S-SERIES Pressure Switches

Switches for Pressure to 8000 psig, Vacuum, Differential, or Level Control with General Purpose, Watertight or Explosion-Proof Enclosures
Features:
Set point repeatability, +1% of operating range. All wiring terminals, adjustments and visual scales are accessible from the front of the switch. Choice of general purpose, watertight or explosionproof enclosures. Choice of fixed or full-range adjustable deadband. Choice of single or two-stage units. Manual reset units available. Mounts in any position. Rugged and vibration resistant. Visual adjustment scales in psi and bars. External adjusting nuts. Separate electrical, pressure and adjusting chambers. Wide selection of transducer wetted materials suitable for air, water, oil or corrosive fluids. Mix and match switch and transducer components for increased stock flexibility or to change pressure ranges in field.

Standard Electrical Ratings


SA, SB, SC, SD and SE Series 15 Amp Res., 125 VAC 10 Amp Res., 250 VAC 1/8 HP, 125 VAC 1/4 HP, 250 VAC 1/2 Amp Res., 125 VDC 1/4 Amp Res., 250 VDC

General Description:
ASCO S-Series pressure switches consist of a switch unit and a transducer unit. They can be ordered separately for customer stocking and/or field assembly or as a complete factory-assembled unit.

SPDT
NO C NC

Switch
S-Series pressure switch units incorporate the unique ASCO TRI-POINT alternating fulcrum balance plate to control the operation of one or more electrical snapaction swtiches. The electrical snap-action switch together with the adjusting mechanism is a fully-tested, self-contained subassembly.

^ %
Standard Temperature Ratings
Ambient: -4F (-20C) to 140F (60C) Fluid: For Buna N or Neoprene Diaphragm -4F (-20C) to 180F (82C) For Viton Diaphragm -4F (-20C) to 250F (121C) For 316 SS Diaphragm -50F (-45C) to 300F (149C)

Transducer
Transducer unit incorporates a diaphragm/piston type pressure sensor, and is also a fully-tested, self-contained subassembly.

Operation
When pressure is applied to the transducer it is converted into movement of the piston. This piston movement is then used to control the operation of the electrical snap-action switch in the switch unit.
14

Options (See pages 34-35)

4
Enclosures
ASCO TRI-POINT S-Series switches are available in three standard enclosures. All of these enclosed units are made in accordance with NEMA and UL standards. General Purpose Type 1. These enclosures are designed for indoor use to protect personnel from accidental contact with the equipment. S-Series general purpose switch units consist of a copper-free* aluminum die-cast body with a formed copper-free* aluminum cover; two 3/4 conduit hubs with one plug are provided. Watertight Type 4. Watertight and dust-tight enclosures are intended for use indoors and outdoors to protect the enclosed equipment against splashing or falling water, windblown dust and water, hose directed water, and severe external condensation. S-Series watertight switch units have a copper-free* aluminum die-cast body and a formed copper-free* aluminum cover with Buna N gaskets; two 3/4 conduit hubs with one plug are provided. Explosion-Proof Types 7 and 9. Type 7 enclosures are intended for use in locations defined by the National Electrical Code as Class I. Type 9 enclosures are intended for Class II locations.

123

Class I locations are those in which flammable gases are or may be present in the air in sufficient quantities to produce explosive or ignitable mixtures. Class I locations are classified by group letter, which defines particular atmospheres. Division 1 locations are areas where the hazardous concentration exists continuously, intermittently or periodically under normal operating conditions. Division 2 locations are those where the hazardous vapors are present only in case of accidental rupture or breakdown of equipment. ASCO TRI-POINT explosion-proof enclosures with letter B, C or D in the fifth position are listed for Class I, Groups B, C, and D, Division 1. They are also suitable for the less stringent Division 2 environment. Class II locations are those which are hazardous because of the presence of combustible dust. All ASCO TRI-POINT explosion-proof enclosures are listed for Groups E, F, and G locations. The switch body and cover are die-cast copper-free* aluminum with a Buna N gasket. Two 3/4 conduit hubs with one plug are provided.

Dimensions (inches)
S-Series Pressure

With Types TD - TV Transducers

With Types TA - TC Transducers

1/4 NPT VENT CONNECTION ON DOUBLE CHAMBER TRANSDUCERS


3.5

ADDITIONAL SPACE REQUIRED FOR REMOVAL OF COVER


3.7

ADDITIONAL SPACE REQUIRED FOR REMOVAL OF COVER

3.5

2.2 1.5

1.6

2.3

1.03

1.03 1.6 2.3

3/4 NPT FOR CONDUIT CONN. BOTH ENDS


7.4

3/4 NPT FOR CONDUIT CONN. BOTH ENDS

7.5

1.0

11/32 DIA. FOR MOUNTING (2PLACES)


1.0

4.3

11/32 DIA. FOR MOUNTING (2PLACES)

4.1
2.2

3.2 3.7

4.06

1.7

1/4 NPT

1/4 OR 1/2 NPT


2.9
1

7.0

ON TV SERIES ADD 7/16" TO THESE DIMENSIONS


3.2 7.0

* Less than 0.6% copper.

15

S-SERIES Pressure Switches


How to Select and Order

(to 8000 psig)


Options Add appropriate suffix for desired option (see pages 34-35). Important Note: The third digit of each of the catalog numbers must be identical, e.g., SA 4 0D and TA 4 0A11.

123

ASCO S-Series switches consist of two components, the switch unit and the transducer unit.

Select transducer unit below

How to Select
1. Select the adjustable operating range based on desired actuation pressure. 2. Check that proof pressure is sufficient. 3. Read across and select the desired S-Series switch unit with the proper enclosure. 4. Continue across and select a matching transducer unit compatible with the fluid.

Select S-Series pressure switch


SA Switch Unit
Single-Stage Adjustable Deadband units allow independent adjustment of the set and reset points over the full operating range of the switch. The minimum difference between set and reset points is the deadband listed below; the maximum difference is the full range of the switch .

SA, SB, SC, SD and SE unit below


SC Switch Unit
Two-Stage Fixed Deadband units consist of two separate snap-action switches, each with an independently adjustable set point and non-adjustable reset point. The difference between the set and reset points of each switch is the deadband listed below; the minimum difference between the set points of the two switches is the separation.

SB, SD or SE Switch Unit


SB Switch Unit: Single-Stage Fixed Deadband units have an adjustable set point and a non-adjustable automatic reset point. SD Switch Unit: Manual reset on decreasing pressure units operate automatically on increasing pressure and must be reset manually on decreasing pressure. (To order, change second digit to letter D, e.g., S B 40D becomes S D 40D). SE Switch Unit: Manual reset on increasing pressure units operate automatically on decreasing pressure and must be reset manually on increasing pressure. (To order, change second digit to letter E, e.g., S B 40D becomes S E 40D).

Series TA-TC

Series TD-TQ

Standard connection is 1/4 NPT; (Optional 1/2 NPT add suffix B to catalog numbers TD thru TQ)

How to Order
Factory assembled Simply
order the switch and transducer unit by catalog number joined by a slash (/), e.g., SA40D/TA40A11. Field assembled Simply order the switch and transducer units separately by individual catalog number, e.g., one SA40D and one TA40A11.

Transducer Unit
These guage pressure type transducers provide for one pressure connection in the bottom of the transducer. They are diaphragm/piston type transducers using an elastomer in contact with the fluid, backed by a piston cylinder. This allows high sensitivity for low pressures and strength for high pressures. Explosion Proof

General Purpose

Specifications

Adjustable Deadband
Adjustable Deadband Maximum Full Scale General Watertight ExplosionPurpose Enclosure Proof Catalog No. Catalog No.

Fixed Deadband or Manual Reset

Two-Stage Fixed Deadband


Separation Air, Oil or Gas General Purpose Catalog No. Watertight Enclosure Catalog No. ExplosionProof Catalog No. Aluminum & Buna N Catalog No.

Transducer Units
Water, Air Oil or Gas Brass & Buna N Catalog No. Corrosive Fluids All 316 SS Catalog No. 316 SS & Viton 3 Catalog No.

Adjustable Operating Range (psig)

Proof Pressure (psig)

Minimum At Mid-Range Catalog (psig) 1 No.

Fixed Deadband At Mid-Range (psig) 1

General Watertight ExplosionPurpose Enclosure Proof Catalog No. Catalog No. Catalog No.

Fixed Deadband At Mid-Range (psig) 1

Maximum Full Scale Minimum At Mid-Range (psig) 1

0 - 12 W.C. 0 - 27 W.C. 0 - 65 W.C. 15 - 140 W.C. 15 - 250 W.C. 25 - 400 W.C. 0.4 - 4.5 0.7 - 9.0 0.8 - 9.0 1.0 - 18 1.0 - 18 1.5 - 36 2 - 60 5 - 60 3 - 100 5 - 120 5 - 200 6 - 200 13 - 300 15 - 400 30 - 600 50 - 1000 75 - 1500 200 - 3500 500 - 8000 16

25 25 25 40 40 40 100 100 150 100 150 150 150 3000 200 3000 3000 400 600 600 900 1500 2300 5000 9000
1

1.5 W.C. 2.0 W.C. 2.5 W.C. 6 W.C. 10 W.C. 15 W.C. 0.4 0.6 1.4 1.1 1.6 2.2 3.6 6.0 6.0 10 14 12 18 24 36 75 115 225 450

SA40D SA30D SA20D SA20D SA10D SA10D SA40D SA30D SA40D SA20D SA30D SA20D SA10D SA30D SA10D SA20D SA10D SA10D SA10D SA10D SA10D SA10D SA10D SA10D SA10D

SA41D SA31D SA21D SA21D SA11D SA11D SA41D SA31D SA41D SA21D SA31D SA21D SA11D SA31D SA11D SA21D SA11D SA11D SA11D SA11D SA11D SA11D SA11D SA11D SA11D

SA42D SA32D SA22D SA22D SA12D SA12D SA42D SA32D SA42D SA22D SA32D SA22D SA12D SA32D SA12D SA22D SA12D SA12D SA12D SA12D SA12D SA12D SA12D SA12D SA12D

1.0 W.C. 1.2 W.C. 1.4 W.C. 3 W.C. 6 W.C. 8 W.C. 0.3 0.3 0.8 0.4 1.0 0.9 1.5 4.0 2.5 5.0 6.0 5.0 8 10 15 30 45 125 275

SB40D SB30D SB20D SB20D SB10D SB10D SB40D SB30D SB40D SB20D SB30D SB20D SB10D SB30D SB10D SB20D SB10D SB10D SB10D SB10D SB10D SB10D SB10D SB10D SB10D

SB41D SB31D SB21D SB21D SB11D SB11D SB41D SB31D SB41D SB21D SB31D SB21D SB11D SB31D SB11D SB21D SB11D SB11D SB11D SB11D SB11D SB11D SB11D SB11D SB11D

SB42D SB32D SB22D SB22D SB12D SB12D SB42D SB32D SB42D SB22D SB32D SB22D SB12D SB32D SB12D SB22D SB12D SB12D SB12D SB12D SB12D SB12D SB12D SB12D SB12D

1.2 W.C. 1.4 W.C. 1.6 W.C. 4.0 W.C. 7.0 W.C. 13.0 W.C. 0.4 0.4 1.0 0.6 1.2 1.4 2.2 5.5 3.5 7.0 8.5 7.0 10 14 20 40 60 150 300
2

2.4 W.C. 2.7 W.C. 6.5 W.C. 14 W.C. 25 W.C. 40 W.C. 0.7 0.9 1.6 1.8 1.8 3.6 6 8 10 12 20 20 30 40 60 100 150 350 800

SC40D SC30D SC20D SC20D SC10D SC10D SC40D SC30D SC40D SC20D SC30D SC20D SC10D SC30D SC10D SC20D SC10D SC10D SC10D SC10D SC10D SC10D SC10D SC10D SC10D

SC41D SC31D SC21D SC21D SC11D SC11D SC41D SC31D SC41D SC21D SC31D SC21D SC11D SC31D SC11D SC21D SC11D SC11D SC11D SC11D SC11D SC11D SC11D SC11D SC11D
3

SC42D SC32D SC22D SC22D SC12D SC12D SC42D SC32D SC42D SC22D SC32D SC22D SC12D SC32D SC12D SC22D SC12D SC12D SC12D SC12D SC12D SC12D SC12D SC12D SC12D

TA40A11 TA30A11 TA20A11 TB20A11 TB10A11 TC10A11 TD40A11 TD30A11 --TD20A11 --TE20A11 TE10A11 --TF10A11 ----TG10A11 TH10A11 TJ10A11 -----------

------------TD40A21 TD30A21 --TD20A21 --TE20A21 TE10A21 --TF10A21 ----TG10A21 TH10A21 TJ10A21 TK10A21 TL10A21 TM10A21 TN10B21 ---

----------------TE40A44 --TE30A44 TE20A44 TE10A44 --TF10A44 ----TG10A44 TH10A44 TJ10A44 -----------

TA40A32 TA30A32 TA20A32 TB20A32 TB10A32 TC10A32 TD40A42 TD30A42 --TD20A42 --TE20A42 TE10A42 TG33A42 TF10A42 TG23A42 TG13A42 TG10A42 TH10A42 TJ10A42 TK10A42 TL10A42 TM10A42 TN10B42 TQ10B42 17

All switch units above are in stock for immediate delivery.


Values shown are nominal.

All switch units and transducer units above are in stock for immediate delivery.
316 SS transducers increase deadband by 50%. Transducers ending in 32 have 303 SS process connections, not 316 SS.

OPTIONS Pressure/Temperature Switches


H-Series, P-Series and S-Series Snap-Action Switch Options
Optional snap-action switches to meet specific electrical loads or application conditions are available on most ASCO TRI-POINT switch units. Generally, the construction of a switch unit with optional snap-action switches contains other specific parts and may be ordered only as a factory-built unit. To specify a particular optional construction, add the appropriate suffix to the switch unit catalog number, e.g., SA10D with optional gold contact snapaction switch (suffix P) would become SA10D P .

P-Series Switch Options


Panel Mount Open frame P-Series compact switch units are
available for panel mounting with the switch unit inside and the transducer outside. The panel separates the fluid sensing portion from the electromechanical portion. Five holes for bolts and operating stem must be drilled or punched through the panel. Three constructions are available: add the suffix listed below to the switch unit catalog number for the desired thickness.

Description

Electrical Rating

Catalog Suffix

Deadband Variation From Listing

Panel Thickness

Suffix

DC Rating 1 Amp Double Break

5 Amp, 125, 250 VAC 1/4 HP, 125 VAC 1/2 HP, 250 VAC 1 Amp, 125 VDC 1/2 Amp, 250 VDC 10 Amp, 125 VAC, VDC 1/8 HP, 125 VAC, VDC 5 Amp, 125, 250 VAC 1/8 HP, 125 VAC 1/4 HP, 250 VAC 1/2 Amp, 125 VDC 1/4 Amp, 250 VDC 1 Amp, 28 VAC 1 Amp, 28 VDC 25 Amp Res, 28 VDC 10 Amp Ind, 28 VDC 5 Amp Motor, 28 VDC 3 Amp Lamp, 28 VDC 1 Amp, 125 VAC 5 Amp, 125, 250 VAC 1/8 HP, 125 VAC 1/4 HP, 250 VAC 1/2 Amp, 125 VDC 1/4 Amp, 250 VDC 20 Amp, 125, 250 VAC 1 HP, 125 VAC 2 HP, 250 VAC 1/2 Amp, 125 VDC 1/4 Amp, 250 VDC 5 Amp, 125, 250 VAC 1/8 HP, 125 VAC 1/4 HP, 250 VAC 1/2 Amp, 125 VDC 1/4 Amp, 250 VDC 5 Amp, 125, 250 VAC 1/8 HP, 125 VAC 1/4 HP, 250 VAC 1/2 Amp, 125 VDC

DC Rating 10 Amps, SPDT Double-pole Double-throw (Two SPDT Switches with Common Lever) Gold Contact Dry Circuit SPDT Hermetically Sealed SPDT

SA: +50% SB, SC, PA: +100% H: +200% PB: +400% SA: +50% SB, SC, PA: +100% H: +120% PB: +400%

10 Ga (.135+.005) 14 Ga (.075+.005) 16 Ga (.060+.005)

10 11 12

SA, SB, SD, SE, PB: +50%

S-Series Switch Options


Industrial Adjusting Nut Covers
Available in clear plastic or metal to prevent tampering with set point adjusting nuts. Clear plastic cover: To order, add suffix 1 to the switch unit catalog number, or order separately as SP01. Metal cover: To order, add suffix 2 to the switch unit catalog number, or order separately as SP02. JIC Construction A switch unit having the electrical and adjusting nut covers attached to the switch body by a chain. Also designed to Type 13 specifications. To order, add suffix 3 to the switch unit catalog number, or order separately as SP03. Terminal Block Applicable to switch units with one single-poledouble-throw switch. The terminal strip is prewired to the snap-action switch. To order, add suffix 4 to the switch unit catalog number, or order separately as SP04. Factory Sealed Explosion-proof units may be ordered with a factory seal separating the electrical chamber from the conduit hubs and 24 long #14 AWG 105C. rated lead wires. To order, change the fourth digit of the switch unit catalog number from 2 to 3, e.g., SA1 2 D becomes SA1 3 D.

SA, SB, SC, PA: +25% H: +50% PB, PC: +100% SA, PA: +100% H: +200% PB: +600%

High Ambient 250F SPDT

SA, SB, SC: +25%

High Power 1 HP SPDT Moisture Resistant Sealed Switch SPDT Tight Fixed Deadband SPDT

SA: +50% SB, SC: +100% PB: +400%

SA: None SB, SC, PA: +25% PB, H: +50%

SB, SC: -50%

34

123

Pressure Transducer Options


Special Wetted Materials The following diaphragms may
be substituted on transducer body materials of aluminum, brass, polyester and stainless steel. To order, substitute the material code below in the seventh digit of the transducer catalog number, e.g., a TF10A1 1 with optional viton diaphragm becomes a TF10A1 2 .
Material Code

Pressure Snubbers A pressure snubber (1/4 NPTF by 1/4 NPTM) installed in the transducer pressure connection will dampen the pressure spikes to a value which will not cause damage. It consists of a body with a porous metal disc of stainless steel through which the fluid passes. To order, select a snubber compatible with the fluid. Available by seperate catalog number only (see table below).
Brass 303 SS Catalog No. Catalog No.

Diaphragm

Temperature Range

Buna N Ethylene Propylene Neoprene Fluorosilicone Viton

1 6 3 7 2

-4F (-20C) to 180F (82C) -4F (-20C) to 250F (121C) -4F (-20C) to 180F (82C) -40F (-40C) to 250F (121C) -4F (-20C) to 250F (121C)

Fluid

Air, Non-Hazardous Gases Water, Light Oil (under 225 SSU) Oil (Heavy, (over 225 SSU) Pressure Rating (psig)

TP04G2 TP04E2 TP04D2 2000

TP04G3 TP04E3 TP04D3 5000

Oxygen Cleaning Pressure transducers for oxygen service should be specially cleaned. They are degreased and blacklight inspected, then assembled in a clean area and tested with oil-free air or nitrogen. Use metal body transducer with viton or neoprene diaphragm and add suffix H to transducer catalog number, e.g., TA40A13 becomes TA40A13 H .

Process Connection A female process connection (1/4


NPT) is standard on all pressure transducers. A 1/2 NPT is available as an option on gauge pressure transducers. To order, add suffix B to transducer catalog number, e.g., RF10A21 becomes RF10A21 B . Note: Not available on nylon transducers.

P-Series and S-Series Temperature Transducer Options


Armored Capillaries Double braided copper armor is standard for copper capillary units. Stainless steel spiral interlocked armor is available for stainless steel capillary units. Add suffix C to transducer catalog number. Longer Capillaries Standard copper and stainless steel
capillary units can be furnished in 12 lengths. To order, add suffix D to transducer catalog number. Consult ASCO for longer length capillaries.
Capillary Length (Feet) Bulb Length (Inches) U Dimension Required (Inches)

Thermal Well

Transducer Suffix

Thermal Well 1 Use with direct or remote sensors for


protecting sensing bulb. This allows removal of bulb while maintaining a pressure-tight vessel. Available in 1/2 NPT or 3/4 NPT process connection in brass or 316 SS. Dimensions are in accordance with SAMA Std. RC17-9. Standard U dimension (insertion length) is 2-1/2 for direct mount and 6 capillary units and is 4-1/2 for 12 capillary units.
Process Connection Pressure Rating (psig) U 1/2 NPT 3/4 NPT Dimensions (Inches) Catalog No. Catalog No.

6 12 13 - 20 21 - 50 51 - 80

--D E F G

3-1/2 5-1/2 5-1/2 8-1/2 11-1/2

2-1/2 4-1/2 4-1/2 7-1/2 10-1/2

Union Connector For use with remote units for mounting


of bulb in fluid being controlled. Available in 1/2 NPT and 3/4 NPT process connections in brass or 316 SS.

Material

Brass

1000

316 SS

6000

2-1/2 4-1/2 7-1/2 10-1/2 2-1/2 4-1/2 7-1/2 10-1/2

QP03 QP13 QP23 QP33 QP07 QP17 QP27 QP37

QP04 QP14 QP24 QP34 QP08 QP18 QP28 QP38

Process Connection Pressure Rating (psig) 1/2 NPT Catalog No. 3/4 NPT Catalog No.

Material

Brass 316 SS

500 1500

QP01 QP05

QP02 ---

Jam nuts provided with thermal wells.

35

Definitions and Fluid Compatibility Guide


Definitions
Accuracy The maximum deviation from the set point under specified operating condition (ambient temperature, barometric pressure, etc.). Adjustable Deadband Refers to the capability of a pressure or temperature switch to allow the deadband to be adjusted over a given range. Certain ASCO TRI-POINT switches have an adjustable deadband which can be adjusted over the total operating range of the switch. Adjustable Operating Range The pressure or temperature range of the switch within which the set point may be adjusted. Differential Pressure The difference between two pressures. A differential pressure switch senses two pressure sources and can be adjusted to actuate on a desired difference between them. Guage Pressure The actual reading of a typical pressure guage and is the difference between the pressure within a vessel and the atmospheric pressure surrounding it. It is normally measured in pounds per square inch (psig). Manual Reset The switch is a semi-automatic device which operates automatically with a signal change in one direction but must be manually reset once the signal returns to its original position. Proof Pressure A pressure which a device can be subjected to for extended periods of time without changes in its operating characteristics. Rated Overrange Temperature A temperature which a device can be subjected to for extended periods of time without changes in its operating characteristics. Repeatability The closeness of agreement among a number of consecutive measurements of the output for the same value of input under the same operating conditions approaching from the same direction. Repeatability is normally specified as a percentage of the upper limit of the operating range. Example: Operating range 5-100 psig with +1% repeatability; equals +1% of 100 psig or +1 psig. Reset Point After a pressure or temperature switch has reached its set point and operated the electrical switch, it must return to a point called the reset point before the electrical switch can return to its original position. Set Point The pressure reading at which the electrical switch element changes contact position (it can be specified either increasing or decreasing). 36 Switch Unit ASCO uses the term switch unit to describe the electromechanical portion of a pressure or temperature switch. This is used in conjunction with a transducer unit to form a complete pressure or temperature switch. Transducer Unit ASCO uses the term transducer unit to describe that portion of a pressure or temperature switch to which a pressure or temperature is applied which converts the input signal to another form of energy to operate the switch unit. Two-Stage (Dual) ASCO uses the term two stage to describe a pressure or temperature switch which is equivalent to two pressure or temperature switches which are independently adjustable. This switch is equivalent to two fixed deadband switches. Deadbands The deadband is the difference between the set point and reset point readings. Deadbands are listed in the specification tables at nominal values. They are representative of the deadbands of the units at the middle of the range. The deadband values for the full range adjustable deadband switches and limited adjustable deadband switches indicate the values through which the deadband may be adjusted. Generally, as the set point is adjusted through the operating range, the deadband will vary. Normally, it will become narrower as the set point is towards the bottom of the range, and will become wider when the set point is towards the top of the range. The graph shown below indicates representative trends of this type of deadband variation.

Deadbands
1.5 x Catalog Value Catalog Value Half Catalog Value

Bottom

Mid

Top

Position of Set Point in Range Temperature switch deadbands are a result of the characteristics of the vapor pressure curve as well as other factors. Normally, this results in a deadband which is narrower in the top third of the range than in the bottom third of the range. The values published are nominal and representative of midrange set points.

4
These recommendations are to be used as a guide only, as service life of material is dependent on temperature, concentrations, or catalysts that may be added and other conditions which are beyond our control. Consult ASCO for specific service applications.
Note: Items in black circles are standard catalog units. All others available on factory order. P - Indicates preferred construction. S - Indicates satisfactory construction.

123

Fluid Compatibility Guide


Transducer Material Code of Two Digits represents process connection material and diaphragm material, respectively; these are the sixth and seventh positions of the pressure transducer catalog number.
Process Connection: 6th Position 1 Aluminum 2 Brass 3 303 S.S. 4 316 S.S. 7 Nylon/Brass Diaphragm: 7th Position 1 Buna N 2 Viton 3 Neoprene 4 316 S.S. 6 Ethylene Propylene 7 Fluorosilicone

Material Code Vacuum Inches of Water P.S.I.G. 5 to


Acetic Acid Acetylene Air Ammonia Argon-Welding Butane Carbon Tetrachloride Cellulube Coke Oven Gas Ethyl Alcohol (denatured) Ethylene Glycol Freon Refrigerants Freon Solvents (MF, TF, BF) Fuel Oils and Diesel Gasoline Gas, Inert Gas (natural and manufactured) Helium Hydrogen Jet Fuel (JP1 to JP6) Kerosene Methyl Alcohol (Methanol) Naphtha Nitrogen Oils (coolant, hydraulic, lubricating and motor) Oxygen, Gaseous Potassium Sulfate Propane Gas and Liquid Pydraul (Monsanto) Steam
3 2 4 4 1

11 12 13 16 17 21 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes No 400 400 400 400 400 3500
P P P P S S S P S P P P S S S S S S S

22 Yes No 3500

23 Yes No 3500

26 Yes No 3500

27 Yes No 3500

31 Yes Yes 8000


S S S S

32 Yes Yes 8000


S S S S S P S P S S

33 Yes Yes 8000


S

36 Yes Yes 8000


S S S S

37 Yes Yes 8000

42 Yes Yes 8000


S S S S S P S P S S

44 No No 400
P S S P S S S S S S S S P S S P S S S S S S S S S S S S S S S S S S S P S S S

71 No No 200

Ranges Available

S S

S S

S S S

S S S S S

S S

S S

S S

S S

S S

P P

Benzene-Benzol

S S S S S S

S S S S S S S S

S S S S S S

S S

P P P P P P P P P P P S S S S S P S S S S S S S P P S S S S S P P S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S

S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S

S S S S S S S S S S S

S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S

S S S S S S S S S S S S S S S S S S S S S S S S

P P

P P

S S

S S S S S S S S P

Steam Condensate Stoddard Solvent Toluene (Tolulo) Vacuum Vegetable Oil Vinegar Water, Fresh, Boiler Feed Water (Distilled, Deionized, Demineralized) Water, Sea

S S

S S

P P P

S P S S

S S

S S S

S S S S S

Notes: 1 For high purity applications use stainless steel transducers. 2 Oxygen service requires special cleaning, specify suffix H. 3 For steam service a condensate loop (pigtail) is required. 4 For pressure transducers for combustion service see pages 20-23. 5 Material availability refers to standard gauge pressure constructions only.