Signal Splitter Configurable MCR-FL-C-UI-2UI-DCI

1. Description
4-way isolation Input, power, output 1, output 2 Signal conversion and amplification Adjustable signal combinations 17.5 mm (0.689 in.) ME housing

V, I

V, I V, I

POWER

The MCR-FL-C-UI-2UI-DCI signal splitter is used to split and electrically isolate analog signals. Module inputs/outputs and the supply are electrically isolated from each other (4-way isolation). In this way, the modules can be used for electrical isolation, signal conversion, and amplication both locally and close to the control system. The power supply required is indicated by a green power LED. DIP switches can be used to switch between a signal selected within the limits of the order key or for the xed signal conversions provided in the conguration table. If no entry is made in the specied order key, the devices are supplied with the default conguration (input signal 020 mA, output signals 020 mA/ 010 V). Adjustment after conguration is not necessary, as each signal range is calibrated and stored in the device.

99

17,5

Headquarters: Phoenix Contact, Inc. P.O. Box 4100 Harrisburg, PA 17111 Phone 1-800-888-7388 Fax 717-944-1625 www.phoenixcon.com

114,5

Configurable Signal Splitter MCR-FL-C-UI-2UI-DCI

2. Technical Data

OUT

OUT

OUT I2 OUT U2 GND 2 IN I IN U GND 3

1 2 3

A D

D A

7 OUT I1 8 OUT U1 9 GND 1 0 +24V DC ! GND 4 " GND 4

4 5 6
IN

A D

MCR-FL-C-UI-2UI-DCI
8 M3 rigid Connection data 0.2-2.5 [mm2] exible AWG 0.2-2.5 24-14 (A with congurable input and output

a planned)

Description MCR signal multiplier, for splitting and electrical isolation of analog signals Precongured Not congured

Type MCR-FL-C-UI-2UI-DCI MCR-FL-C-UI-2UI-DCI-NC

Order No. 28 14 85 4 28 14 86 7

Pcs. Pkt. 1 1

Technical Data Input Input signal range Measuring range span Maximum input signal Input resistance Output Output signal per channel Maximum output signal per channel Load per channel General Data Supply voltage Current consumption (without load) Transmission error Temperature coefcient Cut-off frequency (3 dB) Step response (10 - 90%) Test voltage Protective circuit Ambient operating temperature range Degree of protection Connection method Mounting position/mounting Electromagnetic compatibility: Noise emission Noise immunity 024 mA/012 V, freely selectable in 0.1 (mA/V) steps 8 mA/4 V, minimum 50 mA or 30 V 50 at I (current) input/200 k at U (voltage) input See order key/conguration table 35 mA or 15 V 600 at I (current) output/ 10 k at U (voltage) output

2030 V DC < 25 mA < 0.15% of the nal value; 0.05% (typical) of the nal value < 0.015%/K, 0.0075%/K, typical 30 Hz 12 ms 1.5 kV AC, 50 Hz, 1 minute Transient protection -20C to +55C (-4F to +131F) IP 20 Plug-in COMBICON screw-cage terminal block Any c Conformance with EMC Directive 89/336/EEC EN 50 081-2 EN 50 082-2

PHOENIX CONTACT page 2 of 5

Configurable Signal Splitter MCR-FL-C-UI-2UI-DCI

c
Conforms to the EMC Directive 89/336/EEC and the Low Voltage Directive 73/23/EEC
EMC (Electromagnetic Compatibility) Noise immunity in accordance with EN 50082-2 Electrostatic discharge (ESD) Electromagnetic HF eld Amplitude modulation Pulse modulation Fast transients (burst)

EN 61000-4-2 EN 61000-4-3

8 kV air discharge 2) 10 V/m 1) 10 V/m 1) Input/output/supply 2 kV/5 kHz 2) Input/output: 2 kV/42 2) Supply: 0.5 kV/2 /12 2) Input/output/supply 10 V 1) Class A

EN 61000-4-4

Surge current loads (surge)

EN 61000-4-5

Conducted interference

EN 61000-4-6

Noise emission in accordance with EN 50081-2 EN 61000 corresponds to IEC 1000/ EN 55011 corresponds to CISPR11
1)

EN 55011

2)Criterion

Criterion A: Normal operating characteristics within the specied limits. B: Temporary adverse effects on the operating characteristics, which the device corrects automatically. Industrial application, without special installation measures

Class A:

MCR-FL-C-UI-2UI-DCI Signal Splitter 1 Housing cover, can be removed to set the DIP switches 2 Plug-in screw-cage terminal blocks
1

4V +2

4 R D E GN 1 W 4 O ND 1 GND G T

U O U

I DC UII-2 -U -C -FL R MC
I I

P O W E R

O U T 2
G N D 2 3 U G N D

IN
U

3 Metal lock for fastening on the DIN rail


4 5 6

2 3

OU

CI I-D 2U 4 UI- 5 C- 8 L- 14 -F 28 CR : Mrt.-Nr. T OU A OU 7 OU 8 GN 9 D A 0 ! "


D

I2 U2 2

1 2 3
A

7
D

4 5 6

IN 1 2 3

GN I U D

I2 T 2 OU U T OU 2 D

I1 8 T 1 OU U 9 T OU 1 10 D C GN VD 11 24 + 4 D 2 1 GN 4 D GN RO L VA S

4 5 6

IN IN

3 IO AT

GN

N NE

P AP

PR AP

OB

3 Fig. 06

PHOENIX CONTACT page 3 of 5

Configurable Signal Splitter MCR-FL-C-UI-2UI-DCI

3. Conguration
3.1. Opening the Device (Fig. 07) The locked housing cover is released on both sides using a screwdriver 1. The housing cover and electronics can now be pulled out about 3 cm (1.181 in.) 2. Ensure you take sufcient measures against electrostatic discharge ! 1 2
4 5 6
I2 U2 2 D
A

R MC
I I

C -D UI I-2 -U L-C -F

2 T U O U
G N D 2 G N D 3

IN
U

1 2 3
L -F CR .: Mrt.-Nr
A

OU

1 2 3
A

4 5 6 N I
1

I2 T 2 OU U UT O 2 2 D GN 3 IN IN I U D 3 EN / AP P

4 5

Fig. 07

3.2. Setting (Fig. 08) Modications to the ordered connection method settings are made via DIP switches S1 through S10. In addition to the precongured signal, which is preset by the order key, the remaining 9 DIP switches and their signal behavior can be enabled using DIP switch 10.
Conguration Via DIP switches Signal ranges preset by factory Input (IN) 020 mA 010 mA 420 mA 210 mA 010 V 15 V 05 V 210 V S1 OFF OFF OFF OFF ON ON ON ON S2 OFF OFF ON ON OFF OFF ON ON S3 OFF ON OFF ON OFF ON OFF ON S10 OFF ON DIP 10 9 8 7 6 5 4 3 2 1 Setting the input signal range Output 1: Setting the output signal ranges DIP Switch Function Signal range specication in acc. with the order key or DIP switches Output 2: Setting the output signal ranges

Fig. 08

The current and voltage channel can be used in parallel at each output so that up to four signal outputs with full load capability are provided. Please note: Where possible, output 1 should be used as a current output.
Output: Current/Voltage Signal 020 mA / 010 V 020 mA / 15 V 020 mA / 05 V 010 mA / 05 V 420 mA / 010 V 420 mA / 15 V 420 mA / 05 V 420 mA / 210 V Output 1 (OUT 1) S4 OFF OFF OFF OFF ON ON ON ON S5 OFF OFF ON ON OFF OFF ON ON S6 OFF ON OFF ON OFF ON OFF ON S7 OFF OFF OFF OFF ON ON ON ON Output 2 (OUT 2) S8 OFF OFF ON ON OFF OFF ON ON S9 OFF ON OFF ON OFF ON OFF ON

If the value is above or below the measuring range, a linear transmission response is triggered.

PHOENIX CONTACT page 4 of 5

Configurable Signal Splitter MCR-FL-C-UI-2UI-DCI

4. Application Example (Fig. 09)


Level measurement with ultrasound and subsequent signal multiplication
15 m3
420 mA

010 V

5. Order Key
For custom input settings consult factory
MCR-FL-C-UI-2UI-DCI Defult conguration / 1 1 / 0.0 2 / 20.0 / 3 1 4 / 1 5
4 I

Control system
IN OUT2 1 I2 2 U2 3 GND2 MCR-FL-C-UI-2UI-DCI
POWER

OUT1 I1 7 U1 8

POWER +24V 10 GND4 11 GND4 12

5 U 6 GND3

GND1 9

Ultrasonic transmitter/sensor
420 mA 24V

24V

1 Input Signal 1 = I 2 = U Input Signal Range Measuring range span 8.0 mA/4.0 V, minimum Increment 0.1 mA/0.1 V 2 Start Value I: Freely selectable between 0.024.0 mA U: Freely selectable between 0.012.0 V 3 Final Value I: Freely selectable between 0.024.0 mA U: Freely selectable between 0.012.0 V 4 Output 1 5 Output 2 1 = 020 mA 1 = 020 mA 2 = 420 mA 2 = 420 mA 3 = 010 mA 3 = 010 mA 4 = 010 V 4 = 010 V 5 = 05 V 5 = 05 V 6 = 15 V 6 = 15 V 7 = 210 V 7 = 210 V

AC supply voltage

Fig. 09

PHOENIX CONTACT page 5 of 5

PHOENIX CONTACT

June 1, 2001

TNR: 5106352-00

http://www.phoenixcon.com