactor K2b.

Attached control functions


The parameter set ‘Attached control functions’ prepares the pole-changing starter 1 to support different
circuit arrangements including the use of inputs and outputs for particular use.
Examples:
‘Fault output’ = ‘On’: The output contact DO2 closes if a fault appears.
‘Fault input’ = ‘On’: A closed circuit signal (24 V) on input DI2 corresponds to the fault free status.
Remark: Only remaining outputs can be controlled but all inputs are monitored via fieldbus.
To define the protection behaviour and other functions additional parameters are available. Refer also to
general part chapter ''Data overview, Parameters ...''.
For the two speeds different set currents can be adjusted, see parameters 'Set current 1' (relates to
DO0) and 'Set current 2' (DO1).

Starting
After setting the parameter ‘Pole-changing starter 1’ power-on is necessary to activate and to allow to
start the motor with the bus command RUN FORWARD (speed 1, contactor K1), RUN REVERSE
(speed 2, contactors K2a and K2b) or via local control. All other parameters are activated with motor on.
Change of the speed (K1->K2->K1) is possible without restriction. Between the two speeds a lock-out
time of about 50 ms is waited after current = 0 or auxiliary contact = off resp.

Check-back
When the motor is started the check-back status is expected within 100 ms, otherwise a fault is detected.
Selectable by parameter, motor current or auxiliary contact signal can serve as check-back status.
Notice: ‘Check-back’ = ’Simulation’ is recommended only to be set via Control Panel during commissio-
ning. The control system is onlyallowed to set ‘Auxiliary contacts’ or ‘Motor current’ to guarantee
that the check-back operates correctly after next power-on.

Fault behaviour
All kinds of detected external and internal faults set the internal fault bit. In the following:
 contact DO0 or DO1 for the contactor coil opens,
 the monitoring signal FAULT is sent to the fieldbus,
 the red LED on the UMC22-FBPlights on and
 the FAULT signal on the Control Panel display.
If a motor overload is the cause of the fault signal, the cooling time is started additionally . The cooling
time is a parameter and can be adjusted.
More detailed information are monitored in the diagnosis telegram and on the Control Panel.
All faults must be acknowledged via fieldbus or via Control Panel. In addition the cooling time must be
elapsed to allow to restart the motor with a 0-1 transition of the RUN FORWARD command.
Addressing
The slave address of the UMC22-FieldBusPlug combination is not a parameter but can be set with the
Control Panel or with a separate Addressing Set. Details see general part chapter "Planning and
commissioning, Interfacing to the fieldbus, addressing''.

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-29


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Pole-changing starter 1 (continued)


Important:
Normally the inputs and the internal electronic circuits are supplied locally via the terminals 10 and 11. In
this case the SWITCH must be set to EXT. The connection of distant contacts or sensors requests
urgently this kind of supply.
If only contacts nest to the UMC22-FBP are used - that means the 24 V wiring can be surveyed easily -
the supply via the fieldbus and the FieldBusPlug is possible (SWITCH to INT).
Details see general part chapter ''Planning and commissioning, Wiring an d int ernal 24V / 0V
connections''.

Interface and data overview


Device inputs / outputs

Terminal 13 14 15 16 17 18
Device DI0* DI1 DI2* DI3* DI4* DI5*
Input (aux. cont.) to bus (ext. fault) (local: B1) (local: A) (local: Off)
Terminal 7 8 9
Device DO0* DO1* DO2*
Outputs (cont. K1) (cont. K2) (fault out) all digital inputs are monitored to the bus

Fieldbus telegram: Monitoring signals / Command

Bit No. 7 6 5 4 3 2 1 0
RUN RUN
Monitor LOCAL
WARNING FAULT - - FORWARD OFF REVERSE
Byte 0 CONTROL
(cont. K1) (cont. K2)
Monitor DI5 DI4 DI3 DI2 DI1 DI0
- -
Byte 1 (UMC input) (UMC input) (UMC input) (UMC input) (UMC input) (UMC input)
Monitor
MOTOR CURRENT (% of set current)
Byte 2/3

Command FAULT AUTO RUN RUN


- - - OFF
Byte 0 RESET MODE FORWARD REVERSE
(cont. K1) (cont. K2)
Command DO2*
- - - - - - -
Byte 1 (UMC output)

Fieldbus telegram: Diagnosis

Bit No. 7 6 5 4 3 2 1 0
Fault
Fault Self-test
- input - - - - -
Byte 0 failed
signal*
Commu- Parameter Current Relay 1 Relay 0
Fault Overload Motor
nication out of check-back - check-back check-back
Byte 1 (trip) fault blocked
fault range fault* fault* fault*
Motor Motor Cooling Lock-out
Warning
current high current low - time time - - -
Byte 2
threshold* threshold* running running

Fault Parameter number


Byte 3 (refers to Byte 1, Bit 4)

Details see general part chapter ''Data overview'' * depending on parameterization

Appendix A-30 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix A

Pole-changing starter 1 (continued)


Timing diagram 1: Change speed

RUN FORWARD RUN REVERSE


K1 K2a/b
RUN FORWARD
(conta. K1)
Command
(received telegram)
RUN REVERSE
(conta. K2a/b)

DO0 (conta. K1)


UMC outputs
DO1 (conta. K2a/b)

Check-back Mot.cur. / Aux.cont.


RUN FORWARD
(conta. K1)
RUN REVERSE
(conta. K2a/b)
Monitoring signals
(telegram)
OFF

2CDC 342 079 F0003


LOCK-OUT TIME ca. 50 ms

LEDs yellow LED (Mot. on)

Fig. A-20: UMC22-FBP: Control function 'Pol-changing starter 1' - Timing diagram 'change speed'

Abbreviations:
Mot.cur. = Motor current
Aux.cont. = Auxiliary contact
Mot. on = Motor on
conta. = contactor
Remark:
Restart with the same speed without delay.

FieldBusPlug / Issue: 10.2003 UMC22-FBP Apendix A-31


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix A V6

Pole-changing starter 1 (continued)


Timing diagram 2: Overload

FAULT RESET end of


Over- via fieldbus or cooling
RUN load Control Panel RUN time RUN

RUN K1 or K2a/b
Command
(received telegram) OFF

FAULT RESET

UMC internal FAULT

UMC outputs DO0 (then DO1)

Check-back Mot.cur. / Aux.cont.

RUN K1 or K2a/b

OFF

Monitoring signals
(telegram) WARNING Cooling time

FAULT

DI0 (Auxiliary contact)

Cooling time running


Diagnosis
Overload (trip) fault

yellow LED (Mot. on) 2CDC 342 080 F0003


LEDs
red LED (Fault LED)

Fig. A-21: UMC22-FBP: Control function 'Pole-changing starter 1' - Timing diagram 'Overload'

Abbreviations:
Mot.cur. = Motor current
Aux.cont. = Auxiliary contact
Mot. on = Motor on

Appendix A-32 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix B

Appendix B: Control Panel


Overview and menu

LOC mAVs
REM kHz%
FAULT Cprm
OUTPUT PAR SET MENU FWD REV

MENU

LOC REM

ENTER

Fig. B-1: UMC22-FBP: Control Panel ACS-100 PAN 2CDC 342 092 F0003

Contents Page

Control Panel ........................................................................................................................................... B-1


Overview ............................................................................................................................................. B-2
Menu ................................................................................................................................................... B-3
Monitoring .................................................................................................................................... B-3
Edit 1 ............................................................................................................................................ B-6
Edit 2 ............................................................................................................................................ B-8

FieldBusPlug / Issue: 10.2003 UMC22-FBP B-1


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix B V6

Control Panel Overview


The Control Panel ACS100-PAN offers the selection of a limited set of functions in 3 levels:

ENTER Go to higher menu level or change/save value


LOC mAVs
REM kHz% PAR or LOC Control Panel in Edit 1 or 2
FAULT Cprm
SET Edit 1 or 2: Ready to change the value
OUTPUT PAR SET MENU FWD REV
Go to lower menu level (unconditional / without saving value)
2CDC 342 093 F0003

MENU
Remark: Return to menu point 'Show address' (1.1) after
MENU 5 min if no button is pressed.
2CDC 342 092 F0003

LOC REM Go to next or previous menu point, toggle round, even


"reverse" from the first straight to the last menu point
ENTER

Attention: Changed parameters are displayed immediately but executed after power on
or motor off, see general part chapters ''Data overview, Paramaters ...''.

Edit 1:
Change Edit 2:
parameters that Change
S are mainly used
Monitoring: parameters that
t during operation apply mainly for
e. g. Slave
a address, status e. g. Set current the wiring e.g.
r of digital I/O, Control function,
actual current. MENU MENU Check-back.
t

Password
MENU not 0000
ENTER ENTER
Change
Show password (new)
address ENTER
Local control

Change Control
address function
if password is
Digital input, 0000 (default) Change Set Local control
digital output current 1 via digit. inputs

Acutal current Change Set Check-back


current 2
Show
Trip class Fault input
Set current 1
Show Reversing lock-
Fault output
Set current 2 out time
Star-delta
Fault message Star-delta changeover
starting time mode
Version Cooling time Bus connection

Operating Operating Parameter


hours hours transfer
2CDC 342 094 F0003

Number of Number of Reset to


starts starts default
Automatic fault
Number of trips Number of trips reset

B-2 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix B

Control Panel Menu


Monitoring  Some changed parameters are taken over after motor off, others during power-on.
 Some control systems or fieldbuses overwrite the parameters during power-on of the
UMC22-FBP. In this case the Control Panel seems to be but is not ineffective.

Para. Menu Parameter Display De- Range Description / remark take-


No. No. Menu point name 7-segm. PAR others fault over
after

0701 1.1 Show address depending Actual slave address


no on bus Invalid / no address
- 1.2 Digital input / output
- 1.2.0 DI0 Example: 0 signal at digital input DI0
- : DI1...DI5...DO0..DO1 : :
- 1.2.8 DO 2 Example: 1 signal at digi. output DO2
- 1.2.9 Status DI, DO - Left place of the display: ‘d’ for
digital I/O status
- Upper vertical lines of the 2 right
places: Signal status of the 3 digital
outputs, from DO0 (right) to DO2
(left). Line visible = 1.
- Lower vertical lines of the 3 right
places: Signal status of the 6
digital inputs, from DI0 (right) to DI5
(left). Line visible = 1.
- Horizontal lines: Shall help to find
I/O number.
Example shown left:
DO-No. : 0 1 2
DO-Status : 1 0 1
DI-Status : 1 1 1 0 1 0
DI-No. : 0 1 2 3 4 5
- 1.3 Actual current Highest current of 1 of the 3 phases
- 1.3.1 show % 0 - 640% Actual current in % of set current,
release over the bus 1/32 = 3.125 %
0301 1.4 Show Set current 1 Important: The UMC22-FBP
measures the currents of the lines in
the bushing holes. The currents of
the incoming lines can be different
depending on the circuitry.
Details see general part chapter
"Planning and commissioning, Motor
current = Set current versus wiring".
0301 1.4.1 show A 0.24 - 2 places before the decimal point
63 A
0302 1.5 Show Set current 2 Set current of winding 2 of 2-speed-
motors.
0302 1.5.1 show A 0.24 - 2 places before the decimal point
63 A
- 1.6 Fault messages FAULT  FAULT blinks if fault exists.
blinks  With [ENTER] the first of the exis-
if fault ting faults is shown, with [Cursor] to
other existing faults.
 Shown if no fault exists.

FieldBusPlug / Issue: 10.2003 UMC22-FBP B-3


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix B V6

Control Panel Menu


Monitoring  Some changed parameters are taken over after motor off, others during power-on.
(continued)  Some control systems or fieldbuses overwrite the parameters during power-on of the
UMC22-FBP. In this case the Control Panel seems to be but is not ineffective.

Para. Menu Parameter Display De- Range Description / remark take-


No. No. Menu point name 7-segm. PAR others fault over
after

- 1.6.1 Overload fault FAULT Overload or phase loss has lead to -


blinks trip. Cooling time has started.
Acknowledge is possible when
cooling time has elapsed.
Restart of motor needs:
- Acknowledge and
- 0-1 transition of RUN FORWARD/
RUN REVERSE
Remark: Blocking causes also
overload fault. In this case cooling
time is not started.
- 1.6.1.1 Acknowledge To acknowledge the overload fault:
[ENTER].
Remark: Procedure is similar for all
other faults.
- 1.6.2 Motor blocked FAULT Blocking current limit is exeeded
blinks
- 1.6.3 Communication fault FAULT No connection to control system
blinks (any fault or interruption of FieldBus-
Plug, fieldbus, PLC...).
 When the communication is correct
again after fault, the motor can be
started immediately without fault
acknowledge.
 Communication fault also can

appear when the addresses in the


FieldBusPlug and the UMC22-FBP
are different.
Details see general part chapter
"Planning and commissioning, inter-
facing to the fieldbus, addressing".
- 1.6.4 Parameter out of range FAULT Entered parameter value exeeds low
blinks or high limit.
- 1.6.5 Current check-back fault FAULT  Motor current does not flow latest
blinks 100 ms after switching on or
 does not go to 0 latest 100 ms after

switching off.
- 1.6.6 Relay 2 check-back fault FAULT  Signal on DI2 does not appear la-
blinks taest 100 ms after switching on or
 does not disappear latest 100 ms

after switching off.


- 1.6.7 Relay 1 check-back fault FAULT  Signal on DI1 does not appear la-
blinks taest 100 ms after switching on or
 does not disappear latest 100 ms

after switching off.


- 1.6.8 Relay 0 check-back fault FAULT  Signal on DI0 does not appear la-
blinks taest 100 ms after switching on or
 does not disappear latest 100 ms

after switching off.

B-4 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix B

Control Panel Menu


Monitoring  Some changed parameters are taken over after motor off, others during power-on.
(continued)  Some control systems or fieldbuses overwrite the parameters during power-on of the
UMC22-FBP. In this case the Control Panel seems to be but is not ineffective.

Para. Menu Parameter Display De- Range Description / remark take-


No. No. Menu point name 7-segm. PAR others fault over
after

- 1.6.10 Self-test failed FAULT Self-test failed, e. g. CRC check not


blinks ok.
- 1.6.11 Fault input = 0 FAULT Closed circuit at DI2 interrupted
blinks (supposed DI2 is parametrized as
'Fault input')
- 1.7 Version Firmware-version of UMC22
0601 1.8 Operating hours
0601 1.8.1 0 0- All hours are counted but the unit
.
99 999 place is not displayed on the Control
Panel. The displayed range 00.00 -
99.99 corresponds with real 00.000
to 99.999 hours.
0602 1.9 Number of starts
0602 1.9.1 0 0- All starts are counted but the three
. .
1 000 000 lower places are not displayed on the
Control Panel. The displayed range
0000-1000 corresponds with real
0.000.0000 to 1.000.000 starts
0603 1.10 Number of trips
0603 1.10.1 0 0 - 255 Displays 0000 - 0255 trips
- 1.11 Edit 1 Go to local control, parameters
to 2.1 for motor protection, times and
others with [ENTER].

FieldBusPlug / Issue: 10.2003 UMC22-FBP B-5


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix B V6

Control Panel Menu


Edit 1  Some changed parameters are taken over after motor off, others during power-on.
 Some control systems or fieldbuses overwrite the parameters during power-on of the
UMC22-FBP. In this case the Control Panel seems to be but is not ineffective.

Para. Menu Parameter Display De- Range Description / remark take-


No. No. Menu point name 7-segm. PAR others fault over
after

- 2.1 Password PAR Skipped to 2.2 if the password imme-


(default 0000) is not changed. dia-
tely
- 2.1.1 * * * * (enter password) PAR SET 0 0001-  At any time back with [MENU]
9999 without saving.
 0000 is default and does not act as

password.
 First position flashes, change with

[Cursor], press [ENTER], ....., 4th


number flashes, change with
[Cursor], after position 4 (4!) save
with [ENTER].
- 2.2 Local control  Local control is always possible. If
entered, RUN commands from the
control station are ignored.
 Entering and leaving local control

does not influence the actual status


of the outputs.
 Local control is left immediately

when Control Panel is removed.


- 2.2.1 LOC,  Entering and leaving this menu
select direction SET, point does not influence the actual
FWD status of the outputs.
or  Off is always possible and domi-

REV nating via control system, Control


switch on and off Panel and, if parameterized, via
addi- digital input DI0.
tional  Toggle On/Off of relay outputs, On

if incl. start procedure and check-


motor back.
is on:  Reversig starter:
OUT- Selection of the other direction is
PUT, possible if
cur- - motor is stopped via button AND
rent - reversing lock-out time has
% elapsed.
 Pole-changing starter:
switch over to the other speed is
executed immediately (changeover
time ca. 100 ms).
Display: Speed 1 = FWD
Speed 2 = REV.
0701 2.3 Change address PAR -
0701 2.3.1 show / change PAR SET A000 depen-  Entered address: here 23
ding on  no address set
bus to  Entering 999 results in 'A---'

no address

B-6 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix B

Control Panel Menu


Edit 1  Some changed parameters are taken over after motor off, others during power-on.
(continued)  Some control systems or fieldbuses overwrite the parameters during power-on of the
UMC22-FBP. In this case the Control Panel seems to be but is not ineffective.

Para. Menu Parameter Display De- Range Description / remark take-


No. No. Menu point name 7-segm. PAR others fault over
after

0301 2.4 Change set current 1 PAR Important: The UMC22-FBP motor
measures the currents of the lines in off
the bushing holes. The currents of
the incoming lines can be different
depending on the circuitry.
0301 2.4.1 show / change PAR SET, 1A 0.24 - 2 places befor the decimal point
A 63 A
0302 2.5 Change set current 2 PAR Set current of winding 2 changing motor
starters. off
0302 2.5.1 show / change PAR SET, 1A 0.24 - 2 places befor the decimal point
A 63 A
0401 2.6 Trip class PAR Overload check (thermal motor motor
image) off
0401 2.6.1 Trip class 5 PAR SET
0401 2.6.2 Trip class 10 PAR SET 10
0401 2.6.3 Trip class 20 PAR SET
0401 2.6.4 Trip class 30 PAR SET
0205 2.7 Reversing lock-out time PAR  Only for reversing starter! motor
 Starts with OFF (OFF is necessarry off
between RUN FORWARD and RUN
REVERSE)
 RUN command in other direction is

only accepted when reversing lock-


out time has elapsed.
0205 2.7.1 show / change PAR SET, 2s 0- Show and change reversing lock-out
s 3600 s time in steps of 1s
0207 2.8 Star-delta starting time PAR PAR  Only for Star-delta starter! Starts motor
running with the RUN command. off
0207 2.8.1 show / change PAR SET, 60 s 0- Show / change star-delta starting
s 3600 s time in steps of 1s
0403 2.9 Cooling time PAR PAR motor
0403 2.9.1 show / change PAR SET, 120 s 0- Show / change cooling time in steps off
s 3600 s of 1s
0601 2.10 Operating hours motor
0601 2.10.1 show / change 0 0- All hours are counted but the unit off
99.999 place is not displayed on the Control
Panel.
0602 2.11 Number of starts motor
0602 2.11.1 show / change 0 0- All starts are counted but the three off
1.000.000 lower places are not displayed on the
Control Panel.
0603 2.12 Number of trips motor
0603 2.12.1 show / change 0 0 - 255 Displays 0000 - 0255 trips off
- 2.13 Edit 2 PAR SET Go to next operation level.
to 3.1

FieldBusPlug / Issue: 10.2003 UMC22-FBP B-7


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix B V6

Control Panel Menu


Edit 2  Some changed parameters are taken over after motor off, others during power-on.
 Some control systems or fieldbuses overwrite the parameters during power-on of the
UMC22-FBP. In this case the Control Panel seems to be but is not ineffective.

Para. Menu Parameter Display De- Range Description / remark take-


No. No. Menu point name 7-segm. PAR others fault over
after

- 3.1 Change password PAR


- 3.1.1 show / change PAR SET 0000 0001- Show and change password.
9999
0101 3.2 Control function PAR power
0101 3.2.1 Transparent PAR SET Trans. Direct access to DIs/DOs via fieldbus -on
0101 3.2.2 Overload relay PAR SET Similar to overload relay
0101 3.2.3 Direct starter PAR SET Direct starter with check-back
0101 3.2.4 Reversing starter PAR SET Reversing start with check-back
0101 3.2.5 Star-delta starter 1 PAR SET Star-delta starter start via 2 DOs, with
check-back
0101 3.2.6 Pole-changing starter 1 PAR SET Pole-changing starter with check-
back type 1
0201 3.3 Local control via digital PAR motor
inputs on
0201 3.3.0 No operation via inputs PAR SET no Inputs DI3 - DI5 are not used for
oper. local control
0201 3.3.1 Operation via inputs PAR SET Digital inputs prepared to control
RUN/ STOP locally.
Remark: Local control ist possible
when
 control system sends command

AUTO MODE = 0 or
 communication to control system is

interrupted.
0202 3.4. Check-back PAR motor
0202 3.4.0 Auxiliary contacts PAR SET OK when auxiliary contacts are on
closed 100 ms after start.
0202 3.4.1 Motor current PAR SET curr. OK when current is flowing 100 ms
after start
0202 3.4.2 Simulation PAR SET Simulated check-back (e.g. to be set
to operation without motor).
Remark: Normally overwritten by the
control system during power-on.
Details see general part chapters
"Data overview, Parameters ...".
0203 3.5 Fault input PAR Digital input DI2 to for external fault motor
signal, closed-circuit on
0203 3.5.0 Off PAR SET Off Off: Digital input free available.
0203 3.5.1 On PAR SET On: Signal 1 on DI2 is requested.
If DI2 = 0 internal fault signal is set.
0204 3.6 Fault output PAR Digital output DO2 used to monitor motor
fault signal on
0204 3.6.0 Off PAR SET Off Off: Digital output free available.
0204 3.6.1 On PAR SET On: Digital output DO2 monitors
fault signal.

B-8 UMC22-FBP FieldBusPlug / Issue: 10.2003


Universal Motor Controller
UMC22-FBP
V6 Technical Description - Appendix B

Control Panel Menu


Edit 2  Some changed parameters are taken over after motor off, others during power-on.
(continued)  Some control systems or fieldbuses overwrite the parameters during power-on of the
UMC22-FBP. In this case the Control Panel seems to be but is not ineffective.

Para. Menu Parameter Display De- Range Description / remark take-


No. No. Menu point name 7-segm. PAR others fault over
after

0206 3.9 Star-delta changeover PAR  Only needed for star-delta starter! motor
mode on
0206 3.9.1 Time PAR SET Change from star  delta when star-
delta starting time is over
0206 3.9.2 Current PAR SET curr. Change from star  delta when
motor current = 0,9 x set current
Remark: Must switch to delta before
star-delta starting time has elapsed
otherwise current check-back fault.
0702 3.10 Bus connection PAR power
0702 3.10.0 Stand-alone PAR SET Stand-alone / without bus communi- on
cation, via digital inputs and Control
Panel.
0702 3.10.1 Bus connection PAR SET bus Operation with bus communication.
con.
- 3.11 Parameter transfer PAR Control Panel can read and write the power
complete parameter set from / to on
UMC22-FBP except fieldbus slave
address.
- 3.11.0 Read parameters PAR SET Control Panel reads the actual
parameters from the UMC22-FBP
with [ENTER].
- 3.11.1 Set parameters PAR SET Control Panel overwirtes the actual
parameters in the UMC22-FBP with
[ENTER].
- 3.12 Reset to Default PAR power
- 3.12.1 Execute PAR SET Go back to default values with on
[ENTER].
Fieldbus slave address, Operating
hours, Number of starts and Number
of trips are not changed.
0404 3.13 Automatic fault reset PAR Automatic fault reset (On) is only imme-
possible with the control function diately
overload relay.
0404 3.13.0 not resetted automatically PAR SET not Fault has to be resetted via Control
reset Panel or via fieldbus.
0404 3.13.1 Automatic reset PAR SET Automatic reset of fault when fault
condition is off and cooling time has
elapsed. Fault is not monitored.

FieldBusPlug / Issue: 10.2003 UMC22-FBP B-9


Universal Motor Controller
UMC22-FBP
Technical Description - Appendix B V6

B-10 UMC22-FBP FieldBusPlug / Issue: 10.2003


Manual No.: 2CDC 135 001 D 0204

ABB STOTZ-KONTAKT GmbH


Eppelheimer Straße 82 Postfach 101680
69123 Heidelberg 69006 Heidelberg
Germany Germany

Telephone +49 6221 701-0


Telefax +49 6221 701-240
E-Mail desst.helpline@de.abb.com
Internet http://www.abb.de/stotz-kontakt

Potrebbero piacerti anche