Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
V6
tion
e nta 3 Universal Motor Controller
cum ion UMC22-FBP
Do Vers
Contents Page
Features ....................................................................................................................................................... 5
Maintenance .............................................................................................................................................. 23
Replacement of an UMC22-FBP in an operating installation ............................................................. 23
Replacement of the controller unit only ............................................................................................... 23
Features
Overview
- The Universal Motor Controller UMC22-FBP provides high-grade motor protection and control for the
current range 0.24 up to 63 A with one type.
For higher currents additional protection current transformers (class 5P10) can be used.
- With the integrated FieldBusPlug interface the UMC22-FBP can be connected to different fieldbuses
using the appropriate type of FieldBusPlug.
- 6 digital inputs and 3 relay outputs offer to realize a wide range of predefined control functions and
applications such as direct starter and star-delta starter including local operation via digital inputs
and others as selected by parameters.
- Depending on the parameterization, the status of the digital inputs and outputs, the actual current,
detailed diagnosis information and all parameters are accessible via the fieldbus (supposed the
fieldbus offers the appropiate features).
- LEDs on the UMC22-FBP monitor 'Ready', 'Motor On' or 'Fault'.
- Additional Control Panel ACS100-PAN (separate delivery) offers similar access to all important
information. The Control Panel is necessary to set the fieldbus slave address and can be snapped in
on the front of the UMC22-FBP.
- Also, the overload protection behaviour and other functions can be changed by parameters in a wide
range. More details see chapters "Data overview, Parameters ...".
- The control function Overload relay is dedicated to use the UMC22-FBP similar to an overload relay
with and without fieldbus connection. The other control functions can be used stand-alone, too.
Construction
- The UMC22-FBP consists of two separate parts: Current transformer set and controller unit,
mounted as one device.
- Mounting on DIN rail or with screws. W x H x D = 70 x 105 x 110 mm. Degree of protection IP20.
- Current-carrying motor lines are lead through the current transformer set.
- Replacement of the controller unit without removing the current-carrying motor lines.
- Parameters are stored in the current transformer set even if power down happens. This allows to
replace the controller unit without reparameterization.
Overload protection
- Measuring the motor current (value is also provided to be sent to the fieldbus)
- Electronic overload protection for nominal currents of 0.24 A to 63 A (whole range with onIy one type
of device). Set currents selectable with parameter via fieldbus or Control Panel.
- Trip classes 5, 10, 20 and 30 (selectable with parameter)
- Phase-loss protection
- Short circuit protection of the motor lines by external fuses on the line side.
Other features
- With parameter it can be selected between 'Relays off' or 'Relays retain status' in case of control
system or fieldbus failure.
- Diagnostic information available via LEDs, fieldbus and Control Panel.
- Preventive diagnosis functions (e.g. number of starts)
- Function blocks or similar software tools to be implemented into the program of the control system
Device construction
Overview
UMC22-FBP:
current transformer set
UMC22-FBP:
controller unit
label
Control Panel
ACS100-PAN:
(optional)
complete
device
4
FieldBusPlug
2CDC 342 013 F0003
mounting by 4 screws M4
ENTER
With the parameter 'Control function' = 3 ('Direct starter') Free outputs, commands
the relay output DO0 is used to control the main contactor direct from fieldbus
K1
K1
5 6 7 8 9
DO DO DO DO DO
C C 0 1 2
UMC22
EXT
INT
0V
FieldBus SWITCH
24 V
Plug
max.
70 mA
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18
K1
2CDC 342 060 F0003
24 V 24 V
0V 0V
Important:
Normally the inputs and the internal electronic circuits are supplied locally via the terminals 10 and 11. In
this case the SWITCH must be set to EXT. The connection of distant contacts or sensors requests
urgently this kind of supply.
If only contacts nest to the UMC22-FBP are used - that means the 24 V wiring can be surveyed easily -
the supply via the fieldbus and the FieldBusPlug is possible (SWITCH to INT).
Spark suppression
Spark suppression is always necessary to avoid early failure of the relay contacts.
5 6 7 8 9
DO DO DO DO DO
C C 0 1 2
UMC22
EXT
INT
0V
SWITCH
24 V
max.
70 mA
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18
K1
0 V 24 V 24 V
if EXT supply output
2CDC 342 061 F0003
For check-back the auxiliary contact of the main contactor has to be used!
Fig. 5: UMC22-FBP: Connecting contactors with peak current > 0.5 A: Types A45 and larger
Remark:
Slide switch on the left
side to position "PLC" (up)
1 K1
ON
2 OFF-N
3 COM
5 6 7 8 9
DO DO DO DO DO
C C 0 1 2
UMC22
2CDC 342 062 F0003
Fig. 6: UMC22-FBP: Connecting larger contactors with electronic interface (AF 145 and larger)
U1 V1 W1 U1 V1 W1 U1 V1 W1
W2 U2 V2 W2 U2 V2 W2 U2 V2
U1 V1 W1 U1 V1 W1 U1 V1 W1
W2 U2 V2 W2 U2 V2 W2 U2 V2
2CDC 342 063 F0003
The Delta 冑 3 circuitry is normally used for larger motors to reduce the current transformer size. The
parameter 'Set current' is the nominal motor current devided by 冑 3.
Type / Current range Recom- Second. Hole Cables Link kit (bar) type*
Star, mended current area (E/EN for contactor
Delta 1 range range WxH 60204) (order code see
[A] [A] [A] [mm] [mm2] "Technical data")
UMC22-FBP without 0.24 ... 63 0.24 ... 63 - 11 쏗 max. 252 -
current transformer **
KORC 4L185 46 ... 185 60 ... 185 1.3 ... 4 22 x 28 1 x 702 DT450 / A185
AF145 - AF185
KORC 4L310 80 ... 310 180 ... 310 2.3 ... 4 22 x 28 2 x 702 DT450 / A300
AF260 - AF300
KORC 5L500 125 ... 500 300 ... 500 2.4 ... 4 41 x 22 3 x 702 DT500 / AF460S*
AF400 - AF460
KORC 5L850 213 ... 850 500 ... 850 2.4 ... 4 41 x 22 - DT500 / AF750S*
AF580 - AF750
* Link kits for Star-delta starter. (Others see catalogue.)
** max. cable diameter with insulation 11 mm
Remark:
For Delta 冑 3 circuitry - normally used for larger motors - the parameter 'Set current' is the nominal motor
current devided by 冑 3, see preceeding chapter.
An other way to adjust the address in the FieldBusPlug is to use the "Addressing Set" CAS21-FBP.0
(Interface unit + PC with addressing SW). See technical description 2CDC 190 012 D02--.
Address of UMC22-FBP:
Address of the FieldBusPlug:
- Communication fault (F003) is set.
- With the Control Panel the menu 2.3 'Change address' has to be selected and the desired
address must be adjusted. Details see Appendix B "Control Panel".
- After leaving this menu operation and communication starts immediately. Both the FieldBusPlug
and the UMC22-FBP store the adjusted address.
Remark: If the adjusted FieldBusPlug address is not configured in the fieldbus master the
communication does not start and the red LED on the FieldBusPlug displays fault.
Example
UMC22-FBP connected to an ABB CPU type 07 KT 97 via PROFIBUS DP
Hardware-Configuration
R.....
07 KT 97-DPM (DP-Master)
place pointer, click right mouse key twice
Hardware-Configuration
07 KT 97-DPM [DP-Master]
ABB FBP 2003-03-13 [DP-Slave]
(S-2) x 2
coupler slot 1 x2
PROFIBUS DP (/V0)
LAN
Write parameters with
GSD file during power-on.
Read not possible. Configuration file:
CPU coupler ABB_078F.GSD
--> Master Class 1
PROFIBUS DP/V1
fieldbus Write and read parameters
whenever desired.
--> Master Class 2
DeviceNet:
Write and read parameters
whenever desired. Configuration file:
ABB_UMC22-FBP-ESD
2CDC 342 065 F0003
Example continued
Configuring the UMC22-FBP as slave connected to the 07 KT 97 via PROFIBUS DP
- Select <Properties> on table <Input/Output> when UMC22-FBP is present in the column right
Now the parameters can be changed (left then right mouse key).
Motor control:
In an operating installation, the motor contactors are switched On and Off normally by the control system
with the commands RUN FORWARD, RUN REVERSE and OFF.
Switching On (Run) and Off is possible when the UMC22-FBP is parameterized with one of the motor
controlling Control functions e.g. 'Direct starter, 'Star-delta starter' etc. The exceptions are 'Transparent'
and 'Overload relay'. Switching On (Run) and Off can be done:
via control system via Control Panel via digital inputs
always possible
control system
if menu
'Local control' OFF
is activated*
Control Panel
if parameter
'Local control via
digital inputs' = 'On'
digital inputs
dominating
connection to
control station
interrupted
* AUTO MODE = 1: UMC22-FBP ignores RUN from digital inputs, monitors LOCAL CONTROL = 0,
AUTO MODE = 0: UMC22-FBP ignores RUN from control station, monitors LOCAL CONTROL = 1.
** When local control is entered the UMC22-FBP monitors LOCAL CONTROL to the control system.
local control is immediately stopped when Control Panel is removed or menu 'Local control' is left.
The status of the outputs is not changed when entering or leaving local control.
Monitoring,
S e.g..
t - address
a - I/O-signals Edit 1
r - Current e.g.
t - fault incl.. - password
acknowledge check
- ... - local control Edit 2
- address e.g.
adjust - password
- current change
- trip class - control function
- ... e.g. Y- ,
- fault input
mAVs - behaviour if
LOC
bus fails
REM kHz%
FAULT Cprm
- ...
OUTPUT PAR SET MENU FWD REV
MENU
MENU
ENTER
LOC REM
Remarks:
Most of the changed parameters are taken over after motor off.
Some parameters are taken over during power-on.
Remark: Some control systems overwrite the parameters on principle during power-on. This can lead
to the opinion that the parameterizing via Control Panel is not effective.
Maintenance
Replacement of an UMC22-FBP in an operating installation
The UMC22-FBP can be disconnected from the FieldBusPlug without disturbing the fieldbus and the
other slaves. The FieldBusPlug is supplied via the voltage conducted together with the bus lines.
The FieldBusPlug keeps stored the actual slave address and informs the control system that the
connected device is lost.
After mounting and connecting a new UMC22-FBP, the control system will be informed that the missing
slave is complete again (supposed that the new UMC22-FBP contains an invalid address A - - -).
This allows the control system to download the former parameters and to start up the new UMC22-FBP
again with correct parameters.
current
transformer
unit
* In addition the parameters can be stored also in the control system and downloaded after power-on.
Data overview
Device inputs and outputs
The function of the hardware inputs and outputs is fixed by parameterization. Refer parameters Control
function and Attached control functions.
Example (1)
Control function 'Transparent'
All Inputs and outputs are directly connected to the Fieldbus as monitoring signals and commands.
Terminal 13 14 15 16 17 18
Device DI0 DI1 DI2 DI3 DI4 DI5
Input to bus to bus to bus to bus to bus to bus
Terminal 7 8 9
Device DO0 DO1 DO2
Output from bus from bus from bus
Example (2)
Control function 'Direct starter'
One output is used to control the contactor coil. Access via fieldbus is not possible.The other inputs and
outputs are still transparent to the fieldbus
Terminal 13 14 15 16 17 18
Device DI0 DI1 DI2 DI3 DI4 DI5
Input to bus to bus to bus to bus to bus to bus
Terminal 7 8 9
Device Contactor DO1 DO2
Output coil from bus from bus
Example (3)
Control function 'Direct starter' with
Attached control function 'Local control via digital inputs'
Additional inputs are used to allow local control. Details see Appendix B "Control Functions".
Terminal 13 14 15 16 17 18
Local control Local control
Device DI0 DI1 DI2 DI3
Run Fwd. Off
Input to bus to bus to bus to bus
DI4 to bus DI5 to bus
Terminal 7 8 9
Device Contactor DO1 DO2
Output coil from bus from bus
Bit No. 7 6 5 4 3 2 1 0
REVERSING
Monitor LOCAL RUN RUN
WARNING FAULT LOCK-OUT - OFF
Byte 0 CONTROL FORWARD REVERSE*
TIME*
Monitor DI5 DI4 DI3 DI2 DI1 DI0
- -
Byte 1 (UMC input) (UMC input) (UMC input) (UMC input) (UMC input) (UMC input)
Monitor
MOTOR CURRENT (% of Set current)
Byte 2/3
Example
Control function 'Direct starter' with
Attached control function 'Local control via digital inputs'
Bit No. 7 6 5 4 3 2 1 0
*** corresponding UMC22-FBP output is used to control the motor contactor coil
Commands (description)
RUN REVERSE 0-1 transition: Motor starts running reverse
OFF 1: Motor stops as long as this signal is 1. OFF dominates RUN commands.
RUN FORWARD 0-1 transition: Motor starts running forward or with speed 1.
Remark:
To start the opposite direction or the other speed:
OFF command is necessary, starts immediately the reverse lock-out time.When
the reverse lock-out time has elapsed, the motor can be started with the 0-1
transition of the opposite / different RUN command.
AUTO MODE 0: Enables start of the motor (RUN) via digital inputs on the UMC22-FBP,
supposed the parameter 'Local control via digital inputs' is set. UMC22-FBP
ignores RUN command from control station. Off is always possible.
Details see chapter "Planning and commissioning, Switch on / off motor, local
control".
1: Run via digital inputs is blocked. Off is always possible.
FAULT RESET 0-1-transition: Resets all resettable faults (overload fault, check-back fault, etc.)
UMC output DO0...2 Transparent control of UMC22-FBP digital output DO..., if not used by any
Control function different from Transparent.
Bit No. 7 6 5 4 3 2 1 0
Fault
Fault Self-test
- input - - - - -
Byte 0 failed
signal
Commu- Parameter Current Relay 2 Relay 1 Relay 0
Fault Overload Motor
nication out of check-back check-back check-back check-back
Byte 1 (trip) fault blocked*
fault range fault* fault* fault* fault*
Motor Motor Cooling Lock-out
Warning
current high current low - time time - - -
Byte 2
threshold* threshold* running running*
Current setting:
- 'Set current 1',
- 'Set current 2' (two-speed),
Overload protection:
- 'Trip class' (5, 10, 20, 30)
- 'Cooling time' (seconds)
- 'Blocking current threshold', ...
- etc.
Communication:
- 'Communication fault reaction' (reaction on loss of communication to control system)
To load parameters into the UMC22-FBP, different ways are possible depending on the fieldbus
and the control system:
The slave configuration file (e.g. GSD file for PROFIBUS-DP) contains the parameters. The
parameters can be changed during configuration of the fieldbus and are loaded in the UMC22-FBP
during switching on.
The parameterization is done via application program of the control system.
The parameterization can be done with the Control Panel. Details see Appendix B "Control Panel".
As a special feature the Control Panel can be used to read the complete parameter set of a
parameterized UMC22-FBP and to transfer it to another UMC22-FBP, see Appendix B "Control
Panel".
Remark:
Some parameters are taken over with power-on, others during motor off.
Refer to chapters "Data overview, Parameters, Description".
Para. Group Definition / Range Select. De- UMC behaviour: description take-over
No. No. fault after
0207 Star-delta 1 - 3600 s Sd.St 60 s Star-delta starter only! motor off
starting time step 0.1 s Starts running with the RUN command
0300 Current
Settings
0301 Set current 1 0.24...63 A Cur 1 0.5 A Important: The UMC22-FBP measures the motor off
step 10 mA currents of the lines in the bushing holes. The
current ih the coming lines can be different de-
pending on the connection circuit.
More details see chapter "Planning and Com-
missioning, Motor current = Set current
versus wiring"
0302 Set current 2 0.24 - 63 A Cur 2 0.5 A Pole-changing and Dahlander starter only! motor off
step 10 mA Used for overload calculation
0400 Overload
Protection
0401 Trip class triP Overload calculation (thermal motor image) motor off
Trip class 5 5
Trip class 10 10 10
Trip class 20 20
Trip class 30 30
0402 Phase loss Current of one phase: < 40% of other phases motor off
protection (condition: other phases > 70% of set current)
Off 0 Phase loss protection is not activated
On 1 1 Phase loss protection is activated
0403 Cooling time 30 - 3600 s t i .co 120 s Cooling time simulates the cooling behaviour motor off
step 0.1 s of the inoperating motor after switching off.
While cooling time is running RUN is not
accepted and WARNING is monitored.
0404 Automatic ArES motor off
fault reset Off 0 0 Acknowledgment is necessary to reset Fault.
To switch on cooling time must be elapsed.
On 1 Only for overload relay!
Due to safety considerations: Automatic
reset of fault when fault condition is off and
cooling time has elapsed. Fault is not
monitored.
0405 Start-up time 0 - 600 s 120 s Suppresses some signals / trips until motor is motor off
step 0.1 s in normal running status (Blocking, High/ Low
current threshold)
0406 Blocking 0 - 800% x set current 800% Fault signal when current is above threshold motor off
current step 5% for > 1 s and start-up time has elapsed.
threshold (800% means: Blocking protection is inactive).
Remark: Blocking sets the internal fault signal
and the monitoring telegram Bit OVERLOAD
and displays FAULT on the Control Panel but
cooling time is not started.
0407 Low current 30 - 100% x set current 50% Warning when below threshold and start-up motor off
threshold step 5% time has elapsed
0408 High current 100 - 800% x set current 150% Warning when above threshold and start-up motor off
threshold step 5% time has elapsed
Para. Group Definition / Range Select. De- UMC behaviour: description take-over
No. No. fault after
0500 Communication
5001 Communi- bu.co All cases when UMC22-FBP does not receive motor off
cation fault valid telegrams, either when control system or
reaction fieldbus or FieldBusPlug is out of order or
interrupted.
Relays off 0 0 Relay outputs of UMC22-FBP are switched
off
Relays retain status 1 Relay outputs of UMC22-FBP retain status
0502 Address power-on
check Off 0 0 UMC22-FBP address is valid on the fieldbus
On 1 0 If the UMC22-FBP and the FieldBusPlug
contain different addresses, the user must
decide.
Details see chapter "Planning and Commis-
sioning, connection to the fieldbus,
addressing“.
Technical data
Main power lines
Voltage (three-phase systems) max. 690 V AC, 50 or 60 Hz
Conductor holes in the current transformers 11 mm
Set current range for overload protection 0.24 A ... 63 A
Three-phase motors complete overload protection
Phase loss detection: If current of ... one phase: < 40% of other phases
other condition: phases > 70% of set current
Trip classes, selectable by parameter 5, 10, 20, 30
Tripping diagram
cold Class 30
minutes
Class 20
Trip time
| seconds
warm
Digital Inputs
Number of digital inputs 6 (DI0 ... DI5)
Supply for digital inputs (terminal 12) Internal or external
(see chapter ''Planning and commissioning, Wiring
and internal 24 V / 0 V connections'')
Supply output current for inputs (terminal 12) max. 70 mA
Voltage when standard contacts are used min.18 V
Isolation no (see chapter ''Planning and commissioning,
Wiring and internal 24 V / 0 V connections'')
Input signal bounce suppression typ. 4 ms
1-Signal range including ripple -31.2 V ... +5 V
0-Signal range including ripple +13 V ... +31.2 V
Input current per channel (24 V DC) typ. 6.0 mA
Input resistor to 0V 3.9 k⏲
Line length unshielded max. 600 m
Line length shielded max. 1000 m
Conductor size (solide or stranded) 0.2-1.5 mm2 / AWG 15-24
Tightening torque 0.4 Nm
Digital 0utputs
Number of digital outputs 3 (DO0 ... DO2)
Type of digital outputs Relay contacts
Grouping of contacts 3 contacts with 1 common
Voltage range of contacts 12 ... 250 V AC
Lowest switched power for correct signals 1 W or 1 VA
FieldBusPlug connection
Mounting Plug connection, fastening with supplied screw
Tightening torque of the fixing screw 0.8 Nm + rotation 90 degree
Suitable ABB FieldBusPlug types PDP22-FBP (PROFIBUS-DP)
DNP22-FBP (DeviceNet)
MRP21-FBP (MODBUS) in preparation
COP21-FBP (CANopen) in preparation
Control Panel
Control Panel ACS100-PAN Order code: 1SAJ 510 001 R0001
(not in scope of delivery, to order separately)
Control Panel Extension Cable ACS100-CAB Order code: 1SAJ 510 002 R0001
(not in scope of delivery, to order separately)
FieldBusPlugs
PDP22-FBP (PROFIBUS DP)
Cable length: 0.25 m Order code: 1SAJ 240 000 R0003
Cable length: 0.50 m Order code: 1SAJ 240 000 R0005
Cable length: 1.00 m Order code: 1SAJ 240 000 R0010
Cable length: 2.00 m Order code: 1SAJ 240 000 R0020
Cable length: 5.00 m Order code: 1SAJ 240 000 R0050
DNP22-FBP (DeviceNet)
Cable length: 0.25 m Order code: 1SAJ 230 000 R0003
Cable length: 0.50 m Order code: 1SAJ 230 000 R0005
Cable length: 1.00 m Order code: 1SAJ 230 000 R0010
Cable length: 5.00 m Order code: 1SAJ 230 000 R0050
MRP-21-FBP (MODBUS) in preparation
COP21-FBP (CANopen) in preparation
K1
K1
5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT
Plug
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18
Contents Page
Transparent
The UMC22-FBP parameterized with the 'Control function' = 'Transparent' (default) behaves like an I/O-
module with an integrated overload check. The outputs DO0 ... DO2 and the inputs DI0 ... DI5 are
directly connected to the fieldbus and are independent of the overload status.
The only possible exception: DO2 outputs the internal fault signal, if the parameter 'Fault output' is set to
'On'. Default is 'Off', in this case the output is controlled directly via the fieldbus.
All kinds of faults set the internal fault bit. Following the monitoring signal FAULT is sent to the fieldbus,
the red LED lights on and the FAULT signal on the Control Panel flashes.
If a motor overload is the cause of the fault signal, the cooling time is started additionally. The cooling
time is a parameter and can be adjusted.
More detailed information are monitored in the diagnosis telegram and on the Control Panel.
All faults must be acknowledged via fieldbus or via Control Panel.
The slave address of the UMC22-FieldBusPlug combination is not a parameter but can be set with the
Control Panel or with a separate Addressing Set. Details see general part chapter ''Planning and
commissioning, Interfacing to the fieldbus, addressing''.
Fault
5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT
Plug
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18
Transparent (continued)
Important:
Normally the inputs and the internal electronic circuits are supplied locally via the terminals 10 and 11. In
this case the SWITCH must be set to EXT. The connection of distant contacts or sensors requests
urgently this kind of supply.
If only contacts nest to the UMC22-FBP are used - that means the 24 V wiring can be surveyed easily -
the supply via the fieldbus and the FieldBusPlug is possible (SWITCH to INT).
Details see general part chapter ''Planning and commissioning, Wiring and internal 24 V / 0 V
connections''.
Terminal 13 14 15 16 17 18
Device DI0 DI1 DI2 DI3 DI4 DI5
Input to bus to bus to bus to bus to bus to bus
Terminal 7 8 9
Device DO0 DO1 DO2*
Outputs from bus from bus (fault output)
Bit No. 7 6 5 4 3 2 1 0
Monitor
WARNING FAULT - - - - - -
Byte 0
Command FAULT
- - - - - - -
Byte 0 RESET
Command DO2* DO1 DO0
- - - - -
Byte 1 (UMC output) (UMC output) (UMC output)
Bit No. 7 6 5 4 3 2 1 0
Fault Self-test
- - - - - - -
Byte 0 failed
Commu- Parameter
Fault Overload Motor
nication out of - - - -
Byte 1 (trip) fault blocked*
fault range
Motor Motor Cooling
Warning
current high current low - time - - - -
Byte 2
threshold* threshold* running
Overload relay
The UMC22-FBP parameterized with the 'Control function' = 'Overload relay' provides excellent
protection of a motor. Dedicated to replace a standard overload relay, stand-alone operation can be
selected via Control Panel setting the parameter 'Bus connection' = 'Off'.
Fault
K1
K1
ON
OFF
5 6 7 8 9
SWITCH
UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT
Plug
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18
Important:
When connected to a fieldbus via FieldBusPlug:
Normally the inputs and the internal electronic circuits are supplied locally via the terminals 10 and 11. In
this case the SWITCH must be set to EXT. The connection of distant contacts or sensors requests
urgently this kind of supply.
If only contacts nest to the UMC22-FBP are used - that means the 24 V wiring can be surveyed easily -
the supply via the fieldbus and the FieldBusPlug is possible (SWITCH to INT).
Details see general part chapter ''Planning and commissioning, Wiring and internal 24 V / 0 V
connections''.
Terminal 13 14 15 16 17 18
Device DI0 DI1 DI2 DI3 DI4 DI5
Input to bus to bus to bus to bus to bus to bus
Terminal 7 8 9
Device trip DO2*
trip
Outputs inverted from bus
Bit No. 7 6 5 4 3 2 1 0
Monitor
WARNING FAULT - - - - - -
Byte 0
Bit No. 7 6 5 4 3 2 1 0
Fault Self-test
- - - - - - -
Byte 0 failed
Commu- Parameter
Fault Overload Motor
nication out of - - - -
Byte 1 (trip) fault blocked*
fault range
Motor Motor Cooling
Warning
current high current low - time - - - -
Byte 2
threshold* threshold* running
Command
(received telegram)
FAULT RESET
(/trip) DO0
UMC outputs
(trip) DO1
Fig. A-4: UMC22-FBP: Control function 'Overload relay' - Timing diagram 'Overload'
Direct starter
The UMC22-FBP parameterized with the 'Control function' = 'Direct starter' provides excellent protection
and control of a motor for one direction of rotation. The connection to a fieldbus is made via the appropri-
ate type of the FieldBusPlug.
K1
K1
5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT
Plug
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18
supply inputs
Fault
K1
K1
5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT
Plug
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18
thermistor
K1 switch 1)
2CDC 342 085 F0003
1)
Fault input: Closed circuit signal: 1 = no fault
2)
Fwd: Momentary-contact switch
3)
Off: Closed circuit signal: 0 = dominating Off
Check-back
When the motor is started, the check-back status is expected within 100 ms, otherwise a fault is de-
tected. Selectable by parameter, motor current or auxiliary contact signal can serve as check-back
status.
Notice: 'Check-back' = 'Simulation' is recommended only to be set via Control Panel during commissio-
ning. The control system is only allowed to set 'Auxiliary contacts' or 'Motor current' to guarantee
that the check-back operates correctly after next power-on.
Fault behaviour
All kinds of detected external and internal faults set the internal fault bit. In the following:
contact DO0 for the contactor coil opens,
the monitoring signal FAULT is sent to the fieldbus,
the red LED on the UMC22-FBP lights on and
the FAULT signal on the Control Panel display flashes.
If a motor overload is the cause of the fault signal, the cooling time is started additionally . The cooling
time is a parameter and can be adjusted.
More detailed information are monitored in the diagnosis telegram and on the Control Panel.
All faults must be acknowledged via fieldbus or via Control Panel. In addition the cooling time must be
elapsed to allow to restart the motor.
Addressing
The slave address of the UMC22-FieldBusPlug combination is not a parameter but can be set with the
Control Panel or with a separate Addressing Set. Details see general part chapter ''Planning and com-
missioning, Interfacing to the fieldbus, addressing''.
Important:
Normally the inputs and the internal electronic circuits are supplied locally via the terminals 10 and 11. In
this case the SWITCH must be set to EXT. The connection of distant contacts or sensors requests
urgently this kind of supply.
If only contacts nest to the UMC22-FBP are used - that means the 24 V wiring can be surveyed easily -
the supply via the fieldbus and the FieldBusPlug is possible (SWITCH to INT).
Details see general part chapter ''Planning and commissioning, Wiring an d int ernal 24V / 0V
connections''.
Terminal 13 14 15 16 17 18
Device DI0 DI1 DI2 DI3 DI4* DI5*
Input to bus to bus to bus to bus (local: Run) (local: Off)
Terminal 7 8 9
Device DO0 DO1 DO2*
Outputs from bus from bus (fault out)
Bit No. 7 6 5 4 3 2 1 0
Bit No. 7 6 5 4 3 2 1 0
Fault
Fault Self-test
- input - - - - -
Byte 0 failed
signal*
Commu- Parameter Current Relay 1
Fault Overload Motor
nication out of check-back - - check-back
Byte 1 (trip) fault blocked*
fault range fault* fault*
Motor Motor Cooling
Warning
current high current low - time - - - -
Byte 2
threshold* threshold* running
RUN FORWARD
Command
(received telegram) OFF
FAULT RESET
RUN FORWARD
OFF
Monitoring signals
(telegram) WARNING
FAULT
(Aux.cont.) DI0
Fig. A-7: UMC22-FBP: Control function 'Direct starter' - Timing diagram 'Overload'
Abbreviations:
Mot.cur. = Motor current
Aux.cont. = Auxiliary contact
Mot. on = Motor on
Reversing starter
The UMC22-FBP parameterized with the 'Control function' = 'Reversing starter' provides excellent
protection and control of a motor for two directions of rotation. The connection to a fieldbus is made via
the appropriate type of the FieldBusPlug.
K1
K1
K2
K2
5 6 7 8 9
SWITCH
DO DO DO DO DO
FieldBus UMC22 C C 0 1 2
EXT
INT
Plug
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18
K1 = forward
K2 = reverse
Fault
K1
K1
K2
K2
5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT
Plug
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18
thermistor
K1 K2 switch 1)
2CDC 342 086 F0003
1)
Fault input: Closed circuit signal: 1 = no fault
2)
Fwd, Rev: Momentary-contact switch
3)
Off: Closed circuit signal: 0 = dominating Off
Starting
After setting the parameter 'Reversing starter' power-on is necessary to activate and to allow to start the
motor with the bus command RUN FORWARD / RUN REVERSE or via local control. All other
parameters are activated with motor on.
Change direction
An OFF command is necessary before switching to the opposite direction.
The OFF command starts the reversing lock-out time (parameterizable).
The opposite RUN command - 0-1 transition - is accepted only when the reversing lock-out time has
elapsed.
Check-back
When the motor is started the check-back status is expected within 100 ms, otherwise a fault is detected.
Selectable by parameter, motor current or auxiliary contact signal can serve as check-back status.
Notice: 'Check-back' = 'Simulation' is recommended only to be set via Control Panel during commissio-
ning. The control system is only allowed to set 'Auxiliary contacts' or 'Motor current' to guarantee
that the check-back operates correctly after next power-on.
Fault behaviour
All kinds of detected external and internal faults set the internal fault bit. In the following:
contact DO0 or DO1 for the contactor coil opens,
the monitoring signal FAULT is sent to the fieldbus,
the red LED on the UMC22-FBP lights on and
the FAULT signal on the Control Panel display flashes.
If a motor overload is the cause of the fault signal, the cooling time is started additionally. The cooling
time is a parameter and can be adjusted.
All faults must be acknowledged via fieldbus or via Control Panel. In addition the cooling time must be
elapsed to allow to restart the motor with a 0-1 transition of the RUN FORWARD or RUN REVERSE
command.
More detailed information are monitored in the diagnosis telegram and on the Control Panel.
Addressing
The slave address of the UMC22-FieldBusPlug combination is not a parameter but can be set with
Control Panel or with separate Addressing Set. Details see general part chapter ''Planning and
commissioning, Interfacing to the fieldbus, addressing''.
Terminal 13 14 15 16 17 18
Device DI0* DI1 DI2* DI3* DI4* DI5*
Input (aux. cont.) to bus (ext. fault) (local: Rev) (local: Fwd) (local: Off)
Terminal 7 8 9
Device DO0 DO1 DO2*
Outputs (Forward) (Reverse) (fault out)
Bit No. 7 6 5 4 3 2 1 0
REVERSING
Monitor LOCAL RUN RUN
WARNING FAULT LOCK-OUT - OFF
Byte 0 CONTROL FORWARD REVERSE
TIME
Monitor DI5 DI4 DI3 DI2 DI1 DI0
- -
Byte 1 (UMC input) (UMC input) (UMC input) (UMC input) (UMC input) (UMC input)
Monitor
MOTOR CURRENT (% of set current)
Byte 2/3
Bit No. 7 6 5 4 3 2 1 0
Fault
Fault Self-test
- input - - - - -
Byte 0 failed
signal*
Commu- Parameter Current Relay 1
Fault Overload Motor
nication out of check-back - - check-back
Byte 1 (trip) fault blocked*
fault range fault* fault*
Motor Motor Cooling Reversing
Warning
current high current low - time lock-out - - -
Byte 2
threshold* threshold* running time
RUN
RUN REVERSE RUN
FORWARD OFF ignored REVERSE
RUN FORWARD
Command
(received telegram) RUN REVERSE
OFF
DO0 (forward)
UMC outputs
DO1 (reverse)
RUN FORWARD
RUN REVERSE
Monitoring signals
(telegram)
OFF
Fig. A-10: UMC22-FBP: Control function 'Reversing starter' - Timing diagram 'Change direction'
Abbreviations:
Mot.cur. = Motor current
Aux.cont. = Auxiliary contact
Mot. on = Motor on
Rev.lock-out time = Reversing lock-out time
Remark:
Opposite direction only possible after 'OFF'.
Restart in the same direction without regard of the reversing lock-out time.
RUN FORWARD
RUN REVERSE
Command
(received telegram)
OFF
FAULT RESET
DO0 (forward)
UMC outputs
DO1 (reverse)
RUN FORWARD
RUN REVERSE
OFF
Monitoring signals
(telegram)
WARNING
FAULT
(Aux.cont.) DI0
Fig. A-11: UMC22-FBP: Control function 'Reversing starter' - Timing diagram 'Overload'
Abbreviations:
Mot.cur. = Motor current
Aux.cont. = Auxiliary contact
Mot. on = Motor on
Remark:
Restart possible only if cooling time has elapsed and fault is acknowledged.
Star-delta starter 1
The UMC22-FBP parameterized with the 'Control function' = 'Star-delta starter 1' provides excellent
protection and control of a motor for one direction of rotation including the time or current conrolled star-
delta transition. The connection to a fieldbus is made via the appropriate type of the FieldBusPlug.
K3
K3
K2
K2
K1
K1
5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT
Plug
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18
if EXT to supply
supply inputs
Fig. A-12: UMC22-FBP: Control function 'Star-delta starter 1' (Basis circuit)
Remark:
For this case of motor wiring the set current 1 has to be set to 58% of the nominal motor current. Details
see general part chapter ''Planning and commissioning, Set current = Motor current versus wiring''.
K1 = Star
K2 = Delta
K3 = Main
K3 Fault
K3
K2
K2
K1
K1
5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT
Plug
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18
K1 K2 thermistor
switch 1)
K3
2CDC 342 087 F0003
Remark:
For this case of motor wiring the set current 1 must be set to 58% of the nominal motor current. Details
see general part chapter ''Planning and commissioning, Set current = Motor current versus wiring''.
1)
Fault input: Closed circuit signal: 1 = no fault
2)
Run: Momentary-contact switch 3)
Off: Closed circuit signal: 0 = dominating Off
Check-back
When the motor is started the check-back status is expected within 100 ms, otherwise a fault is detected.
Selectable by parameter, motor current or auxiliary contact signal can serve as check-back status.
Notice: 'Check-back' = 'Simulation' is recommended only to be set via Control Panel during commissio-
ning. The control system is only allowed to set 'Auxiliary contacts' or 'Motor current' to guarantee
that the check-back operates correctly after next power-on.
Fault behaviour
All kinds of detected external and internal faults set the internal fault bit. In the following:
contact DO0 or DO1 for the contactor coil opens,
the monitoring signal FAULT is sent to the fieldbus,
the red LED on the UMC22-FBP lights on and
the FAULT signal on the Control Panel display flashes.
If a motor overload is the cause of the fault signal, the cooling time is started additionally. The cooling
time is a parameter and can be adjusted.
More detailed information are monitored in the diagnosis telegram and on the Control Panel.
All faults must be acknowledged via fieldbus or via Control Panel. In addition the cooling time must be
elapsed to allow to restart the motor with a 0-1 transition of the RUN FORWARD command.
Addressing
The slave address of the UMC22-FieldBusPlug combination is not a parameter but can be set with the
Control Panel or with a separate Addressing Set. Details seegeneral part chapter ''Planning and
commissioning, Interfacing to the fieldbus, addressing''.
Terminal 13 14 15 16 17 18
Device DI0* DI1 DI2* DI3 DI4* DI5*
Input (aux.cont.) to bus (ext. fault) to bus (local: Run) (local: Off)
Terminal 7 8 9
Device DO0 DO1 DO2*
Outputs (star) (delta) (fault out)
Bit No. 7 6 5 4 3 2 1 0
Bit No. 7 6 5 4 3 2 1 0
Fault
Fault Self-test
- input - - - - -
Byte 0 failed
signal*
Commu- Parameter Current Relay 1 Relay 0
Fault Overload Motor
nication out of check-back - check-back check-back
Byte 1 (trip) fault blocked*
fault range fault* fault* fault*
Motor Motor Cooling
Warning
current high current low - time - - - -
Byte 2
threshold* threshold* running
RUN
Fig. A-14: UMC22-FBP: Control function 'Star-delta starter 1' - Timing diagram 'Star-delta start'
Abbreviations:
Mot.cur. = Motor current
Aux.cont. = Auxiliary contact
Mot. on = Motor on
RUN FORWARD
Command
(received telegram) OFF
FAULT RESET
RUN
OFF
Monitoring signals
WARNING Cooling time
(telegram)
FAULT
(Aux.cont.) DI0
Fig. A-15: UMC22-FBP: Control function 'Star-delta starter 1' - Timing diagram 'Overload'
Abbreviations:
Mot.cur. = Motor current
Aux.cont. = Auxiliary contact
Mot. on = Motor on
Pole-changing starter 1
The UMC22-FBP parameterized with the 'Control function' = 'Pole-changing starter 1' provides excellent
protection and control of a two-pole or Dahlander motor for one direction of rotation. The change from
one speed to the other is possible immediately. The connection to a fieldbus is made via the appropriate
type of FieldBusPlug.
K2
K1
5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT
Plug
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18
U1 U2
V1 V2
W1 W2
Fig. A-16: UMC22-FBP: Control function 'Pole-changing starter1 - Two-pole motor' (Basis circuit)
K1 = Speed 1
K2 = Speed 2
Fault
K2
K1
5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT
Plug
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18
thermistor
switch 1)
K1 K2 K2 K1
U1 U2
V1 V2
0 V 24 V 24 V DI1 PTC Run RUN Off W1
2CDC 342 077 F0003
W2
K2 K1
if EXT to supply Local operation via
supply inputs digital inputs 2), 3)
Fig. A-18: UMC22-FBP: Control function 'Pole-changing starter 1 - Two-pole motor' (Extended circuit)
1)
Fault input: Closed circuit signal: 1 = no fault
2)
Run A, Run B: Momentary-contact switch 3)
Off: Closed circuit signal: 0 = dominating Off
K1 = Speed 1
K2a/b = Speed 2
K2a
K2b
K1
5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT
Plug
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18
U1 U2
V1 V2
W1 W2
Fig. A-17: UMC22-FBP: Control function 'Pole-changing starter1 - Dahlander motor' (Basis circuit)
Remark:
Output DO1 controls contactor K2b. Do not change!
K2a Fault
K2b
K1
5 6 7 8 9
SWITCH UMC22 DO DO DO DO DO
FieldBus C C 0 1 2
EXT
INT
Plug
0 24 24 DI DI DI DI DI DI
V V V 0 1 2 3 4 5
10 11 12 13 14 15 16 17 18
thermistor
switch 1)
K1 K2a K1 K2a
K2b
U1 U2
0 V 24 V 24 V DI1 PTC Run Run Off V1 V2
2CDC 342 078 F0003
K2 K1 W1 W2
if EXT to supply Local operation via
supply inputs digital inputs 2), 3)
Fig. A-19: UMC22-FBP: Control function 'Pole-changing starter 1 - Dahlander motor' (Extended circuit)
0)
K2b controls K2a, do not change! 1)
Fault input: Closed circuit signal: 1 = no fault
2)
Run K1, Run K2: Momentary-contact switch 3)
Off: Closed circuit signal: 0 = dominating Off
Starting
After setting the parameter ‘Pole-changing starter 1’ power-on is necessary to activate and to allow to
start the motor with the bus command RUN FORWARD (speed 1, contactor K1), RUN REVERSE
(speed 2, contactors K2a and K2b) or via local control. All other parameters are activated with motor on.
Change of the speed (K1->K2->K1) is possible without restriction. Between the two speeds a lock-out
time of about 50 ms is waited after current = 0 or auxiliary contact = off resp.
Check-back
When the motor is started the check-back status is expected within 100 ms, otherwise a fault is detected.
Selectable by parameter, motor current or auxiliary contact signal can serve as check-back status.
Notice: ‘Check-back’ = ’Simulation’ is recommended only to be set via Control Panel during commissio-
ning. The control system is onlyallowed to set ‘Auxiliary contacts’ or ‘Motor current’ to guarantee
that the check-back operates correctly after next power-on.
Fault behaviour
All kinds of detected external and internal faults set the internal fault bit. In the following:
contact DO0 or DO1 for the contactor coil opens,
the monitoring signal FAULT is sent to the fieldbus,
the red LED on the UMC22-FBPlights on and
the FAULT signal on the Control Panel display.
If a motor overload is the cause of the fault signal, the cooling time is started additionally . The cooling
time is a parameter and can be adjusted.
More detailed information are monitored in the diagnosis telegram and on the Control Panel.
All faults must be acknowledged via fieldbus or via Control Panel. In addition the cooling time must be
elapsed to allow to restart the motor with a 0-1 transition of the RUN FORWARD command.
Addressing
The slave address of the UMC22-FieldBusPlug combination is not a parameter but can be set with the
Control Panel or with a separate Addressing Set. Details see general part chapter "Planning and
commissioning, Interfacing to the fieldbus, addressing''.
Terminal 13 14 15 16 17 18
Device DI0* DI1 DI2* DI3* DI4* DI5*
Input (aux. cont.) to bus (ext. fault) (local: B1) (local: A) (local: Off)
Terminal 7 8 9
Device DO0* DO1* DO2*
Outputs (cont. K1) (cont. K2) (fault out) all digital inputs are monitored to the bus
Bit No. 7 6 5 4 3 2 1 0
RUN RUN
Monitor LOCAL
WARNING FAULT - - FORWARD OFF REVERSE
Byte 0 CONTROL
(cont. K1) (cont. K2)
Monitor DI5 DI4 DI3 DI2 DI1 DI0
- -
Byte 1 (UMC input) (UMC input) (UMC input) (UMC input) (UMC input) (UMC input)
Monitor
MOTOR CURRENT (% of set current)
Byte 2/3
Bit No. 7 6 5 4 3 2 1 0
Fault
Fault Self-test
- input - - - - -
Byte 0 failed
signal*
Commu- Parameter Current Relay 1 Relay 0
Fault Overload Motor
nication out of check-back - check-back check-back
Byte 1 (trip) fault blocked
fault range fault* fault* fault*
Motor Motor Cooling Lock-out
Warning
current high current low - time time - - -
Byte 2
threshold* threshold* running running
Fig. A-20: UMC22-FBP: Control function 'Pol-changing starter 1' - Timing diagram 'change speed'
Abbreviations:
Mot.cur. = Motor current
Aux.cont. = Auxiliary contact
Mot. on = Motor on
conta. = contactor
Remark:
Restart with the same speed without delay.
RUN K1 or K2a/b
Command
(received telegram) OFF
FAULT RESET
RUN K1 or K2a/b
OFF
Monitoring signals
(telegram) WARNING Cooling time
FAULT
Fig. A-21: UMC22-FBP: Control function 'Pole-changing starter 1' - Timing diagram 'Overload'
Abbreviations:
Mot.cur. = Motor current
Aux.cont. = Auxiliary contact
Mot. on = Motor on
LOC mAVs
REM kHz%
FAULT Cprm
OUTPUT PAR SET MENU FWD REV
MENU
LOC REM
ENTER
Fig. B-1: UMC22-FBP: Control Panel ACS-100 PAN 2CDC 342 092 F0003
Contents Page
MENU
Remark: Return to menu point 'Show address' (1.1) after
MENU 5 min if no button is pressed.
2CDC 342 092 F0003
Attention: Changed parameters are displayed immediately but executed after power on
or motor off, see general part chapters ''Data overview, Paramaters ...''.
Edit 1:
Change Edit 2:
parameters that Change
S are mainly used
Monitoring: parameters that
t during operation apply mainly for
e. g. Slave
a address, status e. g. Set current the wiring e.g.
r of digital I/O, Control function,
actual current. MENU MENU Check-back.
t
Password
MENU not 0000
ENTER ENTER
Change
Show password (new)
address ENTER
Local control
Change Control
address function
if password is
Digital input, 0000 (default) Change Set Local control
digital output current 1 via digit. inputs
switching off.
- 1.6.6 Relay 2 check-back fault FAULT Signal on DI2 does not appear la-
blinks taest 100 ms after switching on or
does not disappear latest 100 ms
password.
First position flashes, change with
no address
0301 2.4 Change set current 1 PAR Important: The UMC22-FBP motor
measures the currents of the lines in off
the bushing holes. The currents of
the incoming lines can be different
depending on the circuitry.
0301 2.4.1 show / change PAR SET, 1A 0.24 - 2 places befor the decimal point
A 63 A
0302 2.5 Change set current 2 PAR Set current of winding 2 changing motor
starters. off
0302 2.5.1 show / change PAR SET, 1A 0.24 - 2 places befor the decimal point
A 63 A
0401 2.6 Trip class PAR Overload check (thermal motor motor
image) off
0401 2.6.1 Trip class 5 PAR SET
0401 2.6.2 Trip class 10 PAR SET 10
0401 2.6.3 Trip class 20 PAR SET
0401 2.6.4 Trip class 30 PAR SET
0205 2.7 Reversing lock-out time PAR Only for reversing starter! motor
Starts with OFF (OFF is necessarry off
between RUN FORWARD and RUN
REVERSE)
RUN command in other direction is
AUTO MODE = 0 or
communication to control system is
interrupted.
0202 3.4. Check-back PAR motor
0202 3.4.0 Auxiliary contacts PAR SET OK when auxiliary contacts are on
closed 100 ms after start.
0202 3.4.1 Motor current PAR SET curr. OK when current is flowing 100 ms
after start
0202 3.4.2 Simulation PAR SET Simulated check-back (e.g. to be set
to operation without motor).
Remark: Normally overwritten by the
control system during power-on.
Details see general part chapters
"Data overview, Parameters ...".
0203 3.5 Fault input PAR Digital input DI2 to for external fault motor
signal, closed-circuit on
0203 3.5.0 Off PAR SET Off Off: Digital input free available.
0203 3.5.1 On PAR SET On: Signal 1 on DI2 is requested.
If DI2 = 0 internal fault signal is set.
0204 3.6 Fault output PAR Digital output DO2 used to monitor motor
fault signal on
0204 3.6.0 Off PAR SET Off Off: Digital output free available.
0204 3.6.1 On PAR SET On: Digital output DO2 monitors
fault signal.
0206 3.9 Star-delta changeover PAR Only needed for star-delta starter! motor
mode on
0206 3.9.1 Time PAR SET Change from star delta when star-
delta starting time is over
0206 3.9.2 Current PAR SET curr. Change from star delta when
motor current = 0,9 x set current
Remark: Must switch to delta before
star-delta starting time has elapsed
otherwise current check-back fault.
0702 3.10 Bus connection PAR power
0702 3.10.0 Stand-alone PAR SET Stand-alone / without bus communi- on
cation, via digital inputs and Control
Panel.
0702 3.10.1 Bus connection PAR SET bus Operation with bus communication.
con.
- 3.11 Parameter transfer PAR Control Panel can read and write the power
complete parameter set from / to on
UMC22-FBP except fieldbus slave
address.
- 3.11.0 Read parameters PAR SET Control Panel reads the actual
parameters from the UMC22-FBP
with [ENTER].
- 3.11.1 Set parameters PAR SET Control Panel overwirtes the actual
parameters in the UMC22-FBP with
[ENTER].
- 3.12 Reset to Default PAR power
- 3.12.1 Execute PAR SET Go back to default values with on
[ENTER].
Fieldbus slave address, Operating
hours, Number of starts and Number
of trips are not changed.
0404 3.13 Automatic fault reset PAR Automatic fault reset (On) is only imme-
possible with the control function diately
overload relay.
0404 3.13.0 not resetted automatically PAR SET not Fault has to be resetted via Control
reset Panel or via fieldbus.
0404 3.13.1 Automatic reset PAR SET Automatic reset of fault when fault
condition is off and cooling time has
elapsed. Fault is not monitored.