Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
Er. Lim Say Leong, Region Marketing Manager, South Asia, Automation Products Division, 18 August 2009
My talk today
Title: Low voltage switchgear and controlgear assemblies - Requirements of today and tomorrow Sypnosis: This sharing session covers the current IEC 60439 series and also the development of IEC 61439 for tomorrow. Salient requirements will be presented in details leaving time for discussions such as: difference between IEC 60439 and IEC61439, type tested & partially type tested assemblies, how to confirm/check construction compliance of assemblies as per test report, trend of busbar trunking system, etc.
Situation Many manufacturers could comply with IEC 60439. Many also do not comply due to various reasons: Lack of knowledge. Difficulties to meet customization of their product. Product not verified. Pressure to reduce costs.
ABB sets the standard Local presence and expertise Best technology for the process Cost-effective solutions Responsive local service A supplier with global guidance and direction
Part 1 Type-tested and partially type-tested assemblies. Part 2 Particular requirements for busbar trunking systems. Part 3 Particular requirements for distribution boards. Part 4 Particular requirements for assemblies for construction sites (ACS). Part 5 Particular requirements for cable distribution cabinets (CDC).
IEC 60890 Method of temperature-rise assessment by extrapolation for partially type-tested assemblies (PTTA). IEC 61117 Method of assessing the short-circuit withstand strength of partially type-tested assemblies (PTTA). IEC 61641 Guide for testing under conditions of arcing due to internal fault.
Part 3 Distribution boards where unskilled persons have access for their use.
Part 5 Cable distribution cabinets (CDCs) power distribution and installed outdoors in public places.
TTA
TypeType-tested assemblies
A low voltage switchgear and controlgear assembly conforming to an established type or system without deviations likely to significantly influence the performance, from the typical assembly verified to be in accordance with this standard.
ABB Elettrocondutture
catalogue
PTTA Partially Type-tested assemblies TypeA low voltage switchgear and controlgear assembly containing both type-tested and not type tested arrangements provided that the latter are derived (e.g. by calculation ) from type-tested arrangements which have complied with the relevant tests.
ABB Group August 18, 2009 | Slide 15
calculation
Testing of switchboards
8 Type test 1 verify temperature rise limits 2 verify dielectric properties Performed and 3 verify short-circuit withstand carried out on a 4 verify protective circuit effectiveness representative unit 5 verify clearances and creepage distances 6 verify mechanical operation 7 verify degree of protection 8 verify emc + 3 Routine tests 9 Test 8-3-1: Overall inspection The 3 routine tests 10 Test 8-3-2 or 8-3-4: Insulation check must be carried out 11 Test 8-3-3: verify protection measures & on every
electrical continuity of protective circuits
switchboard
Characteristics of switchboards
Defined by a number of key parameters. Specified by the manufacturer, sometimes by agreement between the manufacturer and user of the equipment. These characteristics, for example, may depend upon the environment in which the equipment is required to operate and the fault level of the supply to the equipment. The manufacturer must specify the relevant characteristics for the relevant type-tests to be conducted by the testing station.
Rated Current (In) Rated Short-time Withstand Current (Icw) Rated Peak Withstand Current (Ipk) Rated Conditional Short-circuit Current (Icc) Rated Fused Short-circuit Current (Icf) Rated Diversity Factor Rated Frequency
ABB Group August 18, 2009 | Slide 18
Information to be provided
On Nameplates manufacturer's name or trade mark type designation or identification number, or any other means of identification making it possible to obtain relevant information from the manufacturer On Nameplates or Technical documentation IEC 60439-1; Type of current (and frequency, in the case of a.c.); Rated operational voltages (see 4.1.1); Rated insulation voltages (see 4.1.2); Rated impulse withstand voltage, when declared by the manufacturer (see 4.1.3); Rated voltages of auxiliary circuits (if applicable);
ABB Group August 18, 2009 | Slide 19
10
Service condition
Ambient air temperature Ambient air temperature for indoor installations Does not exceed +40 and its average over a period C of 24 h does not exceed +35 C. The lower limit of the ambient air temperature is 5 C. Ambient air temperature for outdoor installations Does not exceed +40 and its average over a period C of 24 h does not exceed +35 C. The lower limit of the ambient air temperature is: 25 in a temperate climate, and C 50 in an arctic climate. C
11
Service condition
Atmospheric conditions Atmospheric conditions for indoor installations The air is clean and its relative humidity does not exceed 50 % at a maximum temperature of +40 C. Higher relative humidity may be permitted at lower temperature, for example 90 % at +20 C. Atmospheric conditions for outdoor installations The relative humidity may temporarily be as high as 100 % at a maximum temperature of +25 C.
Service condition
Pollution degree Refers to the environmental conditions for which the ASSEMBLY is intended. For switching devices and components inside an enclosure, the pollution degree of the environmental conditions in the enclosure is applicable.
12
Service condition
Pollution degree (contd) To evaluate clearances and creepage distances, the following four degrees of pollution are established. Pollution degree 1 No pollution or only dry, non-conductive pollution occurs. Pollution degree 2 Normally, only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation may be expected. Pollution degree 3 Conductive pollution occurs or dry, non-conductive pollution occurs which becomes conductive due to condensation. Pollution degree 4 The pollution generates persistent conductivity caused, for instance, by conductive dust or by rain or snow.
Service condition
Altitude Site of installation does not exceed 2 000 m (6 600 ft). Note: For electronic equipment to be used at altitudes above 1 000 m, it may be necessary to take into account the reduction of the dielectric strength and of the cooling effect of the air. Electronic equipment intended to operate in these conditions should be designed or used in accordance with an agreement between manufacturer and user.
13
14
15
16
How we react? The usual way is to blame down the chain Can we overcome it? Yes
Overheating What causes it? Poor connection - Mitigation There is proper tightening torque Equipment Value Correct selection of termination Regular checking
17
Overheating What causes it? Under-size - Mitigation Correct sizing for cable and busbar. At termination oversize to have heatsink effect. Overdoing it results in costs increase
Overheating What causes it? Ventilations - Mitigation Heat concentration Chimney effect Do not block it Regular checking and cleaning
18
Overheating What causes it? Harmonics - Mitigation Know the load in advance Filters
Have sufficient rating for the inductor. Have capacitor that takes the overvoltage and the flame-retardant
19
20
Testing and acceptance Classification of tests in IEC 60439-1 type tests routine tests Practice of acceptance in addition to standard Factory acceptance test - FAT Site acceptance test SAT Operation and maintenance manual O&M
21
22
Testing and acceptance Type tests to verify compliance with standard & carried out on a sample to be manufactured to the same or a similar design. They shall be carried out on the initiative of the manufacturer.
Testing and acceptance Routine tests on every production unit intended to detect faults in materials and workmanship.
a) b) c)
23
Testing and acceptance Factory acceptance test Materials and construction Setting and verifying Site acceptance test Transportation damage Setting, sealing, signed off Operation and maintenance manual Learning to use and maintenance
24
overvoltage category a conventional number based on limiting (or controlling) the values of prospective transient overvoltages occurring in a circuit (or within an electrical system having different nominal voltages) and depending upon the means employed to influence the overvoltages. surge arrester a device designed to protect the electrical apparatus from high transient overvoltages and to limit the duration and frequently the amplitude of the follow-on current
Overvoltages Supply overvoltages are specified in figure 1. This figure applies to the non-periodic overvoltages as a deviation from the rated peak value within the short-time range. The ASSEMBLIES shall be so designed that their service ability in the case of overvoltages below the values represented by curve 1 is ensured. If overvoltages occur within the range between curves 1 and 2, the operation may be interrupted by the response of protective devices safeguarding the ASSEMBLY, no damage to the ASSEMBLY being allowed to occur up to a peak value of the voltage equal to 2 Ui + 1 000 V.
25
Temporary variations in voltage and frequency The equipment shall operate without damage when there are temporary variations in the following conditions. voltage drops not exceeding 15 % of rated voltage for periods not longer than 0,5 s. supply frequency deviation of up to + 1% of rated frequency. the maximum admissible duration of an interruption of the supply voltage for equipment shall be indicated by the manufacturer.
26
System voltage
Uimp
400 V~ 6000 V
230 V~ 4000 V
230 V~ 60 V~ 2500 V II
1500 V I
Category
IV
III
27
Category I
Special equipment communication equipment electronics
Category I 1.5 kV
28
Increasing propagation of disturbance : interconnection and complexity of power and telecommunication networks. switching operations of power electronics.
Statistics from insurance shows high percentage of damage to electronics due to overvoltages Loss of operation Loss of service
29
What is an overvoltage?
Lightning strikes
30
Lightning strikes
Iimp 90%
V ALUE in kA
10/350 waveshape
10/350 is used to test Type 1
10/350
50%
Lightning strikes
Inductive coupling
+ switching operations
Capacitive and inductive equipments are switched on or off Fuse or breaker operations Power electronics
31
Lightning strikes
8/20 waveshape
8/20 is used to test Type 2 and Type 3
Imax 90%
VALUE
8/20
(s)
V A LU E in kA
10/350 8/20
T IM E in us
32
Cumulative frequency
80%
40% of lightning strikes are higher than 20kA (or 60% of lightning strikes are below 20kA) 5 % of lightning strikes are higher than 60kA (or 95% of lightning strikes are below 60kA) 0.1 % of lightning strikes are higher than 200kA
60%
40%
20%
0% 0
20
40
60
80
100
120
140
160
180
200
Cumulative frequency of lightning strikes positive and negative- versus their amplitude. Data from Meteorage. Measurement campaign on 5.4Million strokes between 1995-2005
200 kA
TV network 48,3 kA
power network
33 kA 33 kA 33 kA
PE 100 kA
water and gas pipes
10 100 kA
33
UL
Withstand of equipment
Equipments are divided into withstand categories : Category IV : Industrial equipment, meters Category III : Distribution panels, switchgear Category II : Domestic electrical equipment Category I : Sensitive electronic circuits overvoltage < 6000V overvoltage < 4000V overvoltage < 2500V. overvoltage < 1500V
34
Level of protection = Up
Unetwork
SPD
Up=1,2kV
UProtected
Equipment
Iimp
10/350
50%
35
Imax
40kA 8/20
8/20
70kA 8/20
(s)
36
OVR T1 25-255
Once the surge is earthed, arc enters in the arc chamber. this is self extinguishing time
Hot gas exit passing through the exhaust channel that avoid any fire risks
37
38
IEC 61439 provides detail guidelines on how to prove that assemblies derived from fully typetested assemblies comply with the new standard.
IEC 60439 standard was not so easy to assess whether partially type tested assemblies are compliant.
39
40
Previous ambiguities have been addressed, e.g. diversity, rating of circuits and substitution of devices. The standard requires that the performance of every assembly is demonstrated at design and manufacturing stages by a combination of stringent and defined verification processes : proving tests, inspection, design rules and/or calculation.
41
Tests carried out on devices to their own product standard do not need to be duplicated when installed in an assembly. The new standard fully recognises the use of switchboards assembled from kit systems in accordance with the original manufacturers instructions. The verification process no longer recognizes the classifications of TTA. and PTTA., alternative and equivalent methods to type tests are included
Tests carried out on devices to their own product standard do not need to be duplicated when installed in an assembly. The new standard fully recognises the use of switchboards assembled from kit systems in accordance with the original manufacturers instructions. The verification process no longer recognizes the classifications of TTA. and PTTA., alternative and equivalent methods to type tests are included
42
ArTu K
The completely type tested assembly (TTA) and competitive solution designed to be assembled by an Authorized Panel builder In kit form mainly for power distribution. A pre-engineered product from to be Authorized Panel builder assembled by
Main characteristics
43
Main characteristics
Integrated range of structures up to 4000A with common accessories
Possibility of fullfilling all application requirements in terms of installation and degree of protection (IP31, IP41, IP42, IP65) Segregations in kits up to Form 4
Main characteristics
ArTu complies with the CEI EN60439 Standards Production system certified ISO 9001 and ISO 14000
ArTu has obtained ACAE/LOVAG & ASTA Certification ArTu is in accordance with UL50 and UL891
44
Main characteristics
Compliance with IEC 60439-1 Standard
ArTu K Switchboards have undergone TTA tests foreseen by IEC 439-1 in the ABB & Falcon laboratories. The results guarantee the performance of ArTu K by using the structures and ABB SACE circuit breakers, therefore the assembler does not have to carry out any further type test by following the selection criteria and the assembly instruction for the various components
Main characteristics
Insulation distances (ref. para. 8.2.5 of the standard)
The insulation distances are guaranteed by following the ABB SACE assembly & mounting instructions, and those for ABB SACE circuit breakers
Degree of protection (ref. para. 8.2.7 of the standard) & to IEC 529
Without door : Without door : With door: IP 31 IP 41 IP 65
Impact resistance IK
Strong structure and tempered glass
40c
45
A complete system: Busbars with shaped section up to 3200A Flat Drilled Busbars up to 4000A
Rapid coupling
46
IEC 61439 the new standard for low-voltage switchgear and controlgear assemblies was issued Jan 2009. One of the main improvements is that the definition of fully Type Tested Assemblies (TTA) and Partially Type Tested Assemblies (PTTA) have been removed from the standard.
47
IEC 61439 provides detail guidelines on how to prove that assemblies derived from fully typetested assemblies comply with the new standard. IEC 60439 standard was not so easy to assess whether partially type tested assemblies are compliant. IEC 61439 standard will specify: by testing by calculations by design rules
If we have existing products that have already been tested properly, this will not affect your IEC 60439 certification. Tendency to provide more proof that their product families follow the correct design guidelines and rules to comply with IEC 61439. It is no longer acceptable to provide an assembly without a full design being fully proven. It is difficult to make substitutions of one component or product for another without stringent assurances
48
Certification and acceptance of products from IEC 60439 to IEC 61439. Moving our MS to IEC 61439 It is no longer acceptable to provide an assembly without a full design being fully proven. It is difficult to make substitutions of one component or product for another without stringent assurances.
Smissline
sayleong.lim@sg.abb.com
49
50