General Specications
GS 33L50E20-40E

Models AFV10S, AFV10D Field Control Unit Duplexed Field Control Unit (for Vnet/IP, for FIO, 19" Rack Mountable Type)

GENERAL

This GS covers the hardware specications of the Field Control Unit (FCU) which is the processor of the Field Control Station (FCS).

HARDWARE SPECIFICATIONS

For the installation specications and the environmental conditions common to the systems, refer to Vnet/IP System Overview (GS 33L01A10-40E). Processor VR5432 (133 MHz) Main Memory Capacity 32 Mbyte Memory Protection During Power Failure Battery Battery Back-up for Main Memory: Max. 72 hours Battery Recharge Time: Min. 48 hours FCU Status Contact Output 2 terminals (NC, C) Contact Points open during FCU failure Contact Rating: 30 V DC, max. 0.3 A Communication Interface Vnet/IP Interface: Dual-redundant Vnet/IP Communication Speed 1000 Mbps Full Duplex Connection Specications Cable: CAT5e (Enhanced Category 5 cable) or better, UTP Transmission: 1000BASE-T and 100BASE-TX compliance Connector: RJ45 connector Max. distance: 100 m (Distance between AFV10 and Layer 2 switch) Autonegotiation No. of Node Units Connectable Max. 14/FCU The total number of the local and remote nodes that can be connected to FCU are 14 or less. (The local nodes: 9 or less) LFS1500 allows up to 3 modes, and can be expanded to 14 if LFS1530 Application capacity Expansion Package (for AFV10) is added. No. of I/O Modules Max. 8 Local Node Connection When connecting a Local Node to FCU, install ESB Bus Coupler Module (EC401) on FCU. EC401 must be installed in slot 7 or slot 8. To make single conguration, EC401 must be installed in slot 7, and Slot 8 must be empty.

F01E.ai

[19" Rack Mountable Type FCU]

Remote Node Connection When connecting a Remote Node to FCU, install ER Bus Interface Master Module (EB401) on FCU. To make single conguration, EB401 must be installed in an odd-number slot, and keep empty the right side of the installed EB401. See ER Bus Interface Master Module (for FIO) (GS 33M50F25-40E) for further information. Power Supply (specify with Sufx Codes) Voltage: 100-120 V AC, Frequency: 50/60 Hz Voltage: 220-240 V AC, Frequency: 50/60 Hz Voltage: 24 V DC Power Consumption 100-120 V AC: 200 VA 220-240 V AC: 230 VA 24 V DC: 5.5 A Weight Approx. 7 kg (AFV10S) Approx. 8 kg (AFV10D) Mounting 19" Rack Mounting: Rack mount (8 x M5 screws) Insulation bush (accessory) Connection Power Supply: M4 screw terminal connection Grounding: M4 screw terminal connection Contact Output: M4 screw terminal connection Network: Connect CAT5e (Enhanced Category 5 cable) to Layer 2 switch.

Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-5634 Fax.: 81-422-52-9802

GS 33L50E20-40E Copyright Feb. 4, 2008 (YK) 3rd Edition Nov. 1, 2008 (YK)

<<Contents>> <<Index>> Regulatory Compliance For the detailed information of following standards, see System Overview (Vnet/IP Edition) (GS 33L01A10-40E). Safety Standards [CSA] (for 100-120 V AC power supply) [CE Mark] (for 100-120 V AC and 220-240 V AC power supply) EMC Conformity Standards [CE Mark] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply) [C-Tick Mark] (for 220-240 V AC and 24 V DC power supply) Standards for Hazardous Location Equipment [FM Non-Incendive] (for 100-120 V AC, 220-240 V AC and 24 V DC power supply) [Type n] (for 24 V DC power supply) System Conguration The FCS consists of the FCU and Node Units, and the ESB bus or the ER bus to connect them together.
Dual-redundant Vnet/IP

TM1 READY

FUSE RL1

CN1 (PSU-L)

TM2

100-120V L N

AC

CN2 (PSU-R)

Dual-redundant ESB bus Local Node

FIO Maximum of 14 Nodes Local Node

Dual-redundant ER bus Remote Node

I/O signal connection


F02E.ai

Figure System Conguration

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

GS 33L50E20-40E Nov. 1, 2008-00

<<Contents>> <<Index>>

LIMITATIONS OF INSTALLATION AND NOTICES FOR INSTALLATION

For installing I/O modules in AFV10S and AFV10D, the quantity and allocation are limited. Also, when installing a node unit to the dedicated cabinet, there are limitations of installation under the ambient operating temperature conditions. When modules with built-in barriers are installed in AFV10, an insulating partition kit (Part No. T9083ND) must be installed. For details, please refer to Limitations and Precautions for Installation (GS 33L50F10-40E) and Installation Guidance (TI 33L01J10-40E).

EXTERNAL DIMENSIONS
Unit: mm

8.75 21.3

482.6 465.1 440

207 150.6

20.4

265.9

221.3 146

44.5 31.75 5.9

Hole for 19" rack mounting (8 x M5 screw holes)


F03E.ai

SOFTWARE REQUIREMENT

For AFV10S and AFV10D, LFS1500 Control Function for Basic Field Control Unit (for FIO, for Vnet/IP) is required. Specify these control functions with sufx codes. For the specications of LFS1500, refer to GS 33L15C20-40E. The number of the connectable node units and the application capacity can be expanded if LFS1530 application Capacity Expansion Package (for AFV10) is purchased.

REQUIREMENTS FOR USING SEM (Sequence of Events Manager)

For using SEM, the hardware requires some conditions. For details, refer to SEM Sequence of Events Manager (for FIO and Vnet/IP) (GS 33L30D10-40E).

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation

GS 33L50E20-40E Nov. 1, 2008-00

<<Contents>> <<Index>>

ACCESSORIES AND SPARE PARTS


Parts Names Insulating bush Parts Numbers S9049PM

The spare parts listed below are provided with the FCU.
Description Quantity 8 Remarks Accessory

MODELS AND SUFFIX CODES


Field Control Unit (19 Rack Mountable Type)
Model Description Field Control Unit (for Vnet/IP, for FIO, for 19 Rack Mountable) Standard type Dual-Redundant Vnet/IP, Single power supply Dual-Redundant Vnet/IP, Dual-Redundant power supply Always 1 100120 V AC power supply 220240 V AC power supply 24 V DC power supply 0 Basic type 1 With ISA Standard G3 option LFS1500 Basic software license for Control Function for Basic Field Control Unit 1 (for FIO, for Vnet/IP) /ATDOC Explosion Protection Manual (*1) AFV10S -S 3 4 1 1 2 4

Sufx Codes

Option Code *1:

Select the option code "/ATDOC" to follow the ATEX Directive for use in potentially explosive atmospheres. Description Duplexed Field Control Unit (for Vnet/IP, for FIO, for 19 Rack Mountable) Standard type Dual-Redundant Vnet/IP, Dual-Redundant power supply Always 1 100120 V AC power supply 220240 V AC power supply 24 V DC power supply 0 Basic type 1 With ISA Standard G3 option LFS1500 Basic software license for Control Function for Basic Field Control Unit 1 (for FIO, for Vnet/IP) /ATDOC Explosion Protection Manual (*1) AFV10D -S 4 1 1 2 4

Duplexed Field Control Unit (19 Rack Mountable Type)


Model

Sufx Codes

Option Code *1:

Select the option code "/ATDOC" to follow the ATEX Directive for use in potentially explosive atmospheres. Description

Insulating Partition Kit


Part No. T9083ND Insulating Partition Kit

Conguration of Insulating Partition Kit


Description Part No. T9083NE T9083NG Y9306LB Insulating Partition Insulating Partition for V net 2 screws for T9083NG

ORDERING INFORMATION
Specify model and sufx codes.

TRADEMARK

CENTUM Vnet/IP are registered trademark of Yokogawa Electric Corporation. Other company and product names appearing in this document are trademarks or registered trademarks of their respective holders.
GS 33L50E20-40E Nov. 1, 2008-00

All Rights Reserved. Copyright 2008, Yokogawa Electric Corporation