CT Knee Point Voltage Calculation Sheet

In MVA 20 Primary Secondary Volt Resistance Resistance Length In AMP In kV In ohm In ohm/km in Meter In % 1200 1 13.9 11 6 8.5 120 -

1 2 3 4 5 6 7

CT ratio of the trasformer REF Protection Transformer Rating, MVA % Impedance, %Z Voltage of Line Side, KVLV CT Secondary Resistance, RCT (ohm) Resistance of control cable of 2.5 Sq. mm. Loop Length of Control Cable

Calculation: 1) Fault Current at Primary Side of CT (kA) = MVA/*100(%Z*1.732*KLV) 2) Fault Current at Secondary Side of CT, If (A)= 3) Cable Lead Resistance, RL (Ohm)= 4) Knee Point Voltage Vk (Volt) = 2If(RCT+2RL)

7.55 6.29 1.02 101.2

REMARKS : Knee Point Voltage of CT provided by CGL for REF CT = 115V and for Differental CT = 200V are in order.