CSM_E5_N_E5_N-H_operation_TG_E_3_3
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some parameters are not displayed depending on the protect level setting and the conditions of use. Control stops when you move from the operation level to the initial setting level.
Operation Level
a-m
Manual mode
Press the O Key for at least 3 s while a-m is displayed. (a-m will flash after 1st second.)
*3
PF Key
*5
Press the O+ M Keys for at least 3 s. (Display will flash after 1st second.)
25
100
*5 *4
c
25
100
Press the O Key for at least 3 s. (Display will flash after 1st second.)
Protect Level
Note: The time taken to move to the protect level can be adjusted by changing the Move to protect level time setting.
*1
Control stops.
Advanced Function Setting Level Control in progress Input password. Control stopped Calibration Level Not displayed for some models
*2
Level change *1. You can return to the operation level by executing a software reset. *2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel. It can be done only by first turning OFF the power. *3. From the manual control level, key operations can be used to move to the operation level only. *4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/E5EN). *5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/E5EN).
OFF
OFF
Note: If the input value exceeds the display limit (-1999 to 9999), though it is within the control range, will be displayed under -1999 and above 9999. Under these conditions, control output and alarm output will operate normally. For details on the control range, refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156). * Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status.
Operation Level
a-m
Press the O Key for at least 3 s while a-m is displayed. (a-m will flash after 1st second.)
Press the O Key less than 1 s. Press the O Key less than 1 s.
Adjustment Level
Press the O Key less than 1 s.
Manual mode
*3
Press the O + M Keys for at least 3 s. (Display will flash after 1st second.)
25.0
100.0
PF Key *5
Protect Level
Note: The time taken to move to the protect level can be adjusted by changing the Move to protect level time setting.
*5 Press the O Key for at least 3 s. (Display will flash after 1st second.)
25.0
100.0
Control stops.
Input password while amov is displayed. (Set value 169) Advanced Function Setting Level Input password.
*2
Calibration Level
*1. You can return to the operation level by executing a software reset. *2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel. It can be done only by first turning OFF the power. *3. From the manual control level, key operations can be used to move to the operation level only. *4. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H). *5. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H).
OFF
OFF
Note: If the input value exceeds the display limit (-19999 to 32400), though it is within the control range, will be displayed under -19999 and above 32400. Under these conditions, control output and alarm output will operate normally. For details on the control range, refer to the E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157). * Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status.
Operation Level
a-m
Press the O Key for at least 3 s while a-m is displayed. (a-m will flash after 1st second.)
Press the O Key less than 1 s. Press the O Key less than 1 s.
Manual mode
Adjustment Level
Press the O + M Keys for at least 3 s. (Display will flash after 1st second.)
25.0
100.0
Protect Level
Note: The time taken to move to the protect level can be adjusted by changing the Move to protect level time setting.
25.0
100.0
Press the O Key for at least 3 s. (Display will flash after 1st second.)
Control stops.
Initial Setting Level Press the O Key for at least 1 s. Advanced Function Setting Level
Input password.
Calibration Level
*1. You can return to the operation level by executing a software reset. *2. It is not possible to move to other levels from the calibration level by operating the keys on the front panel. It can be done only by first turning OFF the power. *3. From the manual control level, key operations can be used to move to the operation level only. *4. When the PF Setting parameter is set to A-M. For the E5CN-HT, press the M+U Keys at the same time to implement the PF Key. *5. When the PF Setting parameter is set to PFDP. For the E5CN-HT, press the M+U Keys at the same time to implement the PF Key.
OFF
OFF
Note: If the input value exceeds the display limit (-19999 to 32400), though it is within the control range, will be displayed under -19999 and above 32400. Under these conditions, control output and alarm output will operate normally. For details on the control range, refer to the E5CN-HT/E5AN-HT/E5EN-HT Digital Controllers User's Manual Programmable Type (Cat. No. H169). * Errors are shown only when the display is PV, PV/SV, or PV/MV. Errors are not shown for any other status.
Power ON
Starting in automatic mode.
PF Key *2 Press the O Key for at least 3 s. Other than the Auto/Manual Switch display
Adjustment Level
Operation Level
Press the O Key less than 1 s.
C
M in-h
100
25
l.adj M at
off
Adjustment Level Display Displayed only once when entering adjustment level.
r-s RUN/STOP
run
AT Execute/Cancel
1-point shift M Set either insh Upper Limit of these Temperature 2-point shift M insl Lower Limit Temperature
M dp M d-u
C
Decimal Point
m-sp
0
M sl-h
1300
M p Proportional Band
8.0
M sl-l
-200
M i
233
M al2h
0
M d
40
M ct2
0.0
M s-hc
stnd
Standard or Heating/Cooling
M ct2
0.0
M st ST (Self-tuning)
on
M hb2
0.0
0.0
M ptrn M
20
Program Pattern
M oc2
50.0
M of-r
C
50.0 stabilization of P or PD
M lcr1
0.0 0.0
M o MV Monitor (Heating)
0.0
M hs1
50.0
HS Alarm 1
M lcr2
0.0
M
Press the O and M Keys for at least 3 s. Press the O and M Keys for at least 1 s. Press the O Key less than 1 s.
M hs2
50.0
C
HS Alarm 2
M wt-b
off
M alt1
2
C
Alarm 1 Type
Wait Band
Protect Level
Note: The time taken to move to the protect level can be adjusted by changing the "Move to protect level time" setting.
M sp-0
0
SP 0
M mv-s
0.0
M alh1
0.2
Alarm 1 Hysteresis
MV at Stop
M sp-1
0
SP 1 SP used by multi-SP SP 2
M mv-e
0.0
C
pmov
MV at PV Error
Move to Protect Level: Displayed only when a password 0 is set. Restricts moving to protect level.
M sp-2
0
Operation/Adjustment Protect: oapt Restricts displaying and modifying menus in operation, 0 adjustment, and manual control levels.
and Modbus.
M sp-3 SP 3
0
M ol-h
105.0
M Initial Setting/ icpt Communications Protect: movement This protect level restricts
1 to the initial setting, communications
M ol-l
-5.0
MV Lower Limit
M levels. wtpt Setting Change Protect: by Protects changes to setups M pfpt PF Key Protect operation Restricts PF key
off (E5AN/E5EN only)
*1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/E5EN). *2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/E5EN).
M
sqrp
0.0
Extraction of Square Root Low-cut Point
M sdwt
20
(E5AN/E5EN only)
Monitor/Setting Item Display 2
PF
25
0
PF
PF
PF
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).
alt2
2
C
Alarm 2 Type
hsu
on
HS Alarm Use
pf
a-m
M spru
M alh3
0.2
Alarm 3 Hysteresis
M tr-h
100.0
M sb1n
n-o
M sb2n
n-o
M pfd5
0
Monitor/Setting Item 5
M sb3n
n-o
M spdp
4
M hbu
on
HB ON/OFF
M out2
none
M ev-1
none
M sub1
alm1
M ev-2
stop
M sub2
alm2
M sub3
alm3
M alfa
0.65
M protect is set to 0.
setting/communications
M at-h AT Hysteresis
0.8
M ra2m M ra1
0 Monitor
M csca
off
M o-dp
off
MV Display
M rt RT
off
M och
0.1
Power ON
Manual Control Level
Protect Level
Operation Level
Adjustment Level
2 PID2
d.bnk Bank1
1
d.pid
3 PID3
d.bnk d.bnk
2 2 Bank2
d.pid
8
PID8
d.bnk Bank7
7
M
c
1.p
8.0
c
M 8.p
8.0 PID 8 Proportional Band
c
M 0.lsp
0.0
c
M
c
233.0
M 0.pid
1
c
0.0
7.lsp
0.0
Bank 7 SP
c
M
0.a2l
0.0
7.a-2
M 1.d
40.0
M 7.pid
1 Bank 7 PID Set No.
c
Bank 7 0.0 Alarm Value 2 Bank 7 Alarm Value 0.0 Upper Limit 2
M 1.olh
105.0
M 8.d
40.0
M
7.a 2h
M 0.spr
off
c
M 0.a-3
0.0
c
-5.0
M
c
M 8.oll
-5.0
M 0.a1h
0.0
c
0.0
Bank 7 0.0 Alarm Value 1 Bank 7 Alarm Value 0.0 Upper Limit 1
M
0.a3l
0.0
c
1.aut
1320.0
c
M 1.csc
1.00
M 8.aut M 8.csc
1.00
M
c
M 7.a1h M
0.a 1l
0.0
M 0.sok
1
M
c
7.a 1l M
M 1.lba
0
0.a-2
0.0
c
M
0.wtb
off
M 8.lba
0
M
c
M 7.sok
1
M 7.wtb
off
M 1.oll
105.0
M 8.olh
M
c
M 7.spr M 7.a-1
M
c
0.a-1
M 0.a3h
7.a2l
M 1.i
0.a 2h
Power ON
Starting in manual mode.
*1
Adjustment Level
Operation Level
l.adj M at
off
AT Execute/Cancel
M i
233.0
25.0
al-1
0.0
Alarm Value 1
M cmwt M irda
off
Communications off Writing
M d
40.0
M a-m
Press the O Key for at least 3 s.
Auto/Manual Switch PID control only. Added when auto/manual select addition is ON. Bank No.
c
M al1h
Alarm Value
M bank
0
M spmd
lsp
SP Mode
M c-db
0.0
Heating/cooling
c
M rsp
0.0
Remote SP Monitor
c
al-2
0.0
Dead Band
Alarm Value 2
M
Heater Current 1
M
Manual Reset Value Clear the offset during control.
M
c
of-r
sp-m
Alarm Value
Adjustment Level Display Displayed only once when entering adjustment level.
c c
25.0 M
p
8.0
Proportional Band
r-s RUN/STOP
run
50.0 stabilization of P or PD
0.0 SP Ramp
Heater Burnout
M hys
1.0
M ct1
Heater Current 1 Value
c
0.0 Detection 1
0.0 Monitor
M chys
M ct2
c
Alarm Value 3
Heater Current 2
M soak
1
M
Soak Time
lcr1
Leakage Current 1
0.0 Monitor
M wt-b
off
M
Wait Band
lcr2
Leakage Current 2
0.0 Monitor
M oc2
50.0
M
Heater Overcurrent Detection 2
M
MV at Stop
mv-s
0.0
MV Monitor (Heating)
M lcr1
Leakage Current 1 0.0 Monitor
M mv-e
0.0
MV at PV Error
M c-o
0.0
MV Monitor (Cooling)
M hs1
50.0
M sprt
HS Alarm 1
M
SP Ramp Set Value
M v-m
0.0
Valve Opening Monitor
off
M lcr2
0.0
M ol-h
105.0
M
MV Upper Limit
M hs2
50.0
M ol-l
HS Alarm 2
-5.0
MV Lower Limit
M
c
ins
0.00
M orl
Temperature Input Shift 1-point shift Set either of these parameters.
PF Key *2
MV Change Rate Limit
0.0
(E5AN-H/E5EN-H only)
M
c
M
db
2.0
Position Proportional Dead Band Monitor/Setting Item Display 2
PF
insh
Upper Limit Temperature 0.00 Input Shift Value 2-point shift M Lower Limit Temperature Input Shift Value
M oc-h
0.8
Open/Close Hysteresis
insl
0.00
M sqrp M
PF
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).
PF Key *2
*1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN-H/E5EN-H). *2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN-H/E5EN-H).
Press the O Key for at least 1 s. Press the O Key for at least 3 s. Other than the Auto/Manual Switch display
Protect Level
The time taken to move to the protect level can be adjusted by changing the "Move to protect level time" setting. Level: pmov Move to Protectwhen a password Displayed only
in-t
5
Input Type
alt2
2
Alarm 2 Type
M
in-h
100
Scaling Upper Limit
c
level.
Protocol Setting: psel Switches between cwf CompoWay/F (SYSWAY) and Modbus.
M alh2
0.2
Alarm 2 Hysteresis
Operation/Adjustment Protect:
M
1
M in-l
0
M
alt3
2
Alarm 3 Type
M
dp
Decimal Point
c
icpt M wtpt M
Communications Baud Rate 9.6 CompoWay/F (SYSWAY) only Communications Data Length
c
M
d-u
c
Temperature Unit C, F For input type of temperature SP Upper Limit
M alh3
0.2
Alarm 3 Hysteresis
M
tr-t Transfer Output Type
off
Linear output
Setting Change Protect: Protects changes to setups off by operating the front panel keys. PF Key Protect Restricts PF key operation
M
sl-h
1300.0
pfpt M
M sbit
2
Communications Stop Bits
c
M
tr-h
100.0
Transfer Output Upper Limit
M
tr-l
0.0
Transfer Output Lower Limit
-200.0
M prlp
Password to Move to Protect Level: 0 Password setting
M sdwt
20
Send Data Wait Time
M o1-t
4-20
M s-hc
stnd
Standard or Heating/Cooling
M
ev-b
1
Bank Numbers Used
M st
on
ST (Self-tuning)
For input type of temperature, standard control, or PID Program Pattern
M
ev-1
none
Event Input Assignment 1
M ptrn
off
M
ev-2 Event Input 2 Assignment
stop
M
pbnk
7
Valid Program Bank When assigning PID or control output to ON/OFF output Control Period (Heating) Set the ON/OFF output cycle. Control Period (Cooling)
M
ev-3
none
Event Input Assignment 3
M
cp
20
M
ev-4
none
Event Input Assignment 4
M
c-cp
20
M
clfl
flot
Closed/Floating
M
calb
off
Motor Calibration
M
alt1
2
Alarm 1 Type
M
c
M mot
30
Travel Time
alh1
Alarm 1
0.2 Hysteresis
M sqr
off
Power ON
Manual Control Level
Protect Level
Operation Level
Adjustment Level
init
off
Parameter Initialization
o-dp
off
MV Display
istp
ins1
alsp
sp-m
Alarm SP Selection
pfd1
1
Monitor/Setting Item 1
M
spru
m
SP Ramp Time Unit
M
ret Automatic Display Return Time
off
M
mvse
off
MV at Stop and Error Addition
M
rspu
off
Remote SP Enable
M
pfd2
0
Monitor/Setting Item 2
M
rest
a
Standby Sequence Reset
M
a1lt Alarm 1 Latch
off
M
amad
on
Auto/Manual Select Addition
c
M
rsph
1300.0
Remote SP Upper Limit
M
pfd3
0
Monitor/Setting Item 3
M
sb1n
Auxiliary Output 1
M
a2lt
off
Alarm 2 Latch
M
rt
off
RT
c
M
rspl
-200.0
Remote SP Lower Limit
M
pfd4
0
Monitor/Setting Item 4
M
sb2n
Auxiliary Output 2
M
a3lt
off
Alarm 3 Latch
M
hsu
on
HS Alarm Use
M
sptr
off
SP Tracking
M
pfd5
0
Monitor/Setting Item 5
M
sb3n
n-o
Auxiliary Output 3 Open in Alarm
M
prlt Move to Protect Level
3
Time
M
hsl HS Alarm Latch
off
M
rseo
off
Remote SP Input Error Output
M
spdp
"PV/SP" Display
4 Screen Selection
M
hbu
on
HB ON/OFF
M
sero
off
Input Error Output
M
hsh
0.1
HS Alarm Hysteresis
M
pidi
pv
PID Set Automatic Selection Data
M
odsl MV Display Selection
o
M
hbl Heater Burnout Latch
off
M
cjc
Cold Junction
M
lba
0
LBA Detection Time
M
pidh
0.50
PID Set Automatic Selection Hysteresis
M
pvdp
on
PV Decimal Point Display
on Compensation Method
M
hbh
0.1
Heater Burnout Hysteresis
M
rlrv
off
MB Command Logic Switching
c
M
lbal
8.0
LBA Level
c
M
p-db
0.0
PV Dead Band
M
pvst
off
PV Status Display Function
M
c
M
ST Stable Range
M
PV Change Color
c
M
LBA Band
M
Manual MV Limit Enable
st-b
15.0
colr
red
lbab
3.0
manl
off
svst
off
M
alfa
0.65
c
M
pv-b
5.0
PV Stable Band
M
out1
o
Control Output 1 Assignment
M
pmvd
Direct Setting of
M
d.ref
0.25
Display Refresh Period
M
at-g
1.0
AT Calculated Gain
M
a1on
0
Alarm 1 ON Delay
M
out2
none
Control Output 2 Assignment
M
pvrp
PV Rate of Change
M
ra1m
0 Monitor
Control Output 1 ON/OFF Count
17 Calculation Period
M
c
M
AT Hysteresis
M
Alarm 2 ON Delay
M
Auxiliary Output 1 Assignment
M
Automatic Cooling
at-h
0.8
a2on
0
sub1
alm1
csca
ra2m
M
lcma
20.0
Limit Cycle MV Amplitude
M
a3on
0
Alarm 3 ON Delay
M
sub2
alm2
Auxiliary Output 2 Assignment
M
ocu
on
Heater Overcurrent Use
0 Monitor
M
ra1
0 Alarm Set Value
Control Output 1 ON/OFF Count
M
inf
0.0
Input Digital Filter
M
a1of Alarm 1 OFF Delay
0 0
M
sub3
alm3
Auxiliary Output 3 Assignment (E5AN/E5EN-H only)
M
ocl
Heater Overcurrent
M
ra2
Control Output 2 ON/OFF Count
off Latch
M
pvad
off
Additional PV Display
M
a2of Alarm 2 OFF Delay
0
M
csel
on
Character Select
M
och
0.1
Heater Overcurrent Hysteresis
M
rac ON/OFF Counter Reset
0
M
a3of
0
Alarm 3 OFF Delay
M
t-u
m
Soak Time Unit
M
pf
a-m
PF Setting
M
cmov
0
Move to Calibration Level
Power ON
Manual Control Level
Protect Level
Operation Level
Adjustment Level
Adjustment Level
Press the O Key less than 1 s. Press the O Key less than 1 s.
Adjustment Level Display Displayed only once when entering adjustment level.
l.adj M at
off
mv-e
0.0
MV at PV Error
hs2
50 0 .
HS Alarm 2
M ol-h
MV Upper Limit
105 0 .
AT Execute/ Cancel
2 PID2
M cmwt
off
M ins
0.00
Communications Writing
d.pid
3 PID3
M insh
1-point shift Set either Upper Limit of these Temperature 0.00 Input Shift Value parameters M 2-point shift
0.00
PID8
M
c
M spmd
psp
SP Mode
c
1.p
8.0
c
M 8.p
8.0
M fsp
0.0
M p Proportional Band
8.0
M db Position Proportional
2.0 Dead Band
Fixed SP
M 1.i
233.0
M 1.d
40.0
M ct1
0.0
M i
233 0 .
M oc-h
0.8
Open/Close Hysteresis
M 1.olh
105.0
M hb1
0.0
M d
40.0
M stb
0.00
M 8.ol h
105.0
Standby Time
M 1.oll
-5.0
M
c
M 8.ol l
-5.0
M ps0
-200.0
M of-r
Manual Reset Value Clear the offset during 50.0 stabilization of P or PD control. Hysteresis (Heating) Hysteresis settings Hysteresis (Cooling)
1.aut
1320.0
c
M 8.aut
PID 8 Automatic Selection 1320.0 Range Upper Limit
M hb2 M oc2
M 1.csc
1.00
M hys
M ps1
-200.0
1.0
M ps10
-200.0
M 1.lba
0
M chys
1.0
M bc0
0
Monitor
M hs1
50 0 .
M wt-b
off
Wait Band
HS Alarm 1
M mv-r
0.0
bc1
MV at Reset
0
M bc10
0
10
Power ON
Starting in manual mode.
25 .0 Control
100.0 only
PID
PV/MV
Operation Level
Operation Level
d.prg
7
25.0
PV
ct 2
Heater Current 2
s-n o
M 25.0 PV/SP
0.0
M lcr 1
(See note.)
M a-m Auto/Manual
Switch
M lcr 2 M r-r
M prg
0
Program Number
pid
1 M
c
styp
Alarm Value 1
c
Segment n Format
rst
al-1
0.0 M
ramp M
M
Segment n SP
0.0
M o MV Monitor (Heating)
sp
Hold
Hold
Ral1h
0.0 M
0.0 M 0.0 M
Segment n Ramp Rate
off
Advance
Rpr
M adv
off
M stb m
Remaining Standby
0.0 Monitor
Ra l1 l
c
time
0.00 M
Segment n Time
al-2
Alarm Value 2
Ral2h Ral2l
0.0 M 0.0 M
lin k
end M
M rptm
c
Program Execution
0 Repetition Monitor
ts1 s on1
Time Signal 1
0 Set Segment M
Time Signal 1 ON Time
al-3
Alarm Value 3
ct1
Heater Current 1
0.00 M
M
Time Signal 1
Ral3h
M
c
0.0
of1
al3l
M
0.0
ts2s
0 M
Rrp t
Program Repetitions
on2
0.0 0 M
of2
0.00
PF Key *2
(E5AN/EN-HT only)
PF
PF
PF
Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).
PF Key *2
*1. When the PF Setting parameter is set to A-M for a Controller with a PF Key (E5AN/EN-HT). *2. When the PF Setting parameter is set to PFDP for a Controller with a PF Key (E5AN/EN-HT).
11
Press the O Key for at least 1 s. Press the O Key for at least 3 s. Other than the Auto/Manual Switch display
Protect Level
The time taken to move to the protect level can be adjusted by changing the "Move to protect level time" setting. Level: pmov Move to Protectwhen a password Displayed only is set. Restricts moving to protect
in-t
5 M
Input Type
tr-h
100.0 M
0 M
level.
in-h
100 M
tr-l
0.0 M
M
1
u-no
in-l
0 M 0
oapt Protect
0 M 0
Operation/Adjustment
o1-t
4-20 M
M bps
9.6
dp
M
Decimal Point
icpt
M
M len
7
ev-1
none M
M
Setting Change Protect
d-u
c
Communications Stop Bits
c
Temperature Unit
ev-2
none M
wtpt
off M off M
sbit
2
sl-h
1300.0 M
SP Upper Limit
ev-3
none M
M sdwt
20
sl-l
-200.0 M
SP Lower Limit
clfl Closed/Floating
flot M
Password to Move to
s-hc
stnd M
Standard or Heating/Cooling
calb
off M
Motor Calibration
cp
20 M
mot
Control Period (Cooling)
Travel Time
30 M
c-cp
M
sqr
off M
20
Tt-u
h-m M
alt1
2 M
c
Alarm 1 Type
time M
Alarm 1 Hysteresis
alh1
0.2 M
pru
m M
alt2
2 M
c
Alarm 2 Type
alh2
0.2 M
Alarm 2 Hysteresis
p-on
cont M
alt3
2 M
c
Alarm 3 Type
eset
rst M
alh3
0.2 M
Alarm 3 Hysteresis
pvst PV Start
sp M
tr-t
off M
amov
0 M
12
Power ON
Manual Control Level
Protect Level
Operation Level
Adjustment Level
init
off M
Parameter Initialization
cjc
on M
sub1
alm1 M
pfd1
1 M
Monitor/Setting Item 1
rest
a M
colr
red M
c
sub2
alm 2 M
pfd2
0 M
Monitor/Setting Item 2
sb1n
n-o M
pv-b
5.0 M
PV Stable Band
sub3
M
pfd3
0 M
Monitor/Setting Item 3
sb2n
n-o M n-o M
a1on
0 M
Alarm 1 ON Delay
csel
on M
Character Select
pfd4
0 M
Monitor/Setting Item 4
sb3n hbu
on M
alsp
sp- m M
Alarm SP Selection
pfd5
0 M
Monitor/Setting Item 5
HB ON/OFF
a3on
0 M
Alarm 3 ON Delay
rspu
off M
Remote SP Enable
spdp
3 M
hbl
off M
a1of
0 M
rsph
1300 .0 M
odsl
o M
MV Display Selection
hbh
0.1 M
a2of
0 M
rspl
- .0 200 M
pvdp
on M
alfa
0.65 M
a3of
0 M
sptr
off M
SP Tracking
pvst
off M
at-g
1.0 M
c
AT Calculated Gain
istp
ins1 M
rseo
off M
svst
off M
at-h
0.8 M
AT Hysteresis
pidi
pv M
d.ref
0.25 M
lcma
20.0 M
amad
on M
pidh
0.50 M
ra1m
0 M
Control Output 1 ON/OFF Count Monitor Control Output 2 ON/OFF Count Monitor Control Output 1 ON/OFF Count Alarm Set Value Control Output 2 ON/OFF Count Alarm Set Value ON/OFF Counter Reset
inf
0.0 M
rt
off M
RT
p-db
0.0 M
PV Dead Band
ra2m
0 M
pvad
off M
Additional PV Display
hsu
on M
HS Alarm Use
manl
off M
ra1
0 M
o-dp
off M
MV Display
pmvd
off M
ra2
0 M
ret
off M
hsh
0.1 M
HS Alarm Hysteresis
pvrp
M
PV Rate of Change
17 Calculation Period
Automatic Cooling Coefficient Adjustment
rac
0 M
lba
0 M
c
csca
off M
pend
0.0 M
a2lt
off M
Alarm 2 Latch
ocu
M
Heater Overcurrent
s-u
h-m M
on Use
Heater Overcurrent Latch
a3lt
off M
Alarm 3 Latch
lbab
3.0 M
ocl
off M
psad
off M
prlt
3 M
out1
o M
och
M
Heater Overcurrent
0.1 Hysteresis
PF Setting
rcad
off M
sero
off M
out2
none M
pf
r-r M
cmov
0 M
13