Sei sulla pagina 1di 27

TIME AND CURRENT GRADING FOR PROTECTION RELAY TYPE MK1000 & MK2000

MOHAMAD NAIM B. MOHAMAD

This report is submitted in partial fulfillment of the requirements for the Bachelor of Electrical Engineering (Industrial Power)

Faculty of Electrical Engineering Universiti Teknikal Malaysia Melaka

vi

ABSTRACT

The main purpose of this project is to investigate the characteristic time grading and current grading using the inverse definite minimum time (IDMT) protection relay type MK1000 and MK2000.Generally, time grading can be define as the minimum time to carry the fault current before nearest protection relay disconnect the supply in circuit. Current grading can be used to obtain the correct discrimination in the circuit where it will be a large different ratio of fault current to rated current in the network. Meanwhile the other objectives of this project are to develop a proper test procedure for the time grading and current grading. Beside that computer simulation can be done by using the ERACS software in order to verify the testing results. This project also develops the current injection set with using the autotransformers and toroidal core as the main element. The main purpose of this current injection to produce secondary current around 100 ampere. At the end this project, this research can help the student to understand the basic operation time grading and current grading in the operation protection relay especially the IDMT operation in the low voltages system.

vii

ABSTRAK

Tujuan utama projek ini dijalankan adalah untuk mengenal pasti ciri-ciri yang terdapat pada current grading dan time grading yang digunakan dalam pemasangan geganti perlindungan didalam sistem elektrik. Secara umunya current grading dapat diterangkan dengan masa yang diambil paling singkat yang diambil untuk mengesan arus kegagalan didalam sistem sebelum geganti perlindungan yang paling hampir memutuskan bekalan kuasa didalam sistem. Current grading pula boleh digunakan untuk mendapatkan diskriminasi betul dalam sistem di mana arus kegagalan dan arus didalam sistem akan menjadi satu nisbah yang besar. Selain daripada itu, objektif lain projek ini adalah menyiapkan kaedah pengujian yang melibatkan current grading dan time grading. Projek ini juga akan melibatkan penggunaan perisian ERACS dalam membuktikan praktikal dan teori adalah seiring. Selain daripada projek ini juga merekabentuk alat suntikan arus kedua yang akan diguna pakai dalam menjalankan eksperiment nanti. Dalam mereka bentuk alat suntikkan arus kedua, dua kompenen utama akan digunakan iaitu toroidal core dan pengubah automatik. Diakhir projek ini, diharap kajian yang dilakukan ini dapat membantu pelajar untuk lebih memahami tentang current grading dan time grading dalam yang melibatkan sistem perlindungan terutama yang melibatkan geganti jenis IDMT didalam sistem voltan rendah.

CHAPTER I

INTRODUCTION

1.1 Introduction The main purpose of this project is to investigate the characteristic time grading and current grading using the inverse definite minimum time (IDMT) protection relay type MK1000 and MK2000.Generally, time grading can be define as the minimum time to carry the fault current before nearest protection relay disconnect the supply in circuit. Current grading can be used to obtain the correct discrimination in the circuit where it will be a large different ratio of fault current to rate current in the network. Meanwhile, the other objectives of this project are to develop a proper test procedure for the time grading and current grading. Beside that computer simulation can be done by using the ERACS software in order to verify the testing results. This project also develops the current injection set with using the autotransformers and toroidal core as the main element. The main target of this current injection set is to produce secondary current around 100 amperes. At the end this project, this project can help the students to understand the basic of operation time grading and current grading in the operation protection relay especially the IDMT operation in the low voltages system.

1.2 Project Objective. The main purposes of this project are: Analysis characteristic time grading and current grading Simulate the current grading and time grading characteristic for IDMT (inverse definite time minimum) relay type MK1000 & MK2000 Produce 100 ampere current output in secondary current injection set. By using toroidal core and autotransformers as main element.

1.3 Problem Statement. Problem related with the project are: Define the best discrimination by using time or current and both Discriminate the healthy and faulty equipment or the circuit by current, time and both current and time. Define the minimum time interval between time setting of adjacent circuit breaker to prevent the simultaneous operation Define the time grading and current grading characteristics.

1.4 Scope Scopes of this project research are: This project only related 3 phase and single phase (415 and 240) protection system The type protection relay will be use MK1000 and MK2000 Secondary injection test on protection relay with using 100ADM MK 2

1.5 Expected Results The expected results from the project are: Can be define the characteristic time grading and current grading Secondary current injection set can be operate smoothly The simulation results are able to verify the hardware operation when the hardware implemented soon.

CHAPTER II

LITERATURE REVIEW

2.1 Introduction This project research will discuss the principle of coordination protection system in the system. Coordination protection relay can be classified by three types namely discrimination by time, discrimination by current and discrimination current and time or both. The main common aims for the three methods are to give the correct coordinating relay in system. Beside that, the others target of this project research to increase the general knowledge about protection relay such as the circuit breaker, time grading, current grading and utilizing protection relay among the student and fresh engineer especially related with the protection system.

2.2 Relay as Protection Devices Relay has been designed to measure or receive the signal in others word to make it operate or send the signal to another device such as circuit breaker. Protection relay will operate when the abnormal condition occurs in the system and protection relay will provide signal at circuit breaker to trip the circuit. The circuit breaker will open and the fault area will be isolate to minimize fault current. [3]. Nowadays, relay can be classified by three type such as electromechanical, static and microprocessor relay.

Figure 2.1 Basic Relay Electromechanical relay can be dividing into two important parts called as moving and static. When the flow current equal to the setting value, torque will occurs in the moving part and will touch the static part hence the connecter will close and circuit breakers will trip. Electromechanical relay is easy to maintenance and the cost installation is cheaper than others relay.

Figure 2.2 Electromechanical Relay Another relay that based on electromechanically operation is induction relay, attracted-armature relay, movingcoil relay, thermal relay and timing relay. Induction relay have been apply to watt-metric relay, KVAR relay, over current relay and over voltages or under voltages relay. Inductions relay construction based on kilowatt meter. Attracted armature relay construction is based on electromagnet element and it used to connect the armature. Induction relay normally use as all-or-nothing relay and measurement relay. Thermal relay is operated based on the heat. Thermal relay has been used as an overload relay because it has more accuracy and has a long delay time. Timing relay is using in protection system and can be classified into three groups such as short circuit relays, medium-value accurate-time delays and long time relays. Static relay is usually using in electronic equipment. This relay use electronic circuit as a base circuit to operate. Static relay was used in power protection circuit because it can protect the sensitive equipment from fault current. However this relay is more expensive than electromechanical relay. Beside that, it is easy to maintenance and has the long live time.

Figure 2.3 Block Diagram Static Relay [4]

Figure 2.4 Block Diagram Microprocessor Relay [5] Relay based on microprocessor is a relay where using the software and operate based on binary code. The different of this relay is programming has been used and the basic concept from the conventional relay has been changed for comparison and the binary code. Relay type microprocessor can store the fault of data that already happened previously.

2.3 Protection System with using Single Processor for Low Voltages

Single Processor is use the network of communication system. This network functions to analyze data from equipment by separate. All data will send to main computer. In this network, main computer will send the signal to the devices and finally the signal has been prescribed by protocol. System communication type Ethernet include protocol collision-detection multiple-access (CSMA/DA) has been used in this system. [4].This concept was operating by sending data from the device to main processor. The sending data include the voltage, current and devices status. In the network, microprocessors will used to analyze data and make the decision related to the system. The advantage of this system is the processor can detect all information related to the system. Protection system and controller was design depend on electrical signal like current magnitude and phase angle. As a conclusion this system has a lot of advantages on protection system where the extra protection to feeder device through the main device on current executioner without affects the system.

2.4 Discrimination by Time Discrimination by time is the basic idea to add time lag features to control the relays of the number circuit breaker in the protection system. Discrimination by time can be defined as the nearest circuit breaker to the fault will operate first. The minimum time interval between time settings of adjacent circuit will be considering before setting the time to prevent the simultaneous operation [1].The minimum time interval is required to the breaker to clear the fault in the system. Besides, the minimum time interval setting must be match with the relay and the current transformers (CT) [1]. Discrimination by time has a big problem where the problem occurred from discrimination by time will increase in time fault clearance. The time will be increase if the fault occurs closed at the power source especially when MVA rating value is highest. [2]

Figure 2.5 Radial Systems with Time Discrimination The figure shows the system been provided at the circuit breaker for each section L, K, J, and H in the feed of the power system. Each protection system have been comprises by inverse definite minimum time (IDMT) over-current relay in which the operation of the current sensitive element simply initiates the time delay element. Provide the current element is setting below the fault current where this element plays the no part in the achievement of the discrimination. It is because the relay sometimes described as an independent definite time delay relay since its operating time is for practical purposes independent of the level of over-current. It is time delay element therefore which provides the means discrimination. The relay at zone H is set at the shortest time delay permissible to allow a fuse to blow for a fault on the secondary side of transformer at zone G.

2.5 Discrimination by Current Discrimination by current relies on the fact that the fault current varies with the position of the fault. To discriminate by current the value of impedance must be considered. Relay in the system was controlling the various circuit breaker where are set to operate at suitable tapered values such as nearest relay at the fault to trip the breakers [1].Discrimination by current is not practical this because the impedance between two circuit breaker must be concern to get the correct coordination[2] 2.6 Discrimination by both Current and Time

10 Discrimination by current and time is combination by current and time where the time is inversely proportional to the faulted current level and the actual characteristic is a function of both current and time setting [1].For example when the faulted current is high level the circuit breaker will take the shortest time to clearance the fault current in the system. It will be more efficient. In order to carry out a system analysis before relay coordination all impedance must be calculate. Discrimination by both is the best way in relay coordination relay in the system.

2.7 Summary In this has been discussing basic operation of relay as protection device. Beside that, these chapters also discuss the coordination the relay in systems. Before coordination relay is applied to the system, we must know the basic discrimination for the system. Discrimination can be classified by three ways, co-ordination by time, and current, both.

CHAPTER III

THEORY

3.1 Introduction Power system has been used to supply the electrical energy to customer with efficient and the energy called as a burden. It has two main components called as real power and reactive power during the sending of electrical at home. This energy was delivered by used the transmission line. The power system was provided to the customer by using three phase system and single system depends on their load. In Malaysia, Suruhanjaya Tenaga had decided where the power factor is 0.85 to each customer. During the electrical installation the contractor has considered the voltage drop, current, cost, protection system and the load that will be used in the future. Electrical installation in industry and the building that using a lower voltage 415 V need a matching design. Each design is refer to the safety aspect, practical, effective cost, efficient and follow each rules has been decided by government.

12

TNB Substation 11KV Underground Cable Electric Substation 415V Underground Cable Main Switch Board 415V Underground Cable & Cable in Building Small Switch Board 415V/240 V PVC Or PVC/PVC Cable DB Board 415V/240 V PVC Or PVC/PVC Cable Load

Figure 3.1 Low Voltage Distributions Systems

13

3.2 Faults in Electric System In the electric system, fault will obtained at the point in the power system or equipment. The fault can be divided into several types and the fault can destroyed the system, equipment and user. Three phase fault - short circuit among the three phase supply or fault among three phases with the earth. Fault line to earth short circuit between phases with the earth. Fault line to line short circuit among two phases line. Fault two lines with the earth short circuit among two phases with earth.

3.3 Protection Relay Protection relay is devices that use to measure the level of damage that happen in the system. Beside that, the protection relay also used to control the operation of the circuit breaker. If the leakage of current occurred in the circuit for a short or temporary time, the protection relay will send the signal to circuit breaker. If over current or the earth leakage occurs during the same time and this situation can damage the system and equipment, protection relay will send the signal to circuit breaker to operate.

14

3.4 Relay Coordination Coordination was indicated in protection system and relay coordination. Correct current relay application requires knowledge of the fault current that flow in each part on of the network. Since large scale impracticable, system analysis must be used. The data requires for a relay setting study are [1]: A one line-diagram of the power system involved, showing the type and rating of the protective devices and their associated current transformers. The impedances in ohm, percent or per unit of all power transformers, rotating machines and feeder circuits The maximum and minimum values of the short circuits current that are expected to flow through each protective device. The starting current requirement of motor and the starting and stalling time of induction motors. Maximum peak load current through protective devices Decrement curves showing the rate of decay of the fault current supplied by the generators Performances curves of the current transformers.

Relay coordination use in relay installation by using the discrimination concept. The basic rules for correct relay coordination are: Use same relay operating characteristic in series for each others. Ensure the relay farthest from the source has current setting equal to or less than relays behind, that the primary current required to operate the relay in front is equal to or less than the primary current required to operate relay behind it.

15 Discrimination concept can be explained by the nearest relay where the fault zone will operate first and separated the circuit to smallest fault zone. By using discrimination concept, the fault occurs in shortest time hence the system and the user will be avoided from the accident. Discrimination can be achieved by three ways: Discrimination by time Discrimination by current Discrimination by both (current and time)

The main purpose of the discrimination is to give the correct discriminating with protection relay installation in the system.

3.4 Inverse Definite Minimum Time (IDMT) Protection Concept Inverse time means when the current increase, time will be decrease. It can be achieved by the current in the circuit is high the protection relay will take the shortest time to operate. Definite Minimum Time can be explain when the fault current is high, the protection relay will take shortest time to operate and the protection relay has a fixed time depend on the time delay setting.

Fi g e ur

3.2 IDMT Construction

16

3.5 Determine the size of bus bar comply with the current rate

However if the busbar sizes are not specified, then the busbar rating shall be based on a current density of not more than 1.5 A/sq. mm. in nay case, the busbar rating shall not be less than the rating of the incoming switchgear. All busbar either horizontal or vertical shall be of the same size. The main busbar shall be run for the full length of the switch board without reduction in size. . Neutral busbar shall be full size and full length as the phase busbars. The main busbar shall be arranged in horizontal plane in the order red-yellow-blue-neutral from back to front on each panel connections should be red-yellow-blueneutral TABLE 3.1 Bus Bars Rating Busbar Size (mm x mm) 6.3 x 40 6.3 x 50 6.3 x 63 6.3 x 70 6.3 x 80 6.3 x 90 6.3 x 100 2 x 6.3 x 63 2 x 6.3 x 80 Current Rating (A) 400 500 600 700 800 900 1000 1200 1600

17

3.6 Fault Current When the current is over the rating it can be define as over current. For the conductor, the rating values depend on the capacity value to conduct the current. This value can be obtained from the nominal value or setting value on current protection devices. Over current can be divided into over current on the load and current damage.

3.7 Element Low- Set Normal Curve

Figure 3.3 Normal

Inverse Curves

18 Characteristic curve setting depends on normal inverse because this protection relay can be used for the low voltage protection. This situation allowed the circuit breaker in series each others in the system. The setting time at the others protection relay on the system. There are no special coordination requirements compared with other types of protective equipment farther out on the system. The fault level at the near and far ends of the system does not vary significantly.
0.14 Time equation (t) = If 1 Iset

3.8 IDMT in Distribution System This topics will presents the application of the overcurrent protection in distribution systems with inverse definite minimum time (IDMT) setting in distribution system. Where in this topic will discuss the operation inverse definite minimum (IDMT) typical in ring main distribution system with IDMT time grading based protection scheme. Overcurrent protection is earliest protection principle, has been playing a dominant role in power distribution system protection since the beginning of last century. The overcurrent principle based on the time-graded protection scheme has such shortcomings where the relay located near to source has longest operating time setting, where the fault level is the highest [1]. The maximum tripping time is might be longer to prevent excessive disturbance of the power system. In addition, the tripping can only be made at one end (the source end) of the protected line section for radial connected line or open ring systems.

19

Figure 3.4 Basic Ring Systems in Distribution In the system the protection relay R1, R2, R3, R4, R5, R6, R7 and R8 has been installed in multi-section ring main power cable system in the line C-1, C-2, C-3 and C-4 respectively. B1, B2, B3, B4, B5, B6, B7 and B8 in the system function as are circuit breakers. The BUS B, BUS C and BUS D in system have been connected to the load in the system on each cable section.

Figure 3.5 Clockwise grading

20 of IDMT relay

Figure 3.6 Anticlockwise grading of IDM relay From the graph, we can see the relays R1 and R8 have the longest operating time to clear the fault. It because the relay installed near sources have longest operating times in the section to protect the faults current in such sections will have the highest current levels which can only be allowed to persist for short periods. Even though it is easy to select the operating times needed to ensure the correct discrimination when relays with definite time lags are used, but it have the weakness where it must be used restricted to networks with relatively few series connected sections. From the graph it can be concluded that the relay R2, R4, R7 and R5 is setting for high operating time and R1, R3, R6 and R8 is setting for the lower operating time. In the ring system at above, the protection relay has been divided by two groups directional where the relay has been operated in clockwise operation and anticlockwise operation. In the system, relay R1, R3, R5 and R7 will operate in clockwise directional and R2, R4, R6 and R8 will operate in anticlockwise directional to protect the system when the fault occurs. As a example, if the fault occurring on cable section C-1, the directional relays R1, R2, R4, R6 and R8 will detect the fault since the fault is in the forward direction to these relays and relay R2 will operated where it has been setting the

21 fastest time where the R2 will operate first to open its connected circuit breaker B2. The opening of the circuit breaker B2 means that the fault is on the protected cable section C-1, and R1 will accelerated trip it associated circuit breaker B1 and isolate the faulted cable section C-1.Circuit breaker B2 will isolate the fault from cable sections C-2, C-3 and C-4 to protect the equipment. However, if the circuit breaker B2 does not clear the fault on the section C-1, the relay R1 will start to detect the system balanced condition and the signals will send to determine the operation performed by the isolated circuit breaker. When a fault occurs on section C-2, the protection relays R1, R3, R4, R6 and R8 will detect the fault. The relay R4 which has the fastest time setting curve in the group will operate first to trip its connected circuit breaker B4.The circuit breaker B4 will operated, where the fault will be isolated from cable sections C-3 and C-4, and relays R6 and R8 will restrain from operation and if circuit breaker B4 does not clear the fault on the cable sections C-1 and C-2. The relays R1 will change its operation mode from accelerate to inverse definite minimum time (IDMT) time operation since it fails to detect the operation of the remote circuit breaker R3 within the time interval of 0.3s. This would be the time period from the tripping of the relay R3 to the opening of the circuit breaker B3 if a fault is detected on C-1. The relay R3, however, detects the operation of the circuit breaker B4 using the new technique after a fixed time delay of 0.3s and accelerated trips its associated circuit breaker B3 to isolate the faulted cable section C-2. At the same time, the fault is also isolated from section C-1, which enables the relay R1 to restrain. Again, the operating speed of relay R3 is significantly increased in this case

22

3.9 Transformers This topic will discuss the criteria of power transformers construction where the power transformer has been used to produce the current until 100 ampere. Today transformers are important devices in electrical engineering. Actually, a transformer is a device that changes ac electric power at one voltage level through the action of a magnetic field. It consists of two or more coil of wire wrapped around a common ferromagnetic core [Chapman]. A transformer is consisting of two coils that are electrically isolated from each others but are wound on same magnetic core. The coil to which the source supplies the power is called primary winding. The coil that delivers power to the load is called the secondary winding. Either the winding may be connected to source or the load. Basic formula for transformers can be defined as:
Is V p Np = Ip = V s Ns

Where P is referring to primary side and S is refer to secondary side. Today transformers came in all shapes and size. Transformers can be defined by various types in the industry today. Generator Transformers Power Transformers Distribution Transformers Pole-Mounted Lighting Transformers Grounding Transformers Regulating Transformers Welding Transformers Converter Transformers Instrument Transformers (CT and PT)

23

Some of the transformers at above could be autotransformers. However, this chapter is more focusing on power transformers where power transformer has been used to produce the current until 100 ampere. The purpose of a transformer is to convert ac power at one voltage level to ac power of the same frequency at another voltage level. Transformer also used for variety of the other purpose.

Figure 3.7 Core-form transformers construction Power transformers are constructed on one of two types of core. One type of construction consists of a simple rectangular laminated piece of steel with the transformer winding wrapped around two side of the rectangle. This type of constructions is known as core form. The other type consists of a three-legged laminated core with the winding wrapped around the center leg. This type of construction is known

24 as shell form. The main purpose of thin lamination electrically isolated from each other in order to minimize eddy current.

Figure 3.8 Shell-form transformers

Figure 3.9 The Hysteresis Curve of the Transformers [4]

Potrebbero piacerti anche