Documenti di Didattica
Documenti di Professioni
Documenti di Cultura
MEDIUM VOLTAGE
19000/33000V
CABLE DESCRIPTION
1.CONDUCTOR
Compact circular stranded copper conductor complying with BS6360 Class 2.
CONDUCTOR SCREEN
Extruded semi-conducting compound bonded to the insulation and applied in the same operation as the insulation.
2.INSULATION
Extruded cross-linked polyethylene (XLPE) suitable for operation at a conductor temperature of 90C.
3.INSULATION SCREEN
Extruded semi-conducting compound applied in the same operation as the insulation. Cold strippable screens are supplied as standard but fully bonded screens may be provided if specified.
4.METALLIC SCREEN
Copper tapes applied overlapped to provide an earth fault current path.
5.BEDDING
Extruded black polyvinyl chloride (PVC) or Low Smoke Zero Halogen (LSOH) compound is supplied as standard. Alternative materials may be provided if specified.
6.ARMOURING
Single layer of circular aluminium wires.
7.OVERSHEATH
Extruded black polyvinyl chloride (PVC) or Low Smoke Zero Halogen (LSOH) compound is supplied as standard. Alternative materials may be provided if specified e.g. medium density polyethylene (MDPE).
MEDIUM VOLTAGE
19000/33000V
Installation Data
Cross-sectional area mm 70 95 120 150 185 240 300 400 500 630 800 1000
Appoximate cable weight kg/m 2.4 2.7 3.1 3.6 4.0 4.7 5.5 6.4 7.6 9.1 Please refer to Please refer to
Nominal drum length m 500 500 500 500 500 500 500 250 250 250 our technical our technical
Minimum bending radius mm 650 650 700 750 750 800 850 900 950 1000 department for department for
Nominal internal diameter of ducts mm 100 100 100 100 100 100 100 100 125 125 further information further information
Electrical Data
Cross-sectional area mm 70 95 120 150 185 240 300 400 500 630 800 1000
Maximum DC resistance of conductor at 20C Ohms/m 268.0 193.0 153.0 124.0 99.1 75.4 60.1 47.0 36.6 28.3 Please refer Please refer
Maximum AC resistance of conductor at 90C Ohms/m 343 248 196 159 128 98 80 64 51 42 to our to our
Reactance at 50Hz Ohms/m 151 143 137 135 130 125 121 116 113 108 technical technical
Impedance at 50Hz Ohms/m 374 285 239 207 181 158 144 132 123 115 department department
Maximum Capacitance pF/m 154 169 183 194 210 229 249 273 298 327 for further for further
Maximum charging current at normal voltage and frequency mA/m 0.92 1.01 1.10 1.16 1.26 1.37 1.49 1.64 1.79 1.96 information information
MEDIUM VOLTAGE
19000/33000V
Current Rating Conditions: Ground Temperature Ambient temperature (air) Depth of burial Thermal resistance of soil 15C 25C 0.8m 1.2C m/W
Ref: BS6622/1C_Cu_33kV/05/10