XTREM H07RN-F
N: Rev. 7
CABLE
TYPE
XTREM
H07RN-F.
1.-
OBJECT:
This document defines the design and manufacturing characteristics of the cable type H07RN-F manufactured by Top Cable. 2.DESIGN:
This type of cable is designed, manufactured and tested in accordance with HD 22.4. 3.APPLICATIONS:
Flexible cable for mobile service. Suitable for installations where the cable must withstand medium mechanical stress, for machines in industrial and agricultural workshops, for motors and transportable machines on construction sites, for wind mills and for agricultural exploitations. Suitable for submerged installations (AD8) The use up to 1000 V is accepted in fixed protected assemblies. Not suitable for buried installation. 4.CHARACTERISTICS:
Technical specification
XTREM H07RN-F
N: Rev. 7
5.- GENERAL MAKE-UP OF THE CABLE: 5.1 Conductor. Electrolytic annealed copper conductor, class 5 according to IEC 60228. 5.2 Insulation.
Thermosetting rubber insulation, type EI7 according to HD 22. The standard identification, according to HD 308 and HD 186, is the following: - 1 x ....................natural - 2 x ....................brown + blue - 3 G ....................brown + blue + green/yellow - 4 G....................brown + black + grey + green/yellow - 5 G ....................brown + black + grey + blue + green/yellow 5.3 Assembly of cores. The cores are twisted together. 5.4 Outer sheath. Thermosetting rubber outer sheath, black, type EM2 according to HD 22. 5.5 Diagram representation:
Technical specification
XTREM H07RN-F
N: Rev. 7
6.6.1
CURRENT-CARRYING Nominal
CAPACITIES: capacities.
current-carrying
The table 1 shows the current-carrying capacities and voltage drop detailed for every cable.
n x Cross Fixed Mobile Voltage Section Installation service drop (mm2) (A) (A) (V/Akm) 21 29 40 53 74 101 135 169 207 268 328 383 444 510 607 703 823 946 21 26 36 49 63 86 115 149 21 26 36 16 20 30 38 53 71 94 117 148 185 222 260 300 341 407 468 553 634 10 16 25 34 43 60 79 105 10 16 25 26,7 16,6 9,95 6,63 3,84 2,43 1,57 1,11 0,776 0,546 0,414 0,323 0,259 0,213 0,161 0,129 0,0976 0,0772 45,2 30,9 18,5 11,5 7,66 4,43 2,81 1,81 45,2 30,9 18,5 n x Cross Fixed Mobile Section Installation service (mm2) (A) (A) 49 63 86 115 149 185 225 289 352 17 23 32 42 54 75 100 127 158 192 246 298 17 23 32 42 54 75 100 127 29 36 51 67 89 110 138 172 204 10 16 20 30 37 52 69 92 114 143 178 210 10 16 20 30 38 54 71 94 Voltage drop (V/Akm) 11,5 7,66 4,43 2,81 1,81 1,29 0,896 0,631 0,478 39,2 26,7 16,0 9,95 6,63 3,84 2,43 1,57 1,11 0,776 0,546 0,414 39,2 26,7 16,0 9,95 6,63 3,84 2,43 1,57
1 x 1,5 1 x 2,5 1 x 4 1 x 6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 1 x 500 2 x 1 2 x 1,5 2 x 2,5 2 x 4 2 x 6 2 x 10 2 x 16 2 x 25 3G 1 3 G 1,5 3 G 2,5
Table 1
Technical specification
XTREM H07RN-F
N: Rev. 7
Current-carrying capacities, in amperes, are calculated according to HD 516 for mobile service and according to IEC 60364-5-52 for fixed installations, and for the following conditions: - Mobile service: open air, one cable with adequate ventilation and ambient temperature of 30 C - Fixed installation: open air, one cable with adequate ventilation and ambient temperature of 30 C, supported by cleats and hangers or on perforated tray (reference method F for single-core and E for multicore cables) - For cables having 2 or 3 cores, it is supposed a singlephase circuit. For the rest of the cables it is supposed a three-phase circuit. For conditions other than this apply the adequate correction factors (see point 6.3). Voltage drop is the maximum that may occur. It is calculated for 60 C conductor temperature and for cos = 1. 6.2 Short-circuit current-carrying capacities.
The maximum short-circuit current that a cable can withstand depend on the time of reaction of the protection elements installed in the line. The maximum current capacity in a short-circuit accident, for a specific type of cable, is the result of multiplying the cross section of the cable for the values shown in table 2. These values are taken from IEC 949.
Time (s) A/mm
2
0,1 452
0,2 320
0,3 261
0,5 202
1 143
1,5 117
2 101
2,5 90
3 83
The current-carrying capacities must be multiplied with the adequate correction factor, when the installation conditions differs from point 6.1 Correction factors for air temperature other than 30C.
T. air (C) Mobile service Fixed installation 30 1 1 35 0,91 0,96 40 0,82 0,91 45 0,71 0,87 50 0,58 0,82 55 0,41 0,76
Table 3
Technical specification
XTREM H07RN-F
N: Rev. 7
7.-
DIMENSIONS:
1 x 1,5 1 x 2,5 1 x 4 1 x 6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 1 x 400 1 x 500 2 x 1 2 x 1,5 2 x 2,5 2 x 4 2 x 6 2 x 10 2 x 16 2 x 25 3G 1 3 G 1,5 3 G 2,5
Table 4