local controller provides extra safety with lower installation costs switch controller increases flexibility of emergency lighting control

local controller

extra safety with lower installation costs


Local Controller monitors the local mains supply, and controls the centrally supplied emergency luminaires. It provides two remarkable advantages: Local voltage breakdown switches on the non-maintained emergency luminaires, even if the supply to the central battery unit remains. Both maintained and non-maintained emergency luminaires can be connected to the same circuit. This eliminates separate cabling for maintained and nonmaintained luminaires. The Local Controller is compatible with all Teknoware central battery units with 230 VAC/DC output. The non-maintained luminaires shall be of Teknoware type which have the type code ending -K or -T, or they shall be fitted with a compatible address module.

ts90686 and ts90696


160

The Local Controller is connected to the emergency supply cabling between the central battery unit and luminaires. Its monitoring inputs are connected to the mains supply of the local general lighting, and it can monitor up to 3 phases independently. If any of the monitoring inputs detect supply failure, the Local Controller sends a message via supply cable to the non-maintained luminaires and they switch themselves on. When the supply recovers, the normal operation returns automatically. The Local Controller types TS90695/TS90696 have additionally a switch control input and potential free relay contact output for external control. They include also an adjustable 1-15 min delay for return to mains operation. The non-maintained luminaires detect also the situation where the central battery unit turns to battery mode. In this situation the non-maintained luminaires are switched on regardless of the status of The Local Controller.
71

81

81

201

160

121

ts90695
117

ts90685
117

38

38

70

60

107 117

107 117

technical data
TS90685 Installation Input voltage IP-classification Features Inside a distribution board 230 V AC/DC IP20 3-phase monitoring, controlling the non-maintained luminaires through the supply cabling TS90686 Box enclosure for independent installation TS90695 Inside a distribution board 230 V AC/DC IP20 3-phase monitoring, controlling the non-maintained luminaires through the supply cabling, switch control input, relay contact output, adjustable 1-15 min delay for return to mains operation TS90696 Box enclosure for independent installation

switch controller

increases flexibility of emergency lighting control


Switch Controller TST28xx enables a simple arrangement where the centrally supplied emergency luminaires can be used for general lighting in normal mode. An ordinary light switch or timer controls luminaires. TST28xx is compatible with all Teknoware central battery systems with 230V output, and it can be used together with the Local Controller TS906xx as well. In normal mode the luminaires take their supply from the light switch. When the central battery unit turns to emergency mode, the emergency luminaires are automatically switched over to emergency supply, regardless of the position of the light switch. The same applies also when the Local Controller sends and information of a local supply failure. Switch Controller has also a dimming control output, which can be used to dim the light during emergency mode. The control output is compatible with electronic ballasts having a 1-10V dimming control input according to IEC 60929.

ts2800

ts2801
160

60 81 107 117 201 38 71 160 121 81

technical data
TS2800 Installation Input voltage Inside a distribution board 230 V AC/DC TS2801 Box enclosure for independent installation 230 V AC/DC IP20

IP-classification IP20

system cabling
local controller
Example of cabling: Supply of general lighting

When system has Local Controller maintained and non-maintained luminaires can be connected to to the same circuit.

Local Controller

Physical space

Teknoware central battery unit


L N PE Output circuit

Green = maintained luminaire *

Yellow= non-maintained luminaire **

* maintained = luminaire is on all the time ** non-maintained = luminaire is on only during supply failure

switch controller
Example of cabling:

Switch Controller

Supply from light switch of general lighting

Teknoware central battery unit, 230 V


L N PE Output circuit

Yellow = light switch controlled emergency light

Light switch controlled emergency lights use normally the supply from the light swich of general lighting. During a power failure emergency lights use the supply from central battery unit. Switch Controller is compatible with Local Controller.