FIRE DAMPERS SFD-20R FIRE DAMPERS SFD-20R U.L. - Classified FIRE DAMPERS
2 HOUR RATED SFD-20R (FUSIBLE LINK TYPE) MULTI-BLADES FIRE DAMPER
U.L. 555 2hr. Fire Endurance Rated STANDARD CONSTRUCTION
FRAME : 4 wide 16 Ga. Galvanized steel sheet , Duct Insertion type HAT Frame provides rigidity and strength. BLADE : 16 Ga. Galvanized steel Max. 6 spacing. Parallel action Designed with reinforced 3 grooves for more strength and overlap coverage. Max. length is 48. BLADE STOP : 16 Ga. Galvanized Steel BLADE CATCH: 1.6 mm Thk. Stainless Steel Flat Spring. FUSIBLE LINK : U. L. Approved fuse. Standard 160F (others available) AXLES & STRAP : galvanized steel with axle straps bolted to blades. LINKAGES : 14 Ga. Galv. steel formed brackets and link bars, face linkages inside of air stream. BEARINGS : Bronze Sleeve Bearings. CLOSURE SPRING : 10mm x 1mm Stainless steel coil Spring mounted on 16 Ga. Galv. bracket. SIZES : Made to exact size as required. Max. size 48W x 96H : Divider frame shall be provide for dampers over max. size. Min. size 6W x 5H: Dampers 11 inches high and smaller shall be single blade type. Dampers 12 inches high and larger shall be multi-blade type.
NOTE : For proper operation all dampers must be installed square & free from racking. Any dampers installed over 1 section wide and 1 section high shall have appropriate bracing at every horizontal mullion and vertical bracing min. 80 O.C. Fire Dampers are designed for operation with blades running horizontally.
IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Designs are subject to change without prior notice. Page 2
P.O. Box 60479 Riyadh 11545 K.S.A. Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385 Email: dania@sunaid.com.sa
RFD 50 SERIES
U.L. 555 Fire Endurance Rated CURTAIN TYPE STANDARD CONSTRUCTION VERTICAL OR HORIZONTAL TYPE, 100% FREE AREA
FRAME : 18 ga. galvanized steel BLADE : 22 ga. Galvanized steel blades with interlocking Joints. SPIGOT : 18 ga. Galvanized steel (available in Square, Rectangular, Round or Oval Spigots) FUSIBLE LINK : U. L. Approved fuse. Standard 160F (others available) MIN. SIZE : 4W x 4 H MAX. SIZE : 40W x 48 H FOR HORIZONTAL TYPE UNITS : (Specify if Horizontal Mounted) BLADE LOCK : 16 ga. Galvanized steel blade lock. SPRING : Stainless steel closure springs for Horizontal type units. VARIATIONS : 1. Special finishes. 2. Special made sleeve or collar. 3. Special materials, Stainless Steel. 4. Special micro switch attachments. HOW TO SPECIFY : 1. Model / Type. 2. 3. 4. 5. Mounting type. Duct size. Spigot type. Quantity.
SPIGOT OPTIONS :
STYLE (RE)
STYLE (R)
STYLE (O)
Flat Oval spigot
DIMENSIONAL DETAIL
IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Designs are subject to change without prior notice. Page 3
P.O. Box 60479 Riyadh 11545 K.S.A. Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385 Email: dania@sunaid.com.sa
SFD - 70 SERIES
U.L. 555 3hr. Fire Endurance Rated CURTAIN TYPE STANDARD CONSTRUCTION VERTICAL OR HORIZONTAL TYPE WITH BLADES IN AIR STREAMS 85% Free Area, Duct Insertion Type
FRAME : 20 ga. galvanized steel BLADE : 22 ga. Galvanized steel blades with interlocking Joints. FUSIBLE LINK : U. L. Approved fuse. Standard 160F (others available) MIN. SIZE : 4W x 4 H MAX. SIZE : 40W x 48 H FOR HORIZONTAL TYPE UNITS : (Specify if Horizontal Mounted) BLADE LOCK : 16 ga. Galvanized steel blade lock. SPRING : Stainless steel closure springs for Horizontal type units. VARIATIONS : 1. Special finishes. 2. Special made sleeve or collar. 3. Special materials, Stainless Steel. 4. Special micro switch attachments. HOW TO SPECIFY : 1. Model / Type. 2. 3. 4. 5. Mounting type. Duct size. Spigot type. Quantity.
DIMENSIONAL DETAIL
IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Designs are subject to change without prior notice. Page 4
P.O. Box 60479 Riyadh 11545 K.S.A. Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385 Email: dania@sunaid.com.sa
FIRE DAMPERS SFD-70 SERIES FIRE DAMPERS SFD-70 SERIES U.L. - Classified FIRE DAMPERS
3 HOUR RATED
SFD - 70 HC
U.L. 555 2hr. Fire Endurance Rated CURTAIN TYPE STANDARD CONSTRUCTION VERTICAL OR HORIZONTAL TYPE WITH HEAD CAP 100% Free Area Duct Insertion Type
FRAME : 20 ga. galvanized steel BLADE : 22 ga. Galvanized steel blades with interlocking Joints. FUSIBLE LINK : U. L. Approved fuse. Standard 160F (others available) MIN. SIZE : 4W x 4 H MAX. SIZE : 40W x 48 H FOR HORIZONTAL TYPE UNITS : (Specify if Horizontal Mounted) BLADE LOCK : 16 ga. Galvanized steel blade lock. SPRING : Stainless steel closure springs for Horizontal type units. VARIATIONS : 1. Special finishes. 2. Special made sleeve or collar. 3. Special materials, Stainless Steel. 4. Special micro switch attachments. HOW TO SPECIFY : 1. Model / Type. 2. 3. 4. 5. Mounting type. Duct size. Spigot type. Quantity.
MOUNTING DETAIL
DIMENSIONAL DETAIL
IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Designs are subject to change without prior notice. Page 5
P.O. Box 60479 Riyadh 11545 K.S.A. Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385 Email: dania@sunaid.com.sa
FIRE DAMPERS
RFD-50
SFD-70
IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Designs are subject to change without prior notice. Page 6
P.O. Box 60479 Riyadh 11545 K.S.A. Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385 Email: dania@sunaid.com.sa
H Listed Size (mm) 150 175 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250 1300 1350 1400
NOTE :
H Actual Size (mm) 144 169 194 244 294 344 394 444 494 544 594 644 694 744 794 844 894 944 994 1044 1094 1144 1194 1244 1294 1344 1394
H1 Ho Overall Size Head Size (mm) (mm) 28 197 32 226 32 251 44 313 50 369 54 423 62 481 66 535 74 593 78 647 86 705 90 759 98 817 110 879 114 933 122 991 126 1045 134 1103 138 1157 146 1215 150 1269 158 1327 170 1389 174 1443 187 1506 191 1560 199 1618
H Listed Size (mm) 150 175 200 250 300 350 400 450 500 550 600 650 700 750 800 850 900 950 1000 1050 1100 1150 1200 1250 1300 1350 1400
H Actual Size (mm) 144 169 194 244 294 344 394 444 494 544 594 644 694 744 794 844 894 944 994 1044 1094 1144 1194 1244 1294 1344 1394
H1 Ho Overall Size Head Size (mm) (mm) 28 172 32 201 32 226 44 288 50 344 54 398 62 456 66 510 74 568 78 622 86 680 90 734 98 792 110 854 114 908 122 966 126 1020 134 1078 138 1132 146 1190 150 1244 158 1302 170 1364 174 1418 187 1481 191 1535 199 1593
All dimensions are given in millimeters. Dampers are normally fabricated approximately less than given duct dimensions.
IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Designs are subject to change without prior notice. Page 7
P.O. Box 60479 Riyadh 11545 K.S.A. Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385 Email: dania@sunaid.com.sa
24 28 32 36 40 44 48 52 56 60
9.3 10.0
8.9 10.0 11.1 12.2 13.3 14.4 15.6 16.7 9.8 11.0 12.2 13.4 14.7 15.9 17.1 18.3
8.7 10.1 11.6 13.0 14.4 15.9 17.3 18.8 20.2 21.7 9.3 10.9 12.4 14.0 15.6 17.1 18.7 20.2 21.8 23.3
8.3 10.0 11.7 13.3 15.0 16.7 18.3 20.0 21.7 23.3 25.0
16 20 24 28 32 36 40 44 48
9.20 10.10
8.00 19.20 10.30 11.40 12.30 8.90 10.10 11.30 12.50 13.70
P.O. Box 60479 Riyadh 11545 K.S.A. Tel. No. 01 453-6181 / 453-6072 Fax No. 01 453-6385 Email: dania@sunaid.com.sa
INSPECTION
Before installing, make sure :
The unit Has not been damaged in shipping. Is the model and size specified. If there are discrepancies, check with the job superintendent before installing. The installation site Is the correct size. Is straight, plumb and clean. The mounting surface should be as level as possible. INSTALLATION Secure to the collar or sleeve with dia. Bolts and nuts, or back tack welding with beads (+, -) in length, or with #10 sheet metal screws, or with 3/16 steel pop rivets. Fasteners or weld beads should be 6 to 8 in. on centers. The collar shall be on the same gauge or heavier than the duct sleeve to which it is attached. Gauges shall conform to SMACNA or ASHRAE duct standards. When the following duct collar connections are used, the minimum gauge of the collar shall be 16ga. On dampers not exceeding 36 wide by 24 high and 14ga. On large dampers. 1. Angle reinforced standing steam. 2. Angle reinforced pocket lock. 3. Companion angles. 4. Metal fasteners spaced a minimum of 16 on center. Secure angles to collar only so as to frame the wall opening. Angles shall be a minimum of 1 x 1 x 14 ga. Fasten to collar only using the same means as required for fastening the damper to the collar. Damper shall have a clearance of 1/8 per foot on height and width, and angles shall increase in size proportionately, so that there will be a minimum of 1 of overlap on the partition. At light see the duct sleeve connections which may be used on all systems.
6. 7. 8. 9.
IMPORTANT NOTICE : DANIA Reserves the Rights to alteration. Designs are subject to change without prior notice. Page 9